35
Smart valve positioner
TS800/TS805 Series
tissin
6.5 Main menu description
After the product is booted,
<MAIN LIN>
is displayed, which shows the current opening of the
valve. Press
<UP>
or
<DOWN>
button to move to the following menu and check the
corresponding information.
In Main menu, information such as the valve opening and the magnitude of the input current
signal can be checked and the execution of the command or the modification of the
parameter value cannot be performed.
Main menu
Description
MAIN LIN
Displayed the percentage of current valve opening value.
Depending on the set value of the flow characteristics, one of the
following values is displayed.
LCD display value
Flow characteristics
MAIN LIN
Linear
MAIN EQ1
EQ1 (1/25)
MAIN EQ2
EQ2 (1/50)
MAIN QO
Quick Open
MAIN USR
User defined 17 points
MAIN IN %
Displayed the magnitude of input signal that the positioner recognizes
as percentage.
If the size of the input signal recognized by the positioner differs
from output signal of the DCS or calibrator, check the voltage of
the power supply.
If the supply current is normal, please reset <
IN ZERO
> and <
IN
END
> values in <
TUNING
> of main parameter.
MAIN IN mA
Displayed the magnitude of input signal that the positioner recognizes
as mA
.
If the size of the input signal recognized by the positioner differs
from output signal of the DCS or calibrator, check the voltage of
the power supply.
If the supply current is normal, please reset <
IN ZERO
> and
<
IN END
> values in <
TUNNING
> of main parameter.
MAIN VEL
Displayed currently operating speed of the valve as numbers.
As the value, between -2047 to +2048, negative numbers
indicate speed at close, and positive numbers indicate speed at
open.
0 means stop and
the larger the absolute value, the faster the
speed.
MAIN DEV %
Displayed the percentage of error between the current input signal
and valve opening value.
The larger the error, the lower the control characteristic.