21
Smart valve positioner
TS800/TS805 Series
tissin
3.4 TS820 Remote type installation
The TS820 is designed cable to the sensor part and the main body,
it is designed to transmit
the change of the stem position of the valve to the body through the potentiometer built in the
sensor.
Application site
Where the valve is located at a high or inaccessible location.
High temperature environment. (Over than 85°degrees)
Large vibrating lines.
Installation
①
Install the sensor part on the valve, and install Main body on the accessible places.
②
Please follow the installation instructions of TS800L or TS800R for the sensor part’s
installation.
③
The sensor part and Main body are connected via cable, the length of cable must not
over 20M.
④
Pneumatic piping should connect the OUT port of Main body to the actuator.
①
Sensor part
②
Main body
③
Cable
④
Entry power cable
⑤
OUT1 piping