48
Smart valve positioner
TS800/TS805 Series
tissin
6.7.6 EMERGNCy
Submenu
Description
PASSWORD
Must put a password to enter this menu.
The password is set at the factory and cannot be changed by the user.
Factory setting
Press
UP > ENTER > DOWN > UP
button
sequentially. (1321 on LCD)
EMGY NON
Set the position of the valve to be moved when an abnormality of the
positioner is detected. (If priority value of error code is “0”
)
(refer to page 51)
Mode
EMGy NON
Do not take any action.
EMGy OP
Open the valve fully.
EMGy CL
Close the valve fully.
EMGy STP
Stop the valve operation.
Factory setting
EMGy NON
FULL OP
Open the valve fully by manual
regardless of the input signal
.
FULL CL
Close the valve fully by manual
regardless of the input signal
.
STOP
Maintain the present valve position regardless of the input signal.
UNLOCK
It locks to prevent changing all parameter values.
When set to “
LOCK
”, all commands such as Auto calibration, PID changes,
and parameter values settings cannot be changed.
Mode
LOCK
Lock the program
UNLOCK
Unlock the program
Factory setting
UNLOCK