10
Smart valve positioner
TS800/TS805 Series
tissin
2.7 Specifications
Model
TS800
TS805
Input signal
4~20mA DC
Impedance
500Ω (20mA DC)
Supply pressure
0.14~0.7MPa
Stroke
10~150mm(Linear type), 0~90
0
(Rotary type)
Air connection
PT1/4, NPT1/4
NPT1/4
Gauge connection
PT1/8, NPT1/8
NPT1/8
Conduit
G(PF)1/2, NPT1/2, M20
G1/2
Explosion proof type
II 2G Ex ia IIC T5/T6 Gb
II 2D Ex ia IIIC T100
℃
/85
℃
Db IP6X
Enclosure
IP66 (EN60529)
Ambient
Temp.
Acting Temp.
-30
℃∼+
85
℃
(Standard type),
-40
℃∼+
85
℃
(Low temp type)
Explosion proof
Temp.
-40
℃
~ +60
℃
(T5) / -40
℃
~ +40
℃
(T6)
Linearity
±0.5% F.S.
Sensitivity
±0.2% F.S
Hysteresis
±0.5% F.S
Repeatability
±0.3% F.S
Air consumption
Below 2.3LPM (Sup.=0.14MPa)
Required air quality
Class 3 (ISO8573-1)
Flow capacity
Over 100LPM (Sup.=0.14MPa)
Material
Aluminum die cast
Stainless steel 316
Weight
2.2kg
4.2kg
Option specifications
Option
Item
Specification
HART
HART version
HART 7
Position transmitter
Wire connection type
2 Wires
Supply voltage
10~30V DC
Limit switch
Mechanical type
AC125V, 3A, DC30V, 2A
Proximity type
DC8.2V 8.2A
Note
: Please contact our sales department for other specifications.