APPENDIX
121
NV021 - Manual - 08 - 2012
DESCRIPTION
PARAMETER
UNIT
SETTING RANGE
State
OFF | ON
Pickup value
Hz/s
0.1 ... 10.0 step = 0.1
df>>>>def Operating time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Trip circuit supervision - 74TCS
74TCS Enable
74TCS Enable
OFF | ON
74TCS Logical block
74TCS-BLK1
OFF | ON
74TCS Start relays
74TCS-ST-K
K1 | K2 | K3 | K4 | K5 | K6
74TCS Trip relays
74TCS-TR-K
K1 | K2 | K3 | K4 | K5 | K6
74TCS Start LEDs
74TCS-ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5
74TCS Trip LEDs
74TCS-TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5
Breaker failure - BF
BF Enable
BF Enable
OFF | ON
BF Time delay
Value
s
0.06 ... 10.00 step = 0.01
BF Logical block
BF-BLK1
OFF | ON
BF Start relays
BF-ST-K
K1 | K2 | K3 | K4 | K5 | K6
BF Trip relays
BF-TR-K
K1 | K2 | K3 | K4 | K5 | K6
BF Start LEDs
BF-ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5
BF Trip LEDs
BF-TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5
Profi le B
Thermal protection with RTD thermometric probes - 26
PT1 Probe
ThAL1 Alarm
ThAL1 Enable
ThAL1 Enable
OFF | ON
26 PT1 Alarm threshold
ThAL1
°C
0 ... 200 step = 1
ThAL1 Operating time
Value
s
0 ... 100 step = 1
ThAL1 Alarm relays
ThAL1-K
K1 | K2 | K3 | K4 | K5 | K6
ThAL1 Alarm LEDs
ThAL1-L
START | TRIP | L1 | L2 | L3 | L4 | L5
Th>1 Trip
Th>1 Enable
Th>1 Enable
OFF | ON
26 PT1 Trip threshold
Th>1
°C
0 ... 200 step = 1
Th>1 Operating time
Value
s
0 ... 100 step = 1
Th>1 Breaker failure
Th>1BF
OFF | ON
Th>1 Trip relays
Th>1-K
K1 | K2 | K3 | K4 | K5 | K6
Th>1 Trip LEDs
Th>1-L
START | TRIP | L1 | L2 | L3 | L4 | L5
PT2 Probe
ThAL2 Alarm
ThAL2 Enable
ThAL2 Enable
OFF | ON
26 PT2 Alarm threshold
ThAL2
°C
0 ... 200 step = 1
ThAL2 Operating time
Value
s
0 ... 100 step = 1
ThAL2 Alarm relays
ThAL2-K
K1 | K2 | K3 | K4 | K5 | K6