![Thytronic NV021 Скачать руководство пользователя страница 114](http://html.mh-extra.com/html/thytronic/nv021/nv021_manual_1113995114.webp)
114
NV021 - Manual - 08 - 2012
APPENDIX
DESCRIPTION
PARAMETER
UNIT
SETTING RANGE
Setpoints
U< Enable
U< Enable
OFF | ON
U< Curve type
U<Curve
INVERSE | DEFINITE
U< Logical block
U<BLK1
OFF | ON
U< Breaker failure
U<BF
OFF | ON
U< Start relays
U<ST-K
K1 | K2 | K3 | K4 | K5 | K6
U< Trip relays
U<TR-K
K1 | K2 | K3 | K4 | K5 | K6
U< Start LEDs
U<ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5
U< Trip LEDs
U<TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5
Defi nite time
27 First threshold defi nite time
State
OFF | ON
Pickup value
Un
0.05 ... 1.10 step = 0.01
U<def Operating time
Value
s
0.03 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Inverse time
27 First threshold inverse time
State
OFF | ON
Pickup value
Un
0.05 ... 1.10 step = 0.01
U<inv Operating time
tU<inv
s
0.10 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
U<< Element
Setpoints
U<< Logical block
U<<BLK1
OFF | ON
U<< Breaker failure
U<<BF
OFF | ON
U< Disabling by U<< start
U<disbyU<<
OFF | ON
U<< Start relays
U<<ST-K
K1 | K2 | K3 | K4 | K5 | K6
U<< Trip relays
U<<TR-K
K1 | K2 | K3 | K4 | K5 | K6
U<< Start LEDs
U<<ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5
U<< Trip LEDs
U<<TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5
Defi nite time
27 Second threshold defi nite time
State
OFF | ON
Pickup value
Un
0.05 ... 1.10 step = 0.01
U<<def Operating time
Value
s
0.03 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Positive sequence undervoltage - 27V1
U1< Element
Setpoints
U1< Logical block
U1<BLK1
OFF | ON
U1< Breaker failure
U1<BF
OFF | ON
U1< Start relays
U1<ST-K
K1 | K2 | K3 | K4 | K5 | K6
U1< Trip relays
U1<TR-K
K1 | K2 | K3 | K4 | K5 | K6
U1< Start LEDs
U1<ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5