116
NV021 - Manual - 08 - 2012
APPENDIX
DESCRIPTION
PARAMETER
UNIT
SETTING RANGE
Pickup value
Un
0.50 ... 1.50 step = 0.01
U>>def Operating time
Value
s
0.03 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Average overvoltage - 59Uavg
Common confi guration
59Uavg Operating logic
Logic59Uavg
OR | AND
Uavg> Element
Setpoints
Uavg> Enable
Uavg> Enable
OFF | ON
Uavg> Logical block
Uavg>BLK1
OFF | ON
Uavg> Breaker failure
Uavg>BF
OFF | ON
Uavg> Start relays
Uavg>ST-K
K1 | K2 | K3 | K4 | K5 | K6
Uavg> Trip relays
Uavg>TR-K
K1 | K2 | K3 | K4 | K5 | K6
Uavg> Start LEDs
Uavg>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5
Uavg> Trip LEDs
Uavg>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5
Defi nite time
59Uavg First threshold defi nite time
State
OFF | ON
Pickup value
Un
0.50 ... 1.50 step = 0.01
Uavg>def Delay time
Value
s
0 ... 1000 step = 1
Negative sequence overvoltage - 59V2
U2> Element
Setpoints
U2> Logical block
U2>BLK1
OFF | ON
U2> Breaker failure
U2>BF
OFF | ON
U2> Start relays
U2>ST-K
K1 | K2 | K3 | K4 | K5 | K6
U2> Trip relays
U2>TR-K
K1 | K2 | K3 | K4 | K5 | K6
U2> Start LEDs
U2>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5
U2> Trip LEDs
U2>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5
Defi nite time
59V2 First threshold defi nite time
State
OFF | ON
Pickup value
Un
0.01 ... 0.50 step = 0.01
U2>def Operating time
Value
s
0.07 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Overfrequency - 81O
f> Element
Setpoints
f> Logical block
f>BLK1
OFF | ON
f> Breaker failure
f>BF
OFF | ON
f> Start relays
f>ST-K
K1 | K2 | K3 | K4 | K5 | K6
f> Trip relays
f>TR-K
K1 | K2 | K3 | K4 | K5 | K6
f> Start LEDs
f>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5