APPENDIX
DESCRIPTION
PARAMETER
UNIT
SETTING RANGE
df> Element
Setpoints
df> Operating mode
Mode-df>
Module | Positive | Negative
df> Logical block
df>BLK1
OFF | ON
df> Breaker failure
df>BF
OFF | ON
df> Start relays
df>ST-K
K1 | K2 | K3 | K4 | K5 | K6
df> Trip relays
df>TR-K
K1 | K2 | K3 | K4 | K5 | K6
df> Start LEDs
df>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5
df> Trip LEDs
df>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5
Defi nite time
81R First threshold defi nite time
State
OFF | ON
Pickup value
Hz/s
0.1 ... 10.0 step = 0.1
df>def Operating time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
df>> Element
Setpoints
df>> Operating mode
Mode-df>>
Module | Positive | Negative
df>> Logical block
df>>BLK1
OFF | ON
df>> Breaker failure
df>>BF
OFF | ON
df> Disabling by df>> start
df>disbydf>>
OFF | ON
df>> Start relays
df>>ST-K
K1 | K2 | K3 | K4 | K5 | K6
df>> Trip relays
df>>TR-K
K1 | K2 | K3 | K4 | K5 | K6
df>> Start LEDs
df>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5
df>> Trip LEDs
df>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5
Defi nite time
81R Second threshold defi nite time
State
OFF | ON
Pickup value
Hz/s
0.1 ... 10.0 step = 0.1
df>>def Operating time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
df>>> Element
Setpoints
df>>> Operating mode
Mode-df>>>
Module | Positive | Negative
df>>> Logical block
df>>>BLK1
OFF | ON
df>>> Breaker failure
df>>>BF
OFF | ON
df> Disabling by df>>> start
df>disbydf>>>
OFF | ON
df>> Disabling by df>>> start
df>>disbydf>>>
OFF | ON
df>>> Start relays
df>>>ST-K
K1 | K2 | K3 | K4 | K5 | K6
df>>> Trip relays
df>>>TR-K
K1 | K2 | K3 | K4 | K5 | K6
df>>> Start LEDs
df>>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5
df>>> Trip LEDs
df>>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5
Defi nite time
81R Third threshold defi nite time