![Thytronic NV021 Скачать руководство пользователя страница 124](http://html.mh-extra.com/html/thytronic/nv021/nv021_manual_1113995124.webp)
124
NV021 - Manual - 08 - 2012
APPENDIX
DESCRIPTION
PARAMETER
UNIT
SETTING RANGE
ThAL8 Enable
ThAL8 Enable
OFF | ON
26 PT8 Alarm threshold
ThAL8
°C
0 ... 200 step = 1
ThAL8 Operating time
Value
s
0 ... 100 step = 1
ThAL8 Alarm relays
ThAL8-K
K1 | K2 | K3 | K4 | K5 | K6
ThAL8 Alarm LEDs
ThAL8-L
START | TRIP | L1 | L2 | L3 | L4 | L5
Th>8 Trip
Th>8 Enable
Th>8 Enable
OFF | ON
26 PT8 Trip threshold
Th>8
°C
0 ... 200 step = 1
Th>8 Operating time
Value
s
0 ... 100 step = 1
Th>8 Breaker failure
Th>8BF
OFF | ON
Th>8 Trip relays
Th>8-K
K1 | K2 | K3 | K4 | K5 | K6
Th>8 Trip LEDs
Th>8-L
START | TRIP | L1 | L2 | L3 | L4 | L5
Diagnostic
PT100 probe diagnostic relays
PT100Diag-K
K1 | K2 | K3 | K4 | K5 | K6
PT100 probe diagnostic LEDs
PT100Diag-L
START | TRIP | L1 | L2 | L3 | L4 | L5
Undervoltage - 27
Common confi guration
27 Operating logic
Logic27
OR | AND
U< Element
Setpoints
U< Enable
U< Enable
OFF | ON
U< Curve type
U<Curve
INVERSE | DEFINITE
U< Logical block
U<BLK1
OFF | ON
U< Breaker failure
U<BF
OFF | ON
U< Start relays
U<ST-K
K1 | K2 | K3 | K4 | K5 | K6
U< Trip relays
U<TR-K
K1 | K2 | K3 | K4 | K5 | K6
U< Start LEDs
U<ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5
U< Trip LEDs
U<TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5
Defi nite time
27 First threshold defi nite time
State
OFF | ON
Pickup value
Un
0.05 ... 1.10 step = 0.01
U<def Operating time
Value
s
0.03 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Inverse time
27 First threshold inverse time
State
OFF | ON
Pickup value
Un
0.05 ... 1.10 step = 0.01
U<inv Operating time
tU<inv
s
0.10 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
U<< Element
Setpoints
U<< Logical block
U<<BLK1
OFF | ON