197
NC20 - Manual - 01 - 2015
APPENDIX
197
NC20 - Manual - 01 - 2015
APPENDIX
Description
Parameter Unit
Setting range
I2> Output selective block
I2>BLK2OUT
OFF | ON
I2> Breaker failure
I2>BF
OFF | ON
I2> Start relays
I2>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
I2> Trip relays
I2>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
I2> Start LEDs
I2>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
I2> Trip LEDs
I2>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Defi nite time
46 First threshold defi nite time
State
OFF | ON
Pickup value
%
1 ... 150 step = 1
I2>def within CLP
I2CLP>def
%
1 ... 150 step = 1
I2>def Operating time
Value
s
0.05 ... 9.99 step = 0.01
10.0 ... 60.0 step = 0.1
I2>> Element
Setpoints
I2>> Enable
I2>> Enable
OFF | ON
I2CLP>> Mode
I2CLP>> Mode
OFF | ON - Element blocking | ON - Change setting
I2CLP>> Activation time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
I2>> Reset time delay
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
I2>> Logical block
I2>>BLK1
OFF | ON
I2>> Input selective block
I2>>BLK2IN
OFF | ON
I2>> Output selective block
I2>>BLK2OUT
OFF | ON
I2>> Breaker failure
I2>>BF
OFF | ON
I2> Disabling by I2>> start
I2>disbyI2>>
OFF | ON
I2>> Start relays
I2>>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
I2>> Trip relays
I2>>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
I2>> Start LEDs
I2>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
I2>> Trip LEDs
I2>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Defi nite time
46 Second threshold defi nite time
State
OFF | ON
Pickup value
%
1 ... 150 step = 1
I2>>def within CLP
I2CLP>>def
%
1 ... 150 step = 1
I2>>def Operating time
Value
s
0.05 ... 9.99 step = 0.01
10.0 ... 60.0 step = 0.1
Neutral unbalance current - 46N
IN>AL Element
Setpoints
IN>AL Enable
IN>AL Enable
OFF | ON
INCLP>AL Mode
INCLP>AL Mode
OFF | ON - Element blocking | ON - Change setting
INCLP>AL Activation time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN>AL Logical block
IN>ALBLK1
OFF | ON
IN>AL Start relays
IN>ALST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
IN>AL Trip relays
IN>ALTR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10