background image

124

124

NC20 - Manual - 01 - 2015

FUNCTION CHARACTERISTICS

One input supervision

By means of the right sizing of a resistor, the trip circuit supervision may be performed even with 

lower control voltage  (e.g. when the control voltage is less than 36 V required for driving of two 
binary inputs, typically 

U

AUX 

= 24V).

The binary input is connected to the trip and an external resistor must be connected the 52b auxiliary 

contact

.

The fault condition of the trip circuit is detected by binary input power down.

With healthy circuit and TRIP contact closed, the binary input is feed across the 52a path (CB closed) 
or across the resistor R and 52b path (CB open).
When the TRIP contact turns ON, the binary input becomes short-circuited; to avoid untimely opera-
tions the previous condition are  checked every 80 ms and the output is issued after a 40 s delay in 
order to allow the fault clearing and the consequent reset of the TRIP protection. 
Outputs are reset to zero after 6 s from the TRIP contact open.

[1]

Note 1 The trip contact (TRIP) of the protection relays must be set with automatic reset (No-latched operating mode).

TCS1.ai

TRIP

R

+

U

AUX

-

U

AUX

52a

52b

52

Pro-N

Binary input INx

 TCS1

Towards 74TCS logic

Trip circuit supervision with one binary inputs - 74TCS

Fun-74TCS2.ai

0

2 s

T

0

0.6 s

T

&

&

Enable (ON

Enable)

 74TCS Enable

RESET

TRIP

P

ING

 M

A

TRIX

 

   (LED

+R

EL

A

Y

S

)

 Start 74TCS

 Trip 74TCS

&

&

Block1 input (ON

Block)

 BLK1 74TCS

 Block1

 Start 74TCS

74TCS-ST-K

74TCS-ST-L

74TCS-TR-K

74TCS-TR-L

 Start 74TCS

Trip 74TCS

Trip 74TCS

TCS1

TCS2

&

Enable (ON

Enable)

 74TCS-BLK1

Block1

T

Binary input INx

T

0

Logic

INx 

t

ON

INx 

t

OFF

INx 

t

ON

T

0

n.o.

n.c.

  

INx 

t

OFF

T

Binary input INx

T

0

Logic

INx 

t

ON

INx 

t

OFF

INx 

t

ON

T

0

n.o.

n.c.

  

INx 

t

OFF

T

Binary input INx

T

0

Logic

INx 

t

ON

INx 

t

OFF

INx 

t

ON

T

0

n.o.

n.c.

  

INx 

t

OFF

Logic diagram concerning the trip circuit supervision with two binary inputs - 74TCS

Содержание NC20

Страница 1: ...NC20 Manual 01 2015 MANUAL NC20 MULTIFUNCTION PROTECTION FOR BANK CAPACITORS HARMONIC FILTERS WITH UNDER OVERVOLTAGE ELEMENTS...

Страница 2: ...y Uaux 14 Phase current input circuits 14 Unbalance neutral current input circuit 14 Voltage input circuits 14 Binary input circuits 14 3 3 OUTPUT CIRCUITS 14 Relays 14 Block output Logic selectivity...

Страница 3: ...rmal protection with RTD thermometric probes 26 48 Undervoltage 27 50 Undercurrent 37 54 TD Discharge time 56 Phase unbalance current 46 57 Neutral unbalance current 46N 63 Thermal image 49 71 Phase o...

Страница 4: ...erse time curve IEC 60255 3 BS142 type C 171 Residual overcurrent 50N 51N Standard inverse time curve IEC 60255 3 BS142 type A 172 Residual overcurrent 50N 51N Very inverse time curve IEC 60255 3 BS14...

Страница 5: ...on and commissioning must be carried out by quali ed person Thytronic assumes no re sponsibility for damages caused from improper use that does not comply all warning and caution in this manual In par...

Страница 6: ...e nitions IEn Relay residual nominal current IEnp Residual CT primary nominal current In Relay phase nominal current Inp Phase CT primary nominal current INn Relay unbalance nominal current INnp Unbal...

Страница 7: ...aracter istic quantity in reset condition is changed under speci ed condi tions and the instant when the relay operates Dropout ratio The ratio of a reset value to an operate value in well speci ed co...

Страница 8: ...he 2nd threshold of the 50 element It is not available for reading missing arrow AND and NAND logic gates OR and NOR logic gates Limit block I threshold Computation block Max phase current Threshold s...

Страница 9: ...FF Minimum pulse width operation for output relays tTR tTR t tTR INPUT OUTPUT tTR 0 T tTR t tTR INPUT OUTPUT Latched operating mode for output relays and LEDs Pulse operating mode for output relays t...

Страница 10: ...nominal currents indepen dently selectable at 1 A or 5 A using dip switch Three phase voltages line to ground with nominal voltages programmable in the range 50 130 V UR 100V Two binary inputs One blo...

Страница 11: ...witching type voltage stabilizing circuit having a very wide working range and a very small power dissipation Nominal frequency 50 or 60 Hz The most signi cant operating features are Programming of op...

Страница 12: ...11 Voltage dips short interruptions and voltage variations on dc input power port immunity tests Interruption UT 40 100 ms Interruption UT 0 50 ms Voltage variations UT 80 120 10 s EMC tests for inter...

Страница 13: ...mped oscillatory wave 1 MHz 30 A m Emission Reference standards EN 60255 25 IEC 60255 25 EN 61000 6 4 IEC 61000 6 4 EN 55011 CISPR 11 Electromagnetic emission tests Conducted emission auxiliary power...

Страница 14: ...tral current input circuit Relay nominal unbalance nominal current INn 1 A or 5 A selectable by dip switch Permanent overload 25 A Thermal overload 1 s 500 A Dynamic overload half cycle 1250 A Rated c...

Страница 15: ...yboard 8 keys 3 5 COMMUNICATION INTERFACES Local port Connection RJ10 Baud rate 19200 bps Parity None Protocol Modbus RTU Remote ports RS485 Connection screw terminals Baud rate 1200 57600 bps Protoco...

Страница 16: ...dervoltage 27 Common con guration 27 Operating logic Logic27 AND OR U Element U Curve type U Curve DEFINITE INVERSE 3 De nite time 27 First threshold de nite time U def 0 05 1 10 Un step 0 01 Un U def...

Страница 17: ...100 0 s step 0 1 s I2 Reset time delay t2 RES 0 00 100 0 s 0 00 9 99 s step 0 01 s 10 0 100 0 s step 0 1 s De nite time 46 Second threshold de nite time I2 def 1 150 step 1 I2 def within CLP I2CLP def...

Страница 18: ...1 with 0 1 INn 1 with 1 INn Operate time accuracy 5 or 10 ms Thermal image 49 2 Common con guration Initial thermal image IN DthIN 0 0 1 0 B step 0 1 B Reduction factor at inrush KINR 1 0 3 0 step 0...

Страница 19: ...10 00 In 0 100 0 999 In step 0 001 In 1 00 10 00 In step 0 01 In I inv within CLP ICLP inv 0 100 10 00 In 0 100 0 999 In step 0 001 In 1 00 10 00 In step 0 01 In I inv Operating time t inv 0 02 60 0 s...

Страница 20: ...In 10 0 40 0 In step 0 1 In I def within CLP ICLP def 0 100 40 0 In 0 100 0 999 In step 0 001 In 1 00 9 99 In step 0 01 In 10 0 40 0 In step 0 1 In I def Operating time t def 0 03 10 00 s step 0 01 s...

Страница 21: ...p 0 01 s 10 0 100 0 s step 0 1 s De nite time 50N 51N Third threshold de nite time IE def 0 100 40 0 In 0 100 0 999 In step 0 001 In 1 00 9 99 In step 0 01 In 10 0 40 0 In step 0 01 In IE def within C...

Страница 22: ...Pickup time 0 03 s Dropout ratio 0 95 0 98 Dropout time 0 05 s Overshoot time 0 03 s Pickup accuracy 0 3 with0 1Un 0 1 with1Un Operate time accuracy 5 or 10 ms Breaker failure BF BF Phase current thr...

Страница 23: ...Threshold S 0 10 0 95 step 0 01 74CT Overcurrent threshold I 0 10 1 00 In step 0 01 In S Operating time delay tS 0 03 200 s 0 03 9 99 s step 0 01 s 10 0 99 9 s step 0 1 s 100 200 s step 1 s Dropout r...

Страница 24: ...rrent IN Calculated Thermal image DTheta Displacement angle of IN with respect to IL1 PhiN RMS value of fundamental component for compensated neutral current INC IN IC Displacement angle of INC with r...

Страница 25: ...Ram SRam SPI CPU ETHERNET CPU BOARD POWER SUPPLY BOARD INPUT MODULE DSP DUAL PORT 1A 5A EEprom Thybus RS485 RELAYS K1 K6 Output contacts RS232 MMI LCD LEDs BINARY INPUTS IN1 Input IN2 BLOCK I O BLKIN...

Страница 26: ...ttainment of information pertaining to polarity and amplitude with high resolution The measurement criterion allows precise measurement of even those signals having a unidirectional component such as...

Страница 27: ...cation protocol known as Basic Protocol BP Task The task process e thread are the base components Example are Keyboard management RTC Real Time Clock updating RAM EEPROM updating Diagnostic Input acqu...

Страница 28: ...Basic Protocol BP manages the service communication between the kernel and the other modules through the communication buses with the following services Data and information exchange Calibration Upgra...

Страница 29: ...ct measures of physical channels rst level Calculated measures second level Derived third level The measures concerning a level are based on data worked out in the previous level For each level the re...

Страница 30: ...VT uL3 UL3 IL1 IL2 CT IL3 iL1 iL2 iL3 f T f T T F ai Hz Hz uL1 uL2 UL1 UL2 ACQUISITION VT uL3 UL3 IL1 IL2 CT IL3 iL1 iL2 iL3 f T f T IL1 ai In ACQUISITION iL1 iL2 iL3 DFT CT DFT DFT IL1 IL2 IL3 IL1 2...

Страница 31: ...ai THDL1 THDL2 THDL3 IL1RMS IL1 THDL1 100 IL1RMS IL1 IL2RMS IL2 THDL2 100 IL2RMS IL2 IL3RMS IL3 THDL3 100 IL3RMS IL3 THD ai THDL1 THDL2 THDL3 IL1RMS IL1 THDL1 100 IL1RMS IL1 IL2RMS IL2 THDL2 100 IL2RM...

Страница 32: ...mon parameter Fix Demand ai 1s IL1FIX IL2FIX IL3FIX tFIX In IL2 IL1 IL3 ILxFIX ILxn tFIX 60 tFIX 60 n 1 1 tFIX tFIX tFIX Fix Demand ai 1s IL1FIX IL2FIX IL3FIX tFIX In IL2 IL1 IL3 ILxFIX ILxn tFIX 60 t...

Страница 33: ...ree phase rotating currents a direct cyclic sequence is de ned when the three phases are L1 L2 L3 ordered while an inverse cyclic sequence is de ned when the three phases are L1 L3 L2 ordered fasori a...

Страница 34: ...urrent 50 51 g g g g g g g g Fundamental frequency phase overcurrent 50 51 g g g g g g g Residual overcurrent 50N 51N g g g g g g g Overvoltage 59 g g g g g Breaker failure BF g g g g g CONTROL MONITO...

Страница 35: ...epresents the logical state of the binary input used in the following processing Each binary input may be matched to one of the following default functions FUNCTIONS Binary inputs IN1 IN2 Reset LEDs g...

Страница 36: ...c INx tON Logic INx tOFF INx tOFF Binary input INx Reset led ai TRIPPING M ATRIX LED REL AYS Set ON turn on LED relay S Set Reset latch R Reset ON turn off LED relay Reset LEDs Binary input allocation...

Страница 37: ...lock for Phase Block2 Iph and earth protective functions Block2 IE is similar to that illustrated in the scheme concerning the Block2 IphIIE Note 3 Unlike the Block2 selective block that houses a safe...

Страница 38: ...TCS2 74TCS logic 74TCS logic Binary input INx T 0 IN1 tON 0 n o n c IN1 tON Logic IN1 tOFF IN1 tOFF Binary input INx T 0 IN1 tON 0 n o n c IN1 tON Logic IN1 tOFF IN1 tOFF TCS2 ai TRIP UAUX Trip Circui...

Страница 39: ...Nx tON Logic INx tOFF IN2 tOFF Binary input allocation for CB remote command TRIPPING M ATRIX LED REL AYS UAUX UAUX 52a 52 O I 52b inhit theta ai t T ln Ith IB 2 D P D B Ith IB 2 1 2 D P D IN Binary i...

Страница 40: ...until a reset command is issued RESET key ThySetter or communication command When pulse operating mode is set Operation MODE Pulse the output relay reset after a tTR programmable delay regardless of...

Страница 41: ...g I Start relays I ST K g g g g g g I Trip relays I TR K g g g g g g IE Start relays IE ST K g g g g g g IE Trip relays IE TR K g g g g g g IE Start relays IE ST K g g g g g g IE Trip relays IE TR K...

Страница 42: ...med with following operating mode No latched the LED reset at the end of the trip condition Latched the LED doesn t reset at the end of the trip condition it stays ON until a manual reset com mand is...

Страница 43: ...g g I AL Trip LEDs I ALTR L g g g g g g g I Start LEDs I ST L g g g g g g g I Trip LEDs I TR L g g g g g g g I Start LEDs I ST L g g g g g g g I Trip LEDs I TR L g g g g g g g I Start LEDs I ST L g g...

Страница 44: ...simple manner This is a con nection oriented transaction which means every query expects a response This query response technique ts well with the master slave nature of ModBus adding to the de termi...

Страница 45: ...This nominal value must be set by means dip switch to 1 A or 5 A same as the secondary CT nomi nal current Dip switch is located on board of the CPU module the exhaustive treatment of Dip setup is de...

Страница 46: ...l unbalance current when the primary measure ment reading mode is selected It must be programmed to the same value of the neutral CT s primary nominal current Es2 Un ai KTV V V 6000 3 100 3 60 Ung 6 0...

Страница 47: ...s may be displayed according the following operating modes With RELATIVE setting all measures are related to the nominal value With PRIMARY setting all measures are related to the primary value Es1 IN...

Страница 48: ...g localised overheating due to worn or non lubricated bearings The Pt100 probes detect the temperature in the range 50 C 250 C at 0 C its resistance is 100 ohm an alarm indicates any interruption or s...

Страница 49: ...hALx Th x tThALx tTh x All alarm and or trip elements can be enabled or disabled by setting ON or OFF the ThALx Enable e Th x Enable parameters inside the Set Pro le A or B Thermal protection with RTD...

Страница 50: ...tU inv 1 U U inv Where t operate time U relay input voltage U inv threshold setting tU inv operate time setting For the inverse time characteristic following data applies The operate time setting is r...

Страница 51: ...nhibition U inhibition tU def tU inv U def tU def U def U inv U Curve U Enable State Block1 BLK1U U BLK1 Start U Block1 BLK1U U BLK1 Start U U BF Trip U U BF U AND U UL1 UL2 UL3 OR Common con guration...

Страница 52: ...ING section Fun F27_S2 ai Logic diagram concerning the second threshold U of the undervoltage element 27 RESET tU def 0 T TRIPPING M ATRIX LED REL AYS tU def Start U Start U Trip U Trip U Trip U BF En...

Страница 53: ...characteristic concerning the rst threshold U of the undervoltage element 27 0 9 0 1 1 U U inv 0 01 0 01 0 1 1 10 100 1000 10000 t s 0 25 tU inv 100 s tU inv 10 s tU inv 0 1 s tU inv 1 s t tU inv 1 U...

Страница 54: ...and or I BLK1 enabling parameters are set to ON and a binary input is designed for logical block Block1 the protection is blocked off whenever the given input is active The trip timer is held in reset...

Страница 55: ...ry input INx T 0 Logic INx tON INx tON INx tOFF T 0 n o n c INx tOFF State IL1RMS I def I def 37 Inhibition ON Inhibit by MMI Fun F37_S2 ai Logic diagram concerning the second threshold I of the under...

Страница 56: ...ischarge time in seconds the initial value is the cor responding threshold set by TD decreased with resolution of 1 s to 0 When the discharge timer expires the display message is automatically removed...

Страница 57: ...d if instead the current drops below the threshold the element is restored The element can be enabled or disabled by setting ON or OFF the the I2 Enable parameter inside the Set Pro le A or B Phase un...

Страница 58: ...ed for output selective block Only when the committed pilot wire are used the continuity check of the pilot wire link is active Use of committed pilot wire input BLIN1 The protection is blocked off ac...

Страница 59: ...e I2CLP def t2CLP TRIPPING M ATRIX LED REL AYS A B C A 1 A 0 or OFF Output t2CLP I2 Enable t2CLP CB State CB OPEN CB CLOSED CB OPEN Output t2CLP t 0 1 s HIGH THRESHOLD BLOCK LOW THRESHOLD UNBLOCK HIGH...

Страница 60: ...2IN Iph Start I2 Trip I2 Iph Block2 IE Block2 BLK2IN IE tB timeout Block2 input tB K tB L Block1 FROM EARTH FAULT PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh IE ON IE BLIN1 Block1 T 0 tB IE Blo...

Страница 61: ...I2CLP def t2CLP TRIPPING M ATRIX LED REL AYS A B C A 1 A 0 or OFF Output t2CLP I2 Enable t2CLP CB State CB OPEN CB CLOSED CB OPEN Output t2CLP t 0 1 s HIGH THRESHOLD BLOCK LOW THRESHOLD UNBLOCK HIGH...

Страница 62: ...K2IN Iph Start I2 Trip I2 Iph Block2 IE Block2 BLK2IN IE tB timeout Block2 input tB K tB L Block1 FROM EARTH FAULT PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh IE ON IE BLIN1 Block1 T 0 tB IE Bl...

Страница 63: ...parameters are adjustable inside the Set Compensation 46N menu The compensation may be performed Manually by means the Manual compensation command the setting IC and PhiC parameter are entered Automat...

Страница 64: ...IN Element Setpoints menu Note 1 When the input value is more than 20 times the set point the operate time is limited to the value corresponding to 20 times the set point IC PhiC ACE Compensation 46N...

Страница 65: ...is designed for logical block Block1 the concerning element is blocked off whenever the given input is active 2 The enabling parameters are available inside the Set Pro le A or B Neu tral unbalance c...

Страница 66: ...et Pro le A or B Selective block BLOCK2 Selective block OUT menu 46NAL ai INC RESET tN ALdef 0 T 1 Start IN AL Trip I AL CB State ON Inhibit from IN and or IN element ON Enable IN AL unbalance current...

Страница 67: ...CB CLOSED CB OPEN Output tNCLP t 0 1 s HIGH THRESHOLD BLOCK LOW THRESHOLD UNBLOCK HIGH THRESHOLD BLOCK A ON Change setting B OFF C ON Element blocking IN TR K IN TR L IN ST L IN ST K 1 CLP IN tN def t...

Страница 68: ...tB L Block1 FROM EARTH FAULT PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh IE ON IE BLIN1 Block1 T 0 tB IE Block2 IE Block1 Block2 TRIPPING M ATRIX LED REL AYS 1 1 Neutral unbalance 46N Logic di...

Страница 69: ...ED CB OPEN Output tNCLP t 0 1 s HIGH THRESHOLD BLOCK LOW THRESHOLD UNBLOCK HIGH THRESHOLD BLOCK A ON Change setting B OFF C ON Element blocking IN TR K IN TR L IN ST L IN ST K 1 CLP IN INC IN def IN d...

Страница 70: ...tB L Block1 FROM EARTH FAULT PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh IE ON IE BLIN1 Block1 T 0 tB IE Block2 IE Block1 Block2 TRIPPING M ATRIX LED REL AYS 1 1 Neutral unbalance 46N Logic dia...

Страница 71: ...rrent used for thermal image calculation is Ith max IL1 IL2 IL3 If the second harmonic restraint is enabled the thermal current used for thermal image calculation becomes Ith ILMAX KINR max IL1 IL2 IL...

Страница 72: ...to ON The parameter is available inside the Set Pro le A or B Thermal image 49 Dth Element menu 3 Note 1 The CLP function Cold Load Pick up with blocking of the 49 element has priority compared with...

Страница 73: ...for selective block Block2 the protection is blocked off by phase ele ments Block2 Iph or by any protection element Block2 Iph IE according the selectivity block criteria 2 The enable DthAL1BLK2IN Dt...

Страница 74: ...tside CLP Pickup CLP setting change Block1 Block2 T 0 tDthCLP DthCLPMode tDthCLP Ith KINR TRIPPING M ATRIX LED REL AYS A B C A 1 A 0 or OFF Output tDthCLP DthAL1 Enable DThhAL1 thermal image 49 block...

Страница 75: ...L Block1 FROM EARTH FAULT PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh IE ON IE BLIN1 Block1 T 0 tB IE Block2 IE 1 Block1 Block2 TRIPPING M ATRIX LED REL AYS 1 1 Block2 output ON Enable DthAL1BL...

Страница 76: ...ide CLP Pickup CLP setting change Block1 Block2 T 0 tDthCLP DthCLPMode tDthCLP Ith KINR TRIPPING M ATRIX LED REL AYS A B C A 1 A 0 or OFF Output tDthCLP DthAL2 Enable DThhAL2 thermal image 49 block di...

Страница 77: ...Block1 FROM EARTH FAULT PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh IE ON IE BLIN1 Block1 T 0 tB IE Block2 IE 1 Block1 Block2 TRIPPING M ATRIX LED REL AYS 1 1 Thermal image 49 Logic diagram of...

Страница 78: ...BF Trip Dth TRIPPING M ATRIX LED REL AYS A B C A 1 A 0 or OFF Output tDthCLP Dth Enable DTh thermal image 49 block diagram tDthCLP CB State CB OPEN CB CLOSED CB OPEN Output tDthCLP t 0 1 s HIGH THRES...

Страница 79: ...lock1 FROM EARTH FAULT PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh IE ON IE BLIN1 Block1 T 0 tB IE Block2 IE 1 Block1 Block2 TRIPPING M ATRIX LED REL AYS 1 1 Thermal image 49 Logic diagram of t...

Страница 80: ...ual 01 2015 FUNCTION CHARACTERISTICS F_49 1min Char ai Operating characteristic concerning the thermal image element 49 T 1 min 1 1 1 2 3 4 5 6 7 8 9 10 20 Ith IB 0 01 0 1 1 10 100 1000 10000 1 0 p 0...

Страница 81: ...01 2015 FUNCTION CHARACTERISTICS F_49 200min Char ai Operating characteristic concerning the thermal image element 49 T 200 min 1 1 1 2 3 4 5 6 7 8 9 10 20 Ith IB t s 0 1 1 10 100 1000 10000 100000 1...

Страница 82: ...000 1 1 IRMS I inv 17 1 0 1 Where t operate time IRMS RMS input current I inv threshold setting t inv operate time setting The alarm threshold I AL has de nite time characteristic For all inverse time...

Страница 83: ...adjustable time interval starting from the circuit breaker closure This operating mode may be select by setting ON Change setting the ICLP AL Mode and or ICLP Mode parameters whereas the operating thr...

Страница 84: ...of committed pilot wire output BLOUT1 The information about phase or phase earth block may be select programming the ModeBLOUT1 parameter OFF ON IPh ON IPh IE ON IE inside Set Pro le A or B Selective...

Страница 85: ...REL AYS A B C A 1 A 0 or OFF Output tCLP AL I AL Enable tCLP CB State CB OPEN CB CLOSED CB OPEN Output tCLP t 0 1 s HIGH THRESHOLD BLOCK LOW THRESHOLD UNBLOCK HIGH THRESHOLD BLOCK A ON Change setting...

Страница 86: ...N Enable I BF towards BF logic I BF Trip I TRIPPING M ATRIX LED REL AYS I Curve 0 T A B C A 1 A 0 or OFF Output tCLP I Enable I overcurrent element 50 51RMS block diagram tCLP CB State CB OPEN CB CLOS...

Страница 87: ...lock1 FROM EARTH FAULT PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh IE ON IE BLIN1 Block1 T 0 tB IE Block2 IE Block1 Block2 TRIPPING M ATRIX LED REL AYS 1 1 Phase overcurrent 50 51 RMS Logic dia...

Страница 88: ...har ai 1 1 2 3 4 5 6 7 8 9 10 20 I RMS I inv 0 01 0 1 1 10 100 1000 10000 100000 1000000 t s t t inv 1 1 IRMS I inv 17 1 0 1 50000 t inv 0 1 s t inv 0 02 s t inv 1 0 s t inv 10 s t inv 60 s Operating...

Страница 89: ...undamental I Element Setpoints menu The trip of I AL RMS element may be inhibited by the start of the second and or third element I I ofthefundamentalfrequencyphaseovercurrentbysettingONtheDisableI AL...

Страница 90: ...lable Logical block Block1 If the I BLK1 and or I BLK1 enabling parameters are set to ON and a binary input is de signed for logical block Block1 the concerning element is blocked off whenever the giv...

Страница 91: ...50 51 Fundamental I Element I Element Setpoints menus while the Block2 Iph and Block2 Iph IEfunctions must be assigned to the selected binary inputs inside the Set Inputs Binary input IN1 x menus IN1...

Страница 92: ...ATRIX LED REL AYS A B C Output tCLP I Enable I overcurrent element 50 51 Fundamental Block diagram tCLP CB State CB OPEN CB CLOSED CB OPEN Output tCLP t 0 1 s HIGH THRESHOLD BLOCK LOW THRESHOLD UNBLO...

Страница 93: ...FROM EARTH FAULT PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh IE ON IE BLIN1 Block1 T 0 tB IE Block2 IE 1 Block1 Block2 TRIPPING M ATRIX LED REL AYS 1 1 Phase overcurrent 50 51 Fundamental Logi...

Страница 94: ...I overcurrent element 50 51 Fundamental Block diagram tCLP CB State CB OPEN CB CLOSED CB OPEN Output tCLP t 0 1 s HIGH THRESHOLD BLOCK LOW THRESHOLD UNBLOCK HIGH THRESHOLD BLOCK A ON Change setting B...

Страница 95: ...1 FROM EARTH FAULT PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh IE ON IE BLIN1 Block1 T 0 tB IE Block2 IE 1 Block1 Block2 TRIPPING M ATRIX LED REL AYS 1 1 Phase overcurrent 50 51 Fundamental Log...

Страница 96: ...023 Very Inverse ANSI IEEE type VI t tE inv 3 922 IEC IE inv 2 1 0 098 Extremely Inverse ANSI IEEE type EI t tE inv 5 64 IEC IE inv 2 1 0 024 Where t operate time IEC calculated residual current IE t...

Страница 97: ...e menus For every of the four thresholds the following block criteria are available Logical block Block1 If the IE BLK1 IE BLK1 and or IE BLK1 enabling parameters are set to ON and a bi nary input is...

Страница 98: ...f output relay K1 K6 If the IE BLK2OUT IE BLK2OUT and or IE BLK2OUT enable parameters are set to ONand a output relay is designed for selective block Block2 the protection issues a block output by pha...

Страница 99: ...50N 51N IE inhibition BLK1IE IE BF IE Element Start IE Start IE Start IE Trip IE Trip IE IE disbyIE IE BLK2IN IE disbyIE BLK1IE IE Element BLK2OUT Start IE Start IE Trip IE IE disbyIE IE BLK1 IE BLK2...

Страница 100: ...BF Trip IE TRIPPING M ATRIX LED REL AYS IE Curve 0 T A B C A 1 A 0 or OFF Output tECLP IE Enable IE residual overcurrent element 50 51 Block diagram tECLP CB State CB OPEN CB CLOSED CB OPEN Output tE...

Страница 101: ...Block2 input tB K tB L Block1 FROM EARTH FAULT PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh IE ON IE BLIN1 Block1 T 0 tB IE Block2 IE Block1 Block2 TRIPPING M ATRIX LED REL AYS 1 1 Residual over...

Страница 102: ...IE residual overcurrent element 50N 51N Block diagram tECLP CB State CB OPEN CB CLOSED CB OPEN Output tECLP t 0 1 s HIGH THRESHOLD BLOCK LOW THRESHOLD UNBLOCK HIGH THRESHOLD BLOCK A ON Change setting...

Страница 103: ...lock1 FROM EARTH FAULT PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh IE ON IE BLIN1 Block1 T 0 tB IE Block2 IE Block1 Block2 TRIPPING M ATRIX LED REL AYS 1 1 Residual overcurrent 50N 51N Logic di...

Страница 104: ...REL AYS A B C A ON Change setting B OFF C ON Element blocking Output tECLP IE Enable IE residual overcurrent element 50N 51N Block diagram tECLP CB State CB OPEN CB CLOSED CB OPEN Output tECLP t 0 1 s...

Страница 105: ...Block1 FROM EARTH FAULT PROTECTIONS FROM ANY PROTECTIONS OFF ON IPh ON IPh IE ON IE BLIN1 Block1 T 0 tB IE Block2 IE Block1 Block2 TRIPPING M ATRIX LED REL AYS 1 1 Residual overcurrent 50N 51N Logic d...

Страница 106: ...tting is referred to an input voltage equal to 1 5 of the pickup value Asymptotic reference value minimum pickup value 1 1 U inv Minimum operate time 0 1 s Range where the equation is valid 1 1 U U in...

Страница 107: ...tment of the logical block Block 1 function may be found in the Logic Block paragraph inside CONTROL AND MONITOR ING section Fun F59_S1 ai U Curve 0 T RESET tU 0 T TRIPPING M ATRIX LED REL AYS tU def...

Страница 108: ...e towards BF logic U BF Enable ON Enable Block1 input ON Block Block1 Block1 ON Inhibit U Inhibition U disbyU Binary input INx T 0 Logic INx tON INx tON INx tOFF T 0 n o n c INx tOFF U ST K U TR K U S...

Страница 109: ...U inv 100 s t U inv 10 s t U inv 1 s t U inv 0 1 s 1 5 0 01 0 1 1 10 100 1000 10000 t s Inverse time operating characteristic concerning the rst threshold U of the overvoltage element 59 t tU inv U U...

Страница 110: ...Set Pro le A or B Breaker failure BF menu All the IBF IEBF and tBF parameters can be set separately for Pro le A and Pro le B they are avail able inside the Set Pro le A or B Breaker failure BF menu B...

Страница 111: ...ip BF Trip ProtExt 52a Block1 enable ON Enable BF BLK1 Block1 52a IBF Max IL1 IL3 IBF IL1 IL2 IL3 IEBF IE IEBF IE 1 RESET tBF 0 T tBF 1 Binary input INx T 0 Logic INx tON INx tON INx tOFF T 0 n o n c...

Страница 112: ...lock it is not liable for any inhibition time out so the protective element is disabled for the whole time when the input is ON 2 Note 1 In the following treatment the logical block is de ned as Logic...

Страница 113: ...ncerning the logic block element Block1 IE BLK1 50N 51N element IE BLK11 50N 51N element IE BLK1 50N 51N1 element U BLK1 59 element U BLK1 59 element 74TCSBLK1 74TCS element BFBLK1 BF element DthAL1BL...

Страница 114: ...y an output block signal coming from a Pro N device or by a free voltage contact The protection is blocked off according the selectivity block criteria by phase elements Block2 Iph by earth elements B...

Страница 115: ...tB Iph time related to the downstream relay does not take into account if such margin has been considered for the tF Iph setting s is a safety margin The chronometric selectivity applied among the tB...

Страница 116: ...IE or phase earth ON IPh IE concerning the sending block out signal may be select by means of the ModeBLOUT1 parameter inside the Set Pro le A or B Selective block BLOCK2 Selective block OUT menu The...

Страница 117: ...ing for a possible short circuit in the pilot wire or in the output circuit of the downstream protection The periodic pulses that are sent by output circuit may be enabled or disabled by means the Pul...

Страница 118: ...the main circuit breaker CB1 by the A relay with a fault in 1 A Protection I element with de nite time set to 4 5 In with operate time to 0 10 s blocked by start of B and or C protection Settings I d...

Страница 119: ...zero the Logic parameters ON OFF must be pro grammed in the same way of the related circuit connected with it The RemTrip K matching must be assigned to the selected output relays inside the Set Remot...

Страница 120: ...tage is lower than 1 5 En the sampling frequency is xed to fn 50 or 60 Hz If the measured frequency is outside the locking range the sampling frequency is xed to the lower or upper value 45 or 55 Hz w...

Страница 121: ...ecause it is likely that incorrect operation of the protection would occur on imbalance transient secondary current due to asymmetric line CTs saturation Depending upon the magnitude and duration of t...

Страница 122: ...utput relays inside the Set CT supervision 74CT submenu the same for addressing the LED indicators S TR L If the S BLK1parameter is set to ON and a binary input is designed for logical block Block1 th...

Страница 123: ...hen the input block goes down The 74TCS BLK1 parameter is available inside the Set Pro le A B Trip circuit supervision 74TCS submenu All the parameters can be set separately for Pro le A and Pro le B...

Страница 124: ...r a 40 s delay in order to allow the fault clearing and the consequent reset of the TRIP protection Outputs are reset to zero after 6 s from the TRIP contact open 1 Note 1 The trip contact TRIP of the...

Страница 125: ...To satisfy the above requirements the R value must be chosen between the Rmin and Rmax values typically the normalized value nearest the arithmetic mean R Rmin Rmax 2 The power dissipated by the R res...

Страница 126: ...open K and CBclose K function must be set inside the Set Circuit breaker supervision LEDs relays allocation menu the CB position can be visualized by means two LEDs CBopen L and CBclosed L parameters...

Страница 127: ...L TRIPPING M ATRIX LED REL AYS TRIPPING M ATRIX LED REL AYS TRIPPING M ATRIX LED REL AYS State N Open tbreak State SumI Opening transition N Open Mode N Open From CB position Opening transition Mode t...

Страница 128: ...it information between protections installed in signi cant distance where the traditional connections are critical in terms of reliability Making OR logic for opening control of multiple DDI simultane...

Страница 129: ...reset to zero by means the Reset on demand measures command Thysetter Commands menu The tROL Rolling demand period parameter is the same for rolling demand setting Oscillography Trigger Setup Followin...

Страница 130: ...distortion factor for phase currents THDL1 THDL2 THDL3 THDL1 100 IL1 2 IL1 11th 2 IL1 100 IL1RMS IL1 THDL2 100 IL2 2 IL2 11th 2 IL2 100 IL2RMS IL1 THDL3 100 IL2 2 IL3 11th 2 IL3 100 IL3RMS IL1 RMS val...

Страница 131: ...unters xx Start total counter xx I I 0 9999 xx Trip total counter xx I I 0 9999 xx Block1 total counter xx I I 0 9999 xx Block2 total counter xx I I 0 9999 Self test Lower level diagnostic MINOR can b...

Страница 132: ...enabled for external selective block on output ST IE BLK2 ON OFF Phase protections output selective block state BLK2 OUT Iph ON OFF Ground protections output selective block state BLK2 OUT IE ON OFF P...

Страница 133: ...ages uL1 uL2 uL3 Analog channels RMS value for phase currents IL1RMS IL2RMS IL3RMS Fundamental component for phase currents IL1 IL2 IL3 Fundamental component for input voltages UL1 UL2 UL3 Fundamental...

Страница 134: ...IL3RMS IN Logic variables K1 K2 K3 K4 K5 K6 IN1 IN2 up to 116 record can be stored if f 50 Hz since Example 2 With following setting Pre trigger 0 5 s Post trigger 0 5 s Sampled data iL1 iL2 iL3 iE An...

Страница 135: ...tection availability Flush mounting The xed case tted with special fastening brackets is mounted on the front of electric control board previously drilled as indicated in the drawing In case of side b...

Страница 136: ...ing distance is determined by the dimensions of the mounting plate indicated in the overall dimensions drawing increased horizontally and vertically by as much as needed to allow room for the wiring a...

Страница 137: ...rate mount ai Separate operator panel F1 D1 RX TX F2 F3 F4 F5 A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13 A14 A15 A16 A17 A18 A19 A20 A21 A22 B1 B2 B3 B4 B5 B6 B7 B8 C1 C2 C4 C3 C5 C6 C7 C8 E1 128 5 11...

Страница 138: ...r a one unit space must be provided when several rack are overlapping mounted Rack mount ai Rack mounting 177 4U 101 6 482 6 465 ON 4 1 3 2 5 TRIP START ON 4 1 3 2 5 TRIP START ON 4 1 3 2 5 TRIP START...

Страница 139: ...torque 0 5 0 6 Nm Stripping length 10 mm The connections to the current signal inputs C1 C8 can be made by ring lugs and an insulating panel covering the terminals may be mounted for safety purposes...

Страница 140: ...voltage of the control panel The inputs are polarity free with wide voltage range The optoisolated inputs are immune to transitory interferences however the following recommenda tion must be considere...

Страница 141: ...must be employed if an FX port is implemented The link must be enabled by means ThySetter sw and RS232 connection Set the IP address Host IP address e IP net mask in order that the NA10 and PC paramet...

Страница 142: ...ce of the induc tive components of the same which might compromise good communication RS485 120 SUPERVISION UNIT OUTPUT RELAYS UAUX A1 A2 A9 A10 A11 A12 A13 A14 E1 THYBUS D1 ETHERNET A3 A4 A5 A6 A7 A8...

Страница 143: ...PT100 PT100 MODULE INPUT PT2 MPT2 PT3 MPT3 PT4 MPT4 PT8 MPT8 PT7 MPT7 PT6 MPT6 PT5 MPT5 PUT N I S U B Y H T T U P T U O S U B Y H T MPT 8 T1 PT1 PT8 MPT1 MPT8 PT7 MPT7 PT6 MPT6 PT5 MPT5 PT2 MPT2 PT3...

Страница 144: ...re installed the hardware address must be set to avoid communication collisions on the Thybus for this purpose the default address must be changed on one module by means of dip switch on the top circu...

Страница 145: ...s example they cannot be comprehensive for real applications Block sch ai Logic selectivity with BFO BLIN1 BLIN1 BLIN1 Block2 IPh BLOUT1 BLOUT1 TRIP I TRIP I TRIP I TRIP I Any device Block sch ai Logi...

Страница 146: ...power supply before extracting or re inserting the relay If an attempting is made to insert a relay into an un matching case a mechanical code will prevent full insertion Demage can result if excessiv...

Страница 147: ...g screw in order avoid loss of the internal wash er Unmounting of the case from the switchboard is not needed Split the MMI module and disconnect cable set in ai Unmounting set in ai Unmounting Split...

Страница 148: ...ular attention to avoid any accidental contact with the internal components In order to avoid the static electricity accumulated in the human body from causing damage it is recommended to observe the...

Страница 149: ...the CPU board Facory defaul settings In 5 A phase currents INn 1 A unbalanced neutral current set in ai ETHERNET THYBUS 1 A 5 A S5 485 1 2 3 4 IL1 IL2 IL3 IN Dip switch setting inside the CPU board Fa...

Страница 150: ...art information of any protective functions LED TRIP red committed for trip information of any protective functions 6 6 FINAL OPERATIONS Before energizing the electric board it is advisable to check t...

Страница 151: ...e Products Software 1 ThySetter use Please refer to ThySetter user manual for detailed instructions The document is available on www thytronic it Product Sotware ThySetter Download area Note 1 Startin...

Страница 152: ...reaker Close command At power up the display shows the text THYTRONIC PRO NC20 xxx x serial number date and time 01 01 2000 00 00 The ON green Led points out the auxiliary power supply voltage permane...

Страница 153: ...e auxiliary power supply to the NC20 relay As example to set the operating mode of the K1 output relay as ENERGIZED LATCHED the following procedure must be issued By means Down button select the Set m...

Страница 154: ...he RS485 Protocol or Ethernet parameters message to enter you must press the Right button As example to select the address 12 for the ModBus protocol the following procedure must be issued Select the...

Страница 155: ...menu command Communication Open Verify that inside the modality box Serial and Automatic are selected Thysetter will search automatically the relay from the template regardless of what is selected in...

Страница 156: ...r about 3 minutes elapsed without pressing any button If you do not want to wait three minutes of waiting it must go back to the password menu and come out without input any data and until the the mes...

Страница 157: ...IE OFF CLP IE OFF BLK1 IE OFF BLK2IN IE OFF BLK4IN IE OFF Start IE OFF Trip IE OFF CLP IE OFF BLK1 IE OFF BLK2IN IE OFF BLK4IN IE OFF Start IE OFF Trip IE OFF CLP IE OFF BLK1 IE OFF BLK2IN IE OFF BLK...

Страница 158: ...2Dth cnt 0 ParTrDth cnt 0 ParBk1Dth cnt 0 ParBk1BFcnt 0 ParStBFcnt 0 ParTrTrcnt 0 ParBk1 74TCScnt 0 ParTr74TCScnt 0 ParBk1 74CTcnt 0 ParTr74CTcnt 0 ParBk1IE cnt 0 ParTrIE cnt 0 ParStIE cnt 0 ParStIE c...

Страница 159: ...Operating phase IL2r 0 In IL1rms r 0 In Fault 0 Cause Date Time IL2rms r 0 In IL3rms r 0 In IL3r 0 In UL2r 0 Un UL1r 0 Un UL3r 0 Un IECr 0 In INCr 0 INn I2r 0 INr 0 INn PhiNr 0 gr PhiNCr 0 gr DTheta r...

Страница 160: ...TD TD Enable OFF tD 1 min Relays TD TD K LEDs TD TD L 37 I Element I Element I Enable OFF I def enable OFF I def 0 5 In t def 1 s I BLK1 OFF I BF OFF Relays I I TR K I ST K I ST L I TR L LEDs I I def...

Страница 161: ...NU PROCEED PROFILE A MENU 49 DthAL1 Element Common DthAL2 Element Dth Element DthIN 0 DThetaB KINR 2 T 10 min DthCLP Mode OFF DthCLP 0 1 s DthAL1 Enable OFF DthAL1 0 5 DthetaB DthAL1BLK1 OFF DthAL1BLK...

Страница 162: ...K2OUT OFF IE BLK2IN OFF IE BF OFF IE Curve DEFINITE Relays IE IE TR K IE ST K IE ST L IE TR L LEDs IE tECLP 0 1 s tE RES 0 s IE def enable OFF IECLP def 2 IEn IE Enable OFF IECLP Mode OFF tE def 1 s I...

Страница 163: ...WIRE DIAGNOSTIC PulseBLOUT1 OFF PulseBLIN1 OFF N ROL 12 tRoll 5 min DEMAND MEASURES Periods tFix 15 min BF IEBF 0 1 IEn IBF 0 1 In IBF enable ON IEBF enable ON BF Enable OFF CB Input ON BF BLK1 OFF t...

Страница 164: ...nt values referred to the nominal current of the current transformers as directly in primary amperes according to the preset value of CT s nominal primary current the same is done for the input voltag...

Страница 165: ...racteristics following data applies Asymptotic reference value minimum pickup value 1 1 I inv Minimum operate time 0 1 s Range where the equation is valid 2 3 1 1 I I inv 20 If I pickup 2 5 In the upp...

Страница 166: ...BS142 type A F_46N IECA Char ai 1 1 2 3 4 5 6 7 8 9 10 20 I NC IN inv 0 01 0 1 1 10 100 1000 10000 t s tN inv 10 s tN inv 60 s tN inv 5 s tN inv 1 s tN inv 0 5 s tN inv 0 2 s tN inv 0 1 s tN inv 0 02...

Страница 167: ...BS142 type B F_46N IECB Char ai 1 1 2 3 4 5 6 7 8 9 10 20 INC IN inv 0 01 0 1 1 10 100 1000 10000 t s tN inv 10 s tN inv 60 s tN inv 5 s tN inv 1 s tN inv 0 5 s tN inv 0 2 s t inv 0 02 s t inv 0 1 s 1...

Страница 168: ...5 3 BS142 type C F_51 IECC Char ai 1 1 2 3 4 5 6 7 8 9 10 20 INC IN inv 0 01 0 1 1 10 100 1000 10000 100000 t s tN inv 10 s tN inv 60 s tN inv 5 s tN inv 1 s t inv 0 5 s t inv 0 2 s t inv 0 02 s t inv...

Страница 169: ...3 BS142 type A F_51 IECA Char ai 1 1 2 3 4 5 6 7 8 9 10 20 I RMS I inv 0 01 0 1 1 10 100 1000 10000 t s t inv 10 s t inv 60 s t inv 5 s t inv 1 s t inv 0 5 s t inv 0 2 s t inv 0 1 s t inv 0 02 s t t i...

Страница 170: ...55 3 BS142 type B F_51 IECB Char ai 1 1 2 3 4 5 6 7 8 9 10 20 IRMS I inv 0 01 0 1 1 10 100 1000 10000 t s t inv 10 s t inv 60 s t inv 5 s t inv 1 s t inv 0 5 s t inv 0 2 s t inv 0 02 s t inv 0 1 s 13...

Страница 171: ...3 BS142 type C F_51 IECC Char ai 1 1 2 3 4 5 6 7 8 9 10 20 IRMS I inv 0 01 0 1 1 10 100 1000 10000 100000 t s t inv 10 s t inv 60 s t inv 5 s t inv 1 s t inv 0 5 s t inv 0 2 s t inv 0 02 s t inv 0 1...

Страница 172: ...BS142 type A F_51N IECA Char ai 1 1 2 3 4 5 6 7 8 9 10 20 IEC IE inv 0 01 0 1 1 10 100 1000 10000 t s tE inv 10 s tE inv 60 s tE inv 5 s tE inv 1 s tE inv 0 5 s tE inv 0 2 s tE inv 0 1 s tE inv 0 02 s...

Страница 173: ...142 type B F_51N IECB Char ai 1 1 2 3 4 5 6 7 8 9 10 20 I EC IE inv 0 01 0 1 1 10 100 1000 10000 t s tE inv 10 s tE inv 60 s tE inv 5 s tE inv 1 s tE inv 0 5 s tE inv 0 2 s tE inv 0 02 s tE inv 0 1 s...

Страница 174: ...3 BS142 type C F_51 IECC Char ai 1 1 2 3 4 5 6 7 8 9 10 20 IE IE inv 0 01 0 1 1 10 100 1000 10000 100000 t s tE inv 10 s tE inv 60 s tE inv 5 s tE inv 1 s tE inv 0 5 s tE inv 0 2 s tE inv 0 02 s tE in...

Страница 175: ...rve L 0 024 for ANSI IEEE Extremely inverse curve For all inverse time characteristics following data applies Asymptotic reference value minimum pickup value 1 1 I inv Minimum operate time 0 1 s Range...

Страница 176: ...type MI F_46N ANSIMI Char ai 1 1 2 3 4 5 6 7 8 9 10 20 INC IN inv 0 01 0 1 1 10 100 1000 10000 t s tN inv 10 s tN inv 60 s tN inv 5 s tN inv 1 s t inv 0 02 s t inv 0 2 s t inv 0 1 s t inv 0 5 s t tN i...

Страница 177: ...VI F_46N ANSIVI Char ai 1 1 2 3 4 5 6 7 8 9 10 20 INC IN inv 0 01 0 1 1 10 100 1000 10000 t s tN inv 10 s tN inv 60 s tN inv 5 s tN inv 1 s t inv 0 5 s t inv 0 2 s t inv 0 1 s t inv 0 02 s t tN inv I...

Страница 178: ...E type EI F_46N ANSIEI Char ai 1 1 2 3 4 5 6 7 8 9 10 20 INC IN inv 0 01 0 1 1 10 100 1000 10000 t s tN inv 10 s tN inv 60 s tN inv 5 s t inv 0 5 s t inv 1 s t inv 0 2 s t inv 0 1 s t inv 0 02 s t tN...

Страница 179: ...type MI F_51 ANSIMI Char ai 1 1 2 3 4 5 6 7 8 9 10 20 IRMS I inv 0 01 0 1 1 10 100 1000 10000 t s t inv 10 s t inv 60 s t inv 5 s t inv 1 s t inv 0 02 s t inv 0 2 s t inv 0 1 s t inv 0 5 s t t inv IRM...

Страница 180: ...type VI F_51 ANSIVI Char ai 1 1 2 3 4 5 6 7 8 9 10 20 IRMS I inv 0 01 0 1 1 10 100 1000 10000 t s t inv 10 s t inv 60 s t inv 5 s t inv 1 s t inv 0 5 s t inv 0 2 s t inv 0 1 s t inv 0 02 s t t inv IRM...

Страница 181: ...type EI F_51 ANSIEI Char ai 1 1 2 3 4 5 6 7 8 9 10 20 IRMS I inv 0 01 0 1 1 10 100 1000 10000 t s t inv 10 s t inv 60 s t inv 5 s t inv 0 5 s t inv 1 s t inv 0 2 s t inv 0 1 s t inv 0 02 s t t inv IR...

Страница 182: ...pe MI F_51N ANSIMI Char ai 1 1 2 3 4 5 6 7 8 9 10 20 IEC IE inv 0 01 0 1 1 10 100 1000 10000 t s tE inv 10 s tE inv 60 s tE inv 5 s tE inv 1 s tE inv 0 02 s tE inv 0 2 s tE inv 0 1 s tE inv 0 5 s t tE...

Страница 183: ...I F_51N ANSIVI Char ai 1 1 2 3 4 5 6 7 8 9 10 20 IEC IE inv 0 01 0 1 1 10 100 1000 10000 t s tE inv 10 s tE inv 60 s tE inv 5 s tE inv 1 s tE inv 0 5 s tE inv 0 2 s tE inv 0 1 s tE inv 0 02 s t tE inv...

Страница 184: ...ype EI F_51N ANSIEI Char ai 1 1 2 3 4 5 6 7 8 9 10 20 IEC IE inv 0 01 0 1 1 10 100 1000 10000 t s tE inv 10 s tE inv 60 s tE inv 5 s tE inv 0 5 s tE inv 1 s tE inv 0 2 s tE inv 0 1 s tE inv 0 02 s t t...

Страница 185: ...ERNET RS485 F1 F2 F3 F4 F5 A B OUTPUT RELAYS A9 A10 A11 A12 A13 A14 A3 A4 A5 A6 A7 A8 K2 K3 K4 K5 K6 K1 BLOCK OUT A15 BLOUT BLOUT A16 BLOCK IN A17 A18 C1 IL1 IL2 IL3 CURRENT INPUTS C2 C3 C4 C5 C6 IN C...

Страница 186: ...TPUT MPT ON BUS RUN MODULO PT100 PT100 MODULE INPUT OUTPUT MID16 ON BUS RUN MODULO INGRESSI REMOTI INPUT 34 36 35 30 32 33 31 28 29 43 44 45 39 40 42 41 38 37 52 54 53 48 50 51 49 46 47 1 2 3 4 5 6 7...

Страница 187: ...cannot be comprehensive for real applications For all diagrams the output contacts are shown in de energized state for standard reference NC20 sch1 ai NC20 L1 L2 L3 A B A B a b a b IN C7 C8 P2 P1 S1 S...

Страница 188: ...PPENDIX NC20 sch2 ai NC20 L1 L2 L3 A B A B a b a b IN C7 C8 P2 P1 S1 S2 UL1 UL2 UL3 B6 B3 B4 B5 B1 B2 27 59 46 49 37 50 51 50 51 RMS 74CT 46N BINARY INPUTS 50BF CB position Two phase CTs C2 C1 C3 C4 C...

Страница 189: ...5 C6 C7 C8 E1 128 5 110 200 168 20 205 149 30 5 30 107 177 4 5 102 5 0 3 70 161 154 4 5 4 5 212 5 25 15 170 275 177 4U 101 6 482 6 465 RACK MOUNTING FLUSH MOUNTING CUTOUT SIDE VIEWS FRONT VIEWS ON 4 1...

Страница 190: ...ements reading mode RELATIVE PRIMARY Language English Turkish Russian Inputs Binary input IN1 IN1 Logic Active ON Active OFF IN1 tON Value s 0 00 9 99 step 0 01 10 0 100 0 step 0 1 IN1 tOFF Value s 0...

Страница 191: ...tched TRIP Type No latched Latched L1 Type No latched Latched L2 Type No latched Latched L3 Type No latched Latched L4 Type No latched Latched L5 Type No latched Latched L6 Type No latched Latched Typ...

Страница 192: ...rm NO YES Self test relay K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 MMI Display modules Assigned modules All modules 46N Compensation Compensation current IC INn 0 00 0 50 step 0 01 Compensation angle PhiC deg 0...

Страница 193: ...Th 3 Enable OFF ON 26 PT3 Trip threshold Th 3 C 0 200 step 1 Th 3 Operating time Value s 0 100 step 1 Th 3 Breaker failure Th 3BF OFF ON Th 3 Trip relays Th 3 K K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 Th 3 Tri...

Страница 194: ...1 Th 6 Operating time Value s 0 100 step 1 Th 6 Breaker failure Th 6BF OFF ON Th 6 Trip relays Th 6 K K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 Th 6 Trip LEDs Th 6 L START TRIP L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 PT7...

Страница 195: ...ST K K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 U Trip relays U TR K K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 U Start LEDs U ST L START TRIP L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 U Trip LEDs U TR L START TRIP L1 L2 L3 L4 L5 L6 L...

Страница 196: ...K5 K6 K7 K8 K9 K10 I Trip relays I TR K K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 I Start LEDs I ST L START TRIP L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 I Trip LEDs I TR L START TRIP L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 De ni...

Страница 197: ...p 0 01 10 0 100 0 step 0 1 I2 Logical block I2 BLK1 OFF ON I2 Input selective block I2 BLK2IN OFF ON I2 Output selective block I2 BLK2OUT OFF ON I2 Breaker failure I2 BF OFF ON I2 Disabling by I2 star...

Страница 198: ...IN Output selective block IN BLK2OUT OFF ON IN Breaker failure IN BF OFF ON IN AL Disabling by IN IN ALdisbyIN OFF ON IN Start relays IN ST K K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 IN Trip relays IN TR K K1 K...

Страница 199: ...Mode OFF ON Element blocking ON Change setting DthCLP Activation time Value s 0 00 9 99 step 0 01 10 0 100 0 step 0 1 DthAL1 Element DthAL1 Enable DthAL1 Enable OFF ON 49 First alarm threshold DthAL1...

Страница 200: ...ON Pickup value In 0 100 0 999 step 0 001 1 00 10 00 step 0 01 I ALdef within CLP ICLP ALdef In 0 100 0 999 step 0 001 1 00 10 00 step 0 01 I ALdef Operating time Value s 0 03 9 99 step 0 01 10 0 99...

Страница 201: ...0 0 step 0 1 I Reset time delay Value s 0 00 9 99 step 0 01 10 0 100 0 step 0 1 I Logical block I BLK1 OFF ON I Input selective block I BLK2IN OFF ON I Output selective block I BLK2OUT OFF ON I Breake...

Страница 202: ...001 1 00 9 99 step 0 01 10 0 40 0 step 0 1 I def Operating time Value s 0 03 10 00 step 0 01 Residual overcurrent 50N 51N IE Element Setpoints IE Enable IE Enable OFF ON IE Curve type IE Curve IEC BS...

Страница 203: ...ective block IE BLK2OUT OFF ON IE Breaker failure IE BF OFF ON IE Disabling by IE start IE disbyIE OFF ON IE Start relays IE ST K K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 IE Trip relays IE TR K K1 K2 K3 K4 K5 K...

Страница 204: ...mon con guration 59 Operating logic Logic59 OR AND U Element Setpoints U Enable U Enable OFF ON U Curve type U Curve INVERSE DEFINITE U Logical block U BLK1 OFF ON U Breaker failure U BF OFF ON U Star...

Страница 205: ...lays tB K K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 tB Iph IE Elapsed signalling LEDs tB L START TRIP L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 Selective block OUT BLOUT1 Selective block operating mode ModeBLOUT1 OFF ON IP...

Страница 206: ...8 L9 L10 Th 1 Trip Th 1 Enable Th 1 Enable OFF ON 26 PT1 Trip threshold Th 1 C 0 200 step 1 Th 1 Operating time Value s 0 100 step 1 Th 1 Breaker failure Th 1BF OFF ON Th 1 Trip relays Th 1 K K1 K2 K3...

Страница 207: ...4 Operating time Value s 0 100 step 1 Th 4 Breaker failure Th 4BF OFF ON Th 4 Trip relays Th 4 K K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 Th 4 Trip LEDs Th 4 L START TRIP L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 PT5 Pro...

Страница 208: ...ure Th 7BF OFF ON Th 7 Trip relays Th 7 K K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 Th 7 Trip LEDs Th 7 L START TRIP L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 PT8 Probe ThAL8 Alarm ThAL8 Enable ThAL8 Enable OFF ON 26 PT8 A...

Страница 209: ...block U BLK1 OFF ON U Breaker failure U BF OFF ON U Disabling by U start U disbyU OFF ON U Start relays U ST K K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 U Trip relays U TR K K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 U Star...

Страница 210: ...L6 L7 L8 L9 L10 Phase unbalance 46 I2 Element Setpoints I2 Enable I2 Enable OFF ON I2CLP Mode I2CLP Mode OFF ON Element blocking ON Change setting I2CLP Activation time Value s 0 00 9 99 step 0 01 10...

Страница 211: ...05 9 99 step 0 01 10 0 60 0 step 0 1 Neutral unbalance current 46N IN AL Element Setpoints IN AL Enable IN AL Enable OFF ON INCLP AL Mode INCLP AL Mode OFF ON Element blocking ON Change setting INCLP...

Страница 212: ...State OFF ON Pickup value INn 0 01 1 00 step 0 01 IN inv within CLP INCLP inv INn 0 01 1 00 step 0 01 IN inv Operating time tN inv s 0 02 9 99 step 0 01 10 0 60 0 step 0 1 IN Element Setpoints IN Enab...

Страница 213: ...2 Input selective block DthAL2BLK2IN OFF ON DthAL2 Output selective block DthAL2BLK2OUT OFF ON DthAL2 Alarm relays DthAL2 K K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 DthAL2 Alarm LEDs DthAL2 L START TRIP L1 L2 L...

Страница 214: ...lective block I BLK2IN OFF ON I Output selective block I BLK2OUT OFF ON I Breaker failure I BF OFF ON I AL Disabling by I I ALdisbyI OFF ON I Start relays I ST K K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 I Trip...

Страница 215: ...ON Pickup value In 0 100 0 999 step 0 001 1 00 9 99 step 0 01 10 0 40 0 step 0 1 I def within CLP ICLP def In 0 100 0 999 step 0 001 1 00 9 99 step 0 01 10 0 40 0 step 0 1 I def Operating time Value s...

Страница 216: ...F ON IE Breaker failure IE BF OFF ON IE Start relays IE ST K K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 IE Trip relays IE TR K K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 IE Start LEDs IE ST L START TRIP L1 L2 L3 L4 L5 L6 L7...

Страница 217: ...me Value s 0 03 10 00 step 0 01 IE Element Setpoints IE Enable IE Enable OFF ON IECLP Mode IECLP Mode OFF ON Element blocking ON Change setting IECLP Activation time Value s 0 00 9 99 step 0 01 10 0 1...

Страница 218: ...Un 0 50 1 50 step 0 01 U inv Operating time tU inv s 0 10 9 99 step 0 01 10 0 100 0 step 0 1 U Element Setpoints U Logical block U BLK1 OFF ON U Breaker failure U BF OFF ON U Disabling by U start U di...

Страница 219: ...K6 K7 K8 K9 K10 Phase and ground protections output selective block relays BLK2OUT Iph IE K K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 Phase protections output selective block LEDs BLK2OUT Iph L START TRIP L1 L2...

Страница 220: ...6 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92...

Страница 221: ...mer 6 s 0 00 0 99 step 0 01 1 0 60 0 step 0 1 Timer 7 s 0 00 0 99 step 0 01 1 0 60 0 step 0 1 Timer 8 s 0 00 0 99 step 0 01 1 0 60 0 step 0 1 Timer 9 s 0 0 59 9 step 0 1 60 299 step 1 300 3600 step 10...

Страница 222: ...ipping I 2t threshold SumI 2t In 2s 0 5000 step 1 CB operating time mode Mode tOpen OFF ON Trigger relay for CB opening time trigger measurement Ktrig break K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 Circuit brea...

Страница 223: ...e Trigger Stopped Wait Fail Off Records 0 0 step 0 Buffer storage 0 0 step 0 Trigger Setup Pre trigger time s 0 05 1 00 step 0 01 Post trigger time s 0 05 60 00 step 0 05 Element pickup trigger ON OFF...

Страница 224: ...uency IL1rms IL1 UL1 IL2rms IL2 UL2 IL3rms IL3 UL3 IN PhiN INC PhiNC IEC I2 T1 T2 T3 T4 T5 T6 T7 T8 Off Set digital channels Binary 1 K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 IN1 IN2 Off Binary 2 K1 K2 K3 K4 K5...

Страница 225: ...irobi S Petersburg UTC 4 Baku Dubai Mauritius Samara Tbilisi UTC 5 Karachi Maldives Tashkent Yekaterinburg UTC 6 Almaty Dhaka Omsk UTC 1 Azores CapoVerde UTC 2 Mid Atlantic UTC 3 Brasilia Bueno sAires...

Страница 226: ...ThySetter 3 6 9 ThySetter 3 6 11 18 03 2013 11 2013 03 2014 01 2015 First edition PLC description 26 element ThySetter description removed dedicated manual Current inputs burden output relays breaking...

Страница 227: ...ctive EMC Directive Reference of standards and or technical speci cations applied for this declaration of conformity or parts thereof harmonized standards Reference n Issue Title EN 61010 1 EN 50263 E...

Отзывы: