damage due to vibration of the panel enclosure.
Check that all cables are firmly held in the terminal
blocks & Earth bars. Check that the Earth Bars are
firmly fixed to the enclosure. Check that all Earth
leads are correctly & firmly connected. Check that
End-Of-Line resistors in unused circuits are
positioned in a safe manner and are unlikely to
create short circuit faults due to movement. It is
advised that unused EOL resistors have insulating
sleeving placed on the leads for safety.
[Caution - do not over-tighten]
EOL
RESISTOR
KEEP
LEAD
SHORT
SLEEVING
ON LEAD
Unused
Circuit
Terminals