chassis are fully mounted onto the posts in the 
back-box. 

21.  Reconnect all earth wires and ensure none are 

trapped between the chassis and back-box. Do 
not connect the field wiring at this stage. 

22.  Refit  the  door.  The  refitting  procedure  is  the 

reverse of removal. Ensure that the earth strap 
and ribbon cable are reconnected correctly. 

23.  If a door stay is supplied then this should now 

be  fitted  following  the  instructions  in  section 
5.5.2. 

24.  Connect 

the 

incoming 

protective 

earth 

conductor  to  the  Earth  terminal  in  the  mains 
terminal  block.  This  is  the  primary  earth  point 

and  is  labelled 

  [Also  labelled  E];  see 

section 12. Wiring Diagrams. 

25. 

NOTE

:  When  shutting  the  door  of  the  panel, 

DO  NOT  over  tighten  the  thumb-screws. 
Tighten  until  finger-tight  and  then  turn  another 
quarter-turn using a screwdriver. 

5.2.2  Connection of the incoming AC 

Power Supply 

Note:  For  installations  requiring  the  Mains  AC 
switch-over  unit,  a  24Vdc  supply  will  need  to  be 
connected  from  the  panel  to  the  AC  mains  switch-
over  unit  to  drive  the  LED  indications.  See  Figure 
17 for wiring details. 

1. 

With  both  poles  of  the  incoming  power  supply 
safely  isolated  at  the  feeder  end,  connect  the 
Live  [AC]  conductor  to  the  mains  terminal 
block  [L  terminal]  as  shown  in  section  12. 
Wiring Diagrams. 

2. 

Connect  the  Neutral  [AC]  conductor  to  the 
mains  terminal  block  [N  terminal]  as  shown  in 
section 12. Wiring Diagrams. 

3. 

Secure  the  incoming  supply  cable  using  the 
cable tie supplied. 

NOTE

: The cable tie should 

be over the outer cable insulation. 

5.2.3  T1200B-C Battery Box Installation 

The  T1200B-C  battery  box  can  only  be  bulk  head 
mounted. The  incoming  cable  must  have  an  in-line 
fuse in the  positive power  supply (fuse type: T6.3A 
HRC).  The  fuse  must  be  mounted  external  to  the 
battery  box,  in  a  suitable  terminal  box  which  is 
close-coupled to the battery box. See Figure 19 for 
wiring details. 

To mount the T1200B-C battery box: 

(a)  Identify  the  three  indented  holes  in  the  back 

of  the  enclosure  that  are  used  to  mount  the 
enclosure. 

(b)  Mark  the  location  of  one  of  the  upper  fixing 

holes  on  the  wall/bulkhead.  Drill  and  fix  with 
a  suitably  plated  or  stainless  steel  M5  nut, 
bolt  and  washers  (fixings  not  supplied).  The 
fixing  must  be  sealed  using  two  neoprene 

washers  [supplied  with  the  fixing  kit],  one 
fitted  between  the  panel  and  the  bulkhead 
and  the  other  fitted  between  the  panel  and 
the steel washer inside the panel. See Figure 

– Bulk Head Mounting Details. Do not fully 

tighten at this stage. 

(c)  Level  the  enclosure  and  fix  the  remaining 

fixing points as above. 

(d)  Check  that  neoprene  seals  have  been  fitted 

as  shown  in  Figure  1  then  fully  tighten  all  of 
the fixing nuts & bolts. 

(e)  Check  that  the  enclosure  is  firmly  seated 

against the bulk head and is not deformed in 
any way. 

(f)  Mount  the  fused  terminal  box  (not  supplied) 

adjacent  to  the  battery  box  and  fit  a  suitable 
waterproof coupling to allow cable entry from 
the terminal box to the battery box. 

5.2.4  Battery Installation 

The  T1200B-C  battery  box  will  only  hold  2  x  17Ah 
PowerSonic SLA batteries. 

1. 

Remove  the  battery  clamps  from  the  battery 
box before fitting the batteries. 

2. 

Place the left-hand battery into the battery box. 
The  battery  should  be  located  toward  the  left 
side  of  the  enclosure,  the  battery  terminals 
should be positioned towards the front. 

3. 

Place  the  right-hand  battery  into  the  battery 
box. The battery should be located toward the 
right  side  of  the  enclosure,  the  battery 
terminals  should  be  positioned  towards  the 
front. 

4. 

Fix the battery retaining clamps. [See Figure 2] 

5.2.5  Battery Connection 

1. 

Connect  the  black  battery  lead  to  the  terminal 
marked  BAT-,  connect  the  red  battery  lead  to 
the terminal marked BAT+. 

2. 

The  Thermistor  assembly  is  supplied  loose  in 
the  fixing  kit  supplied  with  the  T1216W-C 
panel.  Connect  the  Thermistor  leads  to  the 
terminals marked THERM. 

3. 

Tie-wrap  the  Thermistor  to  one  of  the  battery 
leads  so  that  when  the  battery  leads  are 
connected,  the  Thermistor  is  located  just 
above one of the batteries. 

4. 

The blue lead is used to connect the batteries 
together. Do not connect this lead until you are 
ready to power up the panel. 

Содержание TYCO T1216W-C

Страница 1: ...12 2012 Thorn Security Ltd PAGE 1 of 39 Registered Company Thorn Security Ltd Registered Office Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE TYCO T1216W C Marine Fire Detection Alarm Con...

Страница 2: ...EW OF THE COMMISSIONING PROCEDURE 17 6 4 PRE COMMISSIONING WIRING CHECK 17 6 5 POWERING UP 18 6 6 CONFIGURATION 19 6 6 1 BASIC DEFAULT CONFIGURATION 19 6 6 2 VESSEL SPECIFIC CONFIGURATION 19 7 OPERATI...

Страница 3: ...D SIDE OF DISPLAY PCB 32 FIGURE 12 C1634 RELAY OUTPUT MODULE 32 FIGURE 13 C1630 OUTPUT EXPANSION INTERFACE 33 FIGURE 14 C1631 REPEATER INTERFACE BOARD 33 FIGURE 15 C1665 MUSTER INTERFACE BOARD 33 FIGU...

Страница 4: ...plicable Refer to the installation instructions in section 5 2 4 Commission the panel Refer to section 6 Commissioning 5 Installation The control panel must be installed by suitably qualified technici...

Страница 5: ...and battery swelling Batteries are irrecoverable from this condition and should be replaced LOW TEMPERATURE will prolong battery life but reduce output capacity DANGER Do not incinerate batteries If...

Страница 6: ...secure the door shut The screws will remain attached to the door 4 Open the door Note that the door will open past 180 degrees and will put tension on the hinges if no support is provided underneath...

Страница 7: ...eck that neoprene seals have been fitted as shown in Figure 1 then fully tighten all of the fixing nuts bolts e Check that the enclosure is firmly seated against the bulk head and is not deformed in a...

Страница 8: ...s in the back of the enclosure that are used to mount the enclosure b Mark the location of one of the upper fixing holes on the wall bulkhead Drill and fix with a suitably plated or stainless steel M5...

Страница 9: ...to the repeater You can use two cores in the data cable for this purpose only if the voltage drop between the panel and repeater is not more than 2Vdc Notes One repeater will draw up to 75mA which me...

Страница 10: ...t St an da rd s A pp ro va l 00 86 0 9 K M 95 74 4 F ir e A la rm S y s te m Is ol at e Su pp ly B ef or e 00 86 C PD 5 55 92 1 O pe ni ng C ov er TH IS U N IT M U ST B E EA R TH ED RATING LABEL T h...

Страница 11: ...ff Top right hand corner of C1626 motherboard Figure 3 Repeater connection diagram M in Sin GND GND M out S out C1665 Muster Interface in Fire Panel M in Sin GND GND M out S out C1665 Muster Interface...

Страница 12: ...in series with R50 2 6k8 Resistor TB5 3 TB5 4 313 314 R50 2 De energised fault condition Before Modification 10k Resistor TB5 3 TB5 4 313 314 R50 2 De energised fault condition After Modification Wir...

Страница 13: ...necessary permits to work are in place The Engineer responsible for the commissioning of the WMRCP system is available and a procedure is in place which includes the allocation of the various tasks a...

Страница 14: ...rm the other side identifies this switch as Muster Additional double sided inserts may be supplied for Chinese or Japanese applications 5 5 1 To change the inserts 1 Isolate the mains supply to the pa...

Страница 15: ...nut by turning the nut a quarter of a turn Press the frame against the enclosure door using fingers only and check for any slack 22 Repeat step 21 until the frame is firmly seated Note Over tightenin...

Страница 16: ...hinge These are used to secure the door stay enclosure mounting bracket 6 Offer the door stay door mounting bracket up to the studs on the display frame as shown in Figure 9 and fit one M6 washer and...

Страница 17: ...basic wiring continuity is proven 6 3 An Overview of the Commissioning Procedure Commissioning is broken in to 3 sections 1 Pre commissioning wiring check 2 Powering the panel up with no field wiring...

Страница 18: ...between the IS barrier and the end of line resistor will support open circuit fault monitoring only short circuit fault will raise a detector fire It will not support detector MCP discrimination all...

Страница 19: ...tively Charts are provided in the System Log Book for planning recording the actual configuration This configuration is not lost when the panel is powered down 7 Operating the Engineer s functions 7 1...

Страница 20: ...Any current alarms disablements will be re indicated along with any active status indications Delay on etc o Close and lock the panel door o Return the ACCESS keyswitch to the 0 position to disable th...

Страница 21: ...Zones o OFF Configuration mode disabled o ON Enables selected zones to be configured to non latching fire mode via the Engineer s Select feature Not EN54 compliant function SW 1 5 Config I S Zones o...

Страница 22: ...immediately if there is a fire in a machinery space zone but will be delayed for 2 minutes for a fire on any other zone Sounder circuits 3 4 on the control board and any output board sounder circuits...

Страница 23: ...lt Output Fault monitored powered O P J6 J7 J8 Fitted C1627 motherboard to the right of the Fault Routing Output relay Volt Free C O relay O P Removed Fire Protection Output Fault monitored powered O...

Страница 24: ...d type of output expansion boards are set on DIL switches on the C1630 For the standard T1216W C panel the C1630 will be configured at works prior to dispatch If further output expansion modules are t...

Страница 25: ...Engine Top Zone 2 O P 2 Main Engine Top Zone 3 O P 3 Generator Sets 1 2 3 Zone 4 O P 4 Generator Sets 1 2 3 Zone 5 O P 5 Generator Engine 4 Zone 6 O P 6 Generator Engine 4 Zone 7 O P 7 Purifier Space...

Страница 26: ...ate a fire condition on a zone to operate the output Check that the fire signal operates the interface relay adjacent to the fire protection equipment 4 Open circuit the field wiring and confirm that...

Страница 27: ...he primary supply Note The battery requires a period in excess of 24hrs to achieve a fully charged condition 7 9 12 T1216W C WMRCP Interface This work must be carried out in conjunction with the Engin...

Страница 28: ...enclosure Check that all Earth leads are correctly firmly connected Check that End Of Line resistors in unused circuits are positioned in a safe manner and are unlikely to create short circuit faults...

Страница 29: ...led Yellow Flashes for a fault on the Fire Output Steady when Fire Output is disabled Fault Output Fault Disabled Yellow Flashes for a fault on the Fault Output Steady when Fault Output is disabled 1...

Страница 30: ...When controls are unlocked Reset Resets any standing fire and or fault conditions When controls are unlocked and panel has fire and or fault conditions Silence Buzzer Press to stop the buzzer soundin...

Страница 31: ...SW1 1 to SW1 10 J18 Earth Fault Monitoring Link Connector for C1632 Zone Expansion Board Alarm Circuits Marked with Active Polarity Aux DC Supply 24V 0V Remote Inputs Silence Alarms Evacuate Reset Aux...

Страница 32: ...osition Muster mode Link removed Evacuate Muster modes disabled Figure 11 Rear Right Hand Side of Display PCB SW1Config switch Top to bottom AD0 AD1 ZN0 ZN1 ZONAL VDR OFF Comms Fault LED J2 Comms In o...

Страница 33: ...ity and type of O P modules connected From top to bottom F P0 Fire Protection F P1 Fire Protection S C0 Sounder Controller S C1 Sounder controller LED0 LED driver LED1 LED driver VDR Voyage Data Recor...

Страница 34: ...DIMENSIONS SHOWN WITH BOTTOM ENTRY CABLE GLAND PLATE IF TOP ENTRY REQUIRED REVERSE DIMENSIONS ENCLOSURE ENCLOSED SPACES SUBJECT TO TEMPERATURE HUMIDITY VIBRATION TECHNICAL DATA DIMENSIONS 400mm WIDE x...

Страница 35: ...PPLY INCOMING PRIMARY AC MAINS SUPPLY OUTGOING AC MAINS SUPPLY TO PANEL INCOMING 24Vdc SUPPLY FROM PANEL 24V 0V AUX D C 24V 0V 4 SIL EVAC RST Panel Motherboard Auxiliary 24Vdc Terminals Mains Terminal...

Страница 36: ...erminals C1634 Relay O P module address 2 zonal outputs 9 14 to Watermist panel C1634 Relay O P module address 1 zonal outputs 1 8 to Watermist panel Gland Plate Earth Wiring Screen Earth Terminal Blo...

Страница 37: ...ect return to Aux 24V Zones 2 8 10k end of line resistor Zones 9 16 10k end of line resistor Field wiring terminals on panel PCB Detector base Manual Call Point Sounder 3k9 end of line resistor Aux 24...

Страница 38: ...80R 1W activation resistor Z15 Z16 Z15 Z16 Wire Links Zones 15 16 from T1216W C panel 9 10 7 8 5 6 TB2 RL FLT I F Fault Signal from from T1216W C panel Watermist Control Panel Modification Note 1 Mods...

Страница 39: ...with a suppression diode as shown in Figure 20 4 Remote Inputs Silence Alarms Evacuate Reset Class Change Connections Connect to 0V AUX DC via the Normally Open contact inactive condition 5 Remote Ou...

Отзывы:

Похожие инструкции для TYCO T1216W-C