background image

T1216W-C

 

MARINEW-P-I

 

11/12

 

PAGE 26 of 39 

 

buttons  after  each  device  test  and  check  the 
alarm  clears  (Manual  Call  Points  must  be 
manually reset before resetting the panel). 

3.  Detector removal operation: 

o

  Remove the 1st detector along the zone cable 

[counting  from  the  panel]  on  zone  1  and 
observe the following: 

  The  appropriate  amber  zone  fault  LED 

illuminates. 

  The internal buzzer sounds. 

  The fault relay operates. 

  Refit  the  detector  and  check  that  the  control 

panel returns to its normal state. 

  Continue  to  test  each  of  the  other  detectors 

in turn, checking on each removal that: 

  The  appropriate  amber  zone  fault  LED 

illuminates. 

  The internal buzzer sounds. 

  The fault relay operates. 

4.  Any  faults  that  are  found  must  be  traced  and 

rectified before proceeding. 

5.  Repeat steps 1 to 4, one zone at a time, until all 

the zones are commissioned. 

7.9.3  Class Change Input  

This is not a marine function. 

7.9.4  Fire [Routing] Output 

1.  Remove the resistor from the Fire  Output circuit 

terminals  and  connect  the  field  wiring  to  the 
terminals,  observing  correct  polarity.  Check  that 
any fault indications clear after a few seconds. 

2.  To operate the output, initiate a fire condition on 

a  zone.  Check  that  the  fire  signal  is  received  at 
the  receiving  station.  Silence  and  reset  the  fire 
alarm panel to clear the output. 

3.  Open-circuit  the  output  wiring  of  each  circuit  in 

turn.  Confirm  the  fire  alarm  panel  indicates  Fire 
Routing and Fault Output faults appropriately. 

4.  Reconnect  the  cabling  and  confirm  the  faults 

clear. 

7.9.5  Fault [Routing] Output 

See section 7.9.12 below. 

7.9.6  Fire Protection Output 

1.  Ensure  any  fire  protection  equipment  to  be 

controlled via the Fire Protection output is locked 
off/safe  before  attempting  any  connection, 
testing or commissioning. 

2.  Remove  the  resistor  from  the  Fire  Protection 

output  circuit  terminal  and  connect  the  field 
wiring  to  the  terminals,  observing  correct 
polarity.  Check  that  any  fault  indications  clear 
after a few seconds. 

3.  Initiate a fire condition  on  a  zone to operate the 

output.  Check  that  the  fire  signal  operates  the 
interface  relay  adjacent  to  the  fire  protection 
equipment. 

4.  Open-circuit the field wiring and confirm that the 

fire  alarm  panel  indicates  a  Fire  Protection 
output fault. 

5.  Reconnect  the  cabling  and  confirm  the  faults 

clear. 

6.  Final  testing  and  commissioning  of  the  loop 

through  to  the  fire  protection  equipment, 
including  test  [simulated]  activation  of  the 
equipment,  should  be  carried  out  at  the 
appropriate time in conjunction with the engineer 
responsible for the fire protection system. 

7.9.7  Ancillary inputs 

Remote  Silence  Alarms,  Reset  and  Evacuate 
[Manual  fire  alarm/Muster]  inputs  should  each  be 
tested  by  the  activation  of  the  remote  equipment. 
The response should be verified for each signal. 

7.9.8  Ancillary outputs 

The  correct  operation  of  equipment  connected  to 
the  Zone  Outputs,  Disablement  Active,  Evacuate 
[Manual fire alarm/Muster] Active and Buzzer Active 
outputs should be verified  in turn by initiating a fire 
condition  on  each  of  the  appropriate  zones; 
disabling/enabling a zone; operating the Manual fire 
alarm/Muster  and  Buzzer  Silence  buttons  on  the 
panel’s display. 

7.9.9  Repeaters [when supplied] 

1. 

Power-up  the  Panel.  At  the  Repeater(s),  only 
the  “Power  Supply  On”  LED  should  be 
illuminated on the Panel and Repeaters. 

2. 

At  Repeater  1,  turn  the  Access  control  switch 
to  “1”,  and  press  the  “Manual  fire  alarm” 
button. Check that the alarms operate and the 
internal buzzer operates on all repeaters. 

3. 

Press  the  “Silence”  button  on  the  fire  alarm 
panel.  Check  that  the  alarm  circuits  silence 
and  the  internal  buzzer  silences  on  all 
repeaters. 

4. 

Repeat steps 2 and 3 for each repeater. 

5. 

Operate  a  Manual  Call  Point  on  zone  1  and 
check  for  correct  fire  indication  at  each 
repeater. 

6. 

Press  the  “Silence  Alarms”  button  on  a 
repeater  and  check  that  the  alarms  are 
silenced and the Zone 1 fire LED is constantly 
illuminated on all repeater panels. 

7. 

Press  the  “Reset”  button  on  a  repeater  and 
check  that  the  panel  and  repeaters  return  to 
the quiescent state. 

8. 

Repeat steps 5 to 7 for each zone and ensure 
“Silence Alarms” and “Reset” operate correctly 
from each repeater. 

Содержание TYCO T1216W-C

Страница 1: ...12 2012 Thorn Security Ltd PAGE 1 of 39 Registered Company Thorn Security Ltd Registered Office Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE TYCO T1216W C Marine Fire Detection Alarm Con...

Страница 2: ...EW OF THE COMMISSIONING PROCEDURE 17 6 4 PRE COMMISSIONING WIRING CHECK 17 6 5 POWERING UP 18 6 6 CONFIGURATION 19 6 6 1 BASIC DEFAULT CONFIGURATION 19 6 6 2 VESSEL SPECIFIC CONFIGURATION 19 7 OPERATI...

Страница 3: ...D SIDE OF DISPLAY PCB 32 FIGURE 12 C1634 RELAY OUTPUT MODULE 32 FIGURE 13 C1630 OUTPUT EXPANSION INTERFACE 33 FIGURE 14 C1631 REPEATER INTERFACE BOARD 33 FIGURE 15 C1665 MUSTER INTERFACE BOARD 33 FIGU...

Страница 4: ...plicable Refer to the installation instructions in section 5 2 4 Commission the panel Refer to section 6 Commissioning 5 Installation The control panel must be installed by suitably qualified technici...

Страница 5: ...and battery swelling Batteries are irrecoverable from this condition and should be replaced LOW TEMPERATURE will prolong battery life but reduce output capacity DANGER Do not incinerate batteries If...

Страница 6: ...secure the door shut The screws will remain attached to the door 4 Open the door Note that the door will open past 180 degrees and will put tension on the hinges if no support is provided underneath...

Страница 7: ...eck that neoprene seals have been fitted as shown in Figure 1 then fully tighten all of the fixing nuts bolts e Check that the enclosure is firmly seated against the bulk head and is not deformed in a...

Страница 8: ...s in the back of the enclosure that are used to mount the enclosure b Mark the location of one of the upper fixing holes on the wall bulkhead Drill and fix with a suitably plated or stainless steel M5...

Страница 9: ...to the repeater You can use two cores in the data cable for this purpose only if the voltage drop between the panel and repeater is not more than 2Vdc Notes One repeater will draw up to 75mA which me...

Страница 10: ...t St an da rd s A pp ro va l 00 86 0 9 K M 95 74 4 F ir e A la rm S y s te m Is ol at e Su pp ly B ef or e 00 86 C PD 5 55 92 1 O pe ni ng C ov er TH IS U N IT M U ST B E EA R TH ED RATING LABEL T h...

Страница 11: ...ff Top right hand corner of C1626 motherboard Figure 3 Repeater connection diagram M in Sin GND GND M out S out C1665 Muster Interface in Fire Panel M in Sin GND GND M out S out C1665 Muster Interface...

Страница 12: ...in series with R50 2 6k8 Resistor TB5 3 TB5 4 313 314 R50 2 De energised fault condition Before Modification 10k Resistor TB5 3 TB5 4 313 314 R50 2 De energised fault condition After Modification Wir...

Страница 13: ...necessary permits to work are in place The Engineer responsible for the commissioning of the WMRCP system is available and a procedure is in place which includes the allocation of the various tasks a...

Страница 14: ...rm the other side identifies this switch as Muster Additional double sided inserts may be supplied for Chinese or Japanese applications 5 5 1 To change the inserts 1 Isolate the mains supply to the pa...

Страница 15: ...nut by turning the nut a quarter of a turn Press the frame against the enclosure door using fingers only and check for any slack 22 Repeat step 21 until the frame is firmly seated Note Over tightenin...

Страница 16: ...hinge These are used to secure the door stay enclosure mounting bracket 6 Offer the door stay door mounting bracket up to the studs on the display frame as shown in Figure 9 and fit one M6 washer and...

Страница 17: ...basic wiring continuity is proven 6 3 An Overview of the Commissioning Procedure Commissioning is broken in to 3 sections 1 Pre commissioning wiring check 2 Powering the panel up with no field wiring...

Страница 18: ...between the IS barrier and the end of line resistor will support open circuit fault monitoring only short circuit fault will raise a detector fire It will not support detector MCP discrimination all...

Страница 19: ...tively Charts are provided in the System Log Book for planning recording the actual configuration This configuration is not lost when the panel is powered down 7 Operating the Engineer s functions 7 1...

Страница 20: ...Any current alarms disablements will be re indicated along with any active status indications Delay on etc o Close and lock the panel door o Return the ACCESS keyswitch to the 0 position to disable th...

Страница 21: ...Zones o OFF Configuration mode disabled o ON Enables selected zones to be configured to non latching fire mode via the Engineer s Select feature Not EN54 compliant function SW 1 5 Config I S Zones o...

Страница 22: ...immediately if there is a fire in a machinery space zone but will be delayed for 2 minutes for a fire on any other zone Sounder circuits 3 4 on the control board and any output board sounder circuits...

Страница 23: ...lt Output Fault monitored powered O P J6 J7 J8 Fitted C1627 motherboard to the right of the Fault Routing Output relay Volt Free C O relay O P Removed Fire Protection Output Fault monitored powered O...

Страница 24: ...d type of output expansion boards are set on DIL switches on the C1630 For the standard T1216W C panel the C1630 will be configured at works prior to dispatch If further output expansion modules are t...

Страница 25: ...Engine Top Zone 2 O P 2 Main Engine Top Zone 3 O P 3 Generator Sets 1 2 3 Zone 4 O P 4 Generator Sets 1 2 3 Zone 5 O P 5 Generator Engine 4 Zone 6 O P 6 Generator Engine 4 Zone 7 O P 7 Purifier Space...

Страница 26: ...ate a fire condition on a zone to operate the output Check that the fire signal operates the interface relay adjacent to the fire protection equipment 4 Open circuit the field wiring and confirm that...

Страница 27: ...he primary supply Note The battery requires a period in excess of 24hrs to achieve a fully charged condition 7 9 12 T1216W C WMRCP Interface This work must be carried out in conjunction with the Engin...

Страница 28: ...enclosure Check that all Earth leads are correctly firmly connected Check that End Of Line resistors in unused circuits are positioned in a safe manner and are unlikely to create short circuit faults...

Страница 29: ...led Yellow Flashes for a fault on the Fire Output Steady when Fire Output is disabled Fault Output Fault Disabled Yellow Flashes for a fault on the Fault Output Steady when Fault Output is disabled 1...

Страница 30: ...When controls are unlocked Reset Resets any standing fire and or fault conditions When controls are unlocked and panel has fire and or fault conditions Silence Buzzer Press to stop the buzzer soundin...

Страница 31: ...SW1 1 to SW1 10 J18 Earth Fault Monitoring Link Connector for C1632 Zone Expansion Board Alarm Circuits Marked with Active Polarity Aux DC Supply 24V 0V Remote Inputs Silence Alarms Evacuate Reset Aux...

Страница 32: ...osition Muster mode Link removed Evacuate Muster modes disabled Figure 11 Rear Right Hand Side of Display PCB SW1Config switch Top to bottom AD0 AD1 ZN0 ZN1 ZONAL VDR OFF Comms Fault LED J2 Comms In o...

Страница 33: ...ity and type of O P modules connected From top to bottom F P0 Fire Protection F P1 Fire Protection S C0 Sounder Controller S C1 Sounder controller LED0 LED driver LED1 LED driver VDR Voyage Data Recor...

Страница 34: ...DIMENSIONS SHOWN WITH BOTTOM ENTRY CABLE GLAND PLATE IF TOP ENTRY REQUIRED REVERSE DIMENSIONS ENCLOSURE ENCLOSED SPACES SUBJECT TO TEMPERATURE HUMIDITY VIBRATION TECHNICAL DATA DIMENSIONS 400mm WIDE x...

Страница 35: ...PPLY INCOMING PRIMARY AC MAINS SUPPLY OUTGOING AC MAINS SUPPLY TO PANEL INCOMING 24Vdc SUPPLY FROM PANEL 24V 0V AUX D C 24V 0V 4 SIL EVAC RST Panel Motherboard Auxiliary 24Vdc Terminals Mains Terminal...

Страница 36: ...erminals C1634 Relay O P module address 2 zonal outputs 9 14 to Watermist panel C1634 Relay O P module address 1 zonal outputs 1 8 to Watermist panel Gland Plate Earth Wiring Screen Earth Terminal Blo...

Страница 37: ...ect return to Aux 24V Zones 2 8 10k end of line resistor Zones 9 16 10k end of line resistor Field wiring terminals on panel PCB Detector base Manual Call Point Sounder 3k9 end of line resistor Aux 24...

Страница 38: ...80R 1W activation resistor Z15 Z16 Z15 Z16 Wire Links Zones 15 16 from T1216W C panel 9 10 7 8 5 6 TB2 RL FLT I F Fault Signal from from T1216W C panel Watermist Control Panel Modification Note 1 Mods...

Страница 39: ...with a suppression diode as shown in Figure 20 4 Remote Inputs Silence Alarms Evacuate Reset Class Change Connections Connect to 0V AUX DC via the Normally Open contact inactive condition 5 Remote Ou...

Отзывы: