PAGE 27 of 39 

Registered Company: Thorn Security Ltd.  Registered Office: Dunhams Lane  Letchworth Garden City  Hertfordshire  SG6 1BE

 

9. 

Set  the  DIL  switches  on  the  C1631  Repeater 
Interface card  in the fire alarm panel OFF (No 
Repeaters). Check that all repeaters indicate a 
“Comms. Fault”. 

10.  Set  the  C1631  Repeater  Interface  card  DIL 

switches  in  the  fire  alarm  panel  back  to  their 
previous settings and check that the repeaters 
return to normal. 

11.  Set the first repeater  address to 0. Check that 

the panel indicates a “Repeater fault” and any 
additional  repeaters  display  a  steady  “Comms 
fault” LED. 

12.  Set  the  repeater  address  back  to  normal  and 

check  that  the  panel  and  repeaters  return  to 
normal. 

13.  Repeat  steps  11  and  12  for  any  other 

connected repeaters. 

7.9.10 Repeater Muster link [if fitted] 

1. 

On  repeater  1,  select  the  Access  Controls 
switch  to  position  1  and  press  the  Muster 
button on the display.  

2. 

Check  the  fire  panel  and  the  fire  alarm 
sounders respond correctly. 

3. 

On repeater 1, press the Silence Alarms button 
and  check  that  the  fire  alarm  panel  responds 
correctly  and  the  fire  alarm  sounders  cease 
operating. 

4. 

Repeat  steps  1,  to  3  at  each  repeater  panel 
fitted with a muster interface board. 

5. 

At  the  last  repeater  panel  disconnect  one  of 
the  3k9  resistors  connected  to  the  C1665  and 
check  the  fire  alarm  panel  reports  “Repeater 
Fault”. 

6. 

Reconnect the resistor & confirm the Repeater 
Fault clears at the fire alarm panel. 

7. 

Disconnect  the  other  resistor  and  confirm  the 
Repeater Fault at the fire alarm panel. 

8. 

Reconnect  the  resistor  and  confirm  the  fault 
signal clears. 

7.9.11 Power Supply Unit. 

 

Ensure  that  the  system  is  fully  commissioned 
with  all  output  circuits  loaded  as  required  by 
the system design. 

 

Ensure that the battery has been on charge for 
at least 2 hours.  

 

Isolate  the  primary  power  supply  feed  to  the 
panel. 

 

Check the panel indicates power supply fault. 

 

Operate Test Alarms to load the panel. 

 

Confirm  that  the  system  continues  to  respond 
correctly during the test. 

 

Quit the test and restore the primary supply. 

Note: The battery requires a period in excess of 
24hrs to achieve a fully charged condition.

 

7.9.12 T1216W-C 

– WMRCP Interface. 

This  work  must  be  carried  out  in  conjunction 
with 

the 

Engineer 

responsible 

for 

the 

commissioning of the Watermist System. 

Before  commencing  commissioning  of  the 
interface,  ensure  the  Watermist  System  is 
suitably  disabled  such  that  the  functionality 
associated with the interface can be fully tested 
and  proven  without  risk  of  damage  to  other 
plant/equipment or risk of injury to personnel. 

Any necessary permit to work must be in place 
and strictly observed. 

1. 

Recheck the cable cores at the T1216W-C and 
WMRCP  for  correct  polarity  before  final 
connection of the interface wiring. 

2. 

Reconnect  the  interface  wiring  at  T1216W-C 
and WMRCP in turn. 

3. 

Power  up  the  T1216W-C  and  check  that  the 
following  indications  associated  with  the 
WMRCP  correctly  represent  the  WMRCP 
status: 

Zone 15

–[System Activated] - No alarm. 

Zone 16

–[System Abnormal] - Fault [because 

the WMRCP is de-energised]. 

4. 

Ensure  that  the  T1216W-C  is  in  the  quiescent 
state. 

5. 

Power up the WMRCP and check that none of 
the  Watermist  fire  protection  zones  are 
actuated. 

6. 

At the T1216W-C, check that Zone 16 [System 
Abnormal] Fault clears. 

7. 

At  the  T1216W-C,  initiate  any  fault  condition 
and  confirm  the  correct  response  at  the 
WMRCP.  The  WMRCP  will  also  send  this 
signal  back  to  the  T1216W-C  and  indicate  a 
fault  on  Zone  16.  Clear  the  fault  condition  on 
the  T1216W-C  and  confirm  both  panels  clear 
down. 

8. 

Single  knock  fire  tests:  Trigger  a  fire  detector 
in each detection circuit starting at zone circuit 
1  through  to  14. 

Reset  the  T1216W-C  after 

each  circuit  test

.  Check  the  correct  fire 

indication  is  given  on  the  T1216W-C  and  that 
the Watermist system is not activated. 

9. 

Double  knock  fire  tests:  Trigger  a  fire  detector 
on  both  detection  circuits  in  each  Watermist 
fire  protection  zone  starting  at  zone  1  through 
to  7.  Check  the  correct  Watermist  fire 
protection system is activated for each test and 
that  Zone  15  on  the  T1216W-C  indicates  an 
alarm  in  response  to  receiving  the  System 
Activated signal from the WMRCP. 

7.9.13 Final Dressing of the Cables 

Ensure that the field conductors are secure and tidy 
inside  the  enclosure.  Use  Tie-wraps  to  secure  any 
long  conductors  or  looms  which  might  be  prone  to 

Содержание TYCO T1216W-C

Страница 1: ...12 2012 Thorn Security Ltd PAGE 1 of 39 Registered Company Thorn Security Ltd Registered Office Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE TYCO T1216W C Marine Fire Detection Alarm Con...

Страница 2: ...EW OF THE COMMISSIONING PROCEDURE 17 6 4 PRE COMMISSIONING WIRING CHECK 17 6 5 POWERING UP 18 6 6 CONFIGURATION 19 6 6 1 BASIC DEFAULT CONFIGURATION 19 6 6 2 VESSEL SPECIFIC CONFIGURATION 19 7 OPERATI...

Страница 3: ...D SIDE OF DISPLAY PCB 32 FIGURE 12 C1634 RELAY OUTPUT MODULE 32 FIGURE 13 C1630 OUTPUT EXPANSION INTERFACE 33 FIGURE 14 C1631 REPEATER INTERFACE BOARD 33 FIGURE 15 C1665 MUSTER INTERFACE BOARD 33 FIGU...

Страница 4: ...plicable Refer to the installation instructions in section 5 2 4 Commission the panel Refer to section 6 Commissioning 5 Installation The control panel must be installed by suitably qualified technici...

Страница 5: ...and battery swelling Batteries are irrecoverable from this condition and should be replaced LOW TEMPERATURE will prolong battery life but reduce output capacity DANGER Do not incinerate batteries If...

Страница 6: ...secure the door shut The screws will remain attached to the door 4 Open the door Note that the door will open past 180 degrees and will put tension on the hinges if no support is provided underneath...

Страница 7: ...eck that neoprene seals have been fitted as shown in Figure 1 then fully tighten all of the fixing nuts bolts e Check that the enclosure is firmly seated against the bulk head and is not deformed in a...

Страница 8: ...s in the back of the enclosure that are used to mount the enclosure b Mark the location of one of the upper fixing holes on the wall bulkhead Drill and fix with a suitably plated or stainless steel M5...

Страница 9: ...to the repeater You can use two cores in the data cable for this purpose only if the voltage drop between the panel and repeater is not more than 2Vdc Notes One repeater will draw up to 75mA which me...

Страница 10: ...t St an da rd s A pp ro va l 00 86 0 9 K M 95 74 4 F ir e A la rm S y s te m Is ol at e Su pp ly B ef or e 00 86 C PD 5 55 92 1 O pe ni ng C ov er TH IS U N IT M U ST B E EA R TH ED RATING LABEL T h...

Страница 11: ...ff Top right hand corner of C1626 motherboard Figure 3 Repeater connection diagram M in Sin GND GND M out S out C1665 Muster Interface in Fire Panel M in Sin GND GND M out S out C1665 Muster Interface...

Страница 12: ...in series with R50 2 6k8 Resistor TB5 3 TB5 4 313 314 R50 2 De energised fault condition Before Modification 10k Resistor TB5 3 TB5 4 313 314 R50 2 De energised fault condition After Modification Wir...

Страница 13: ...necessary permits to work are in place The Engineer responsible for the commissioning of the WMRCP system is available and a procedure is in place which includes the allocation of the various tasks a...

Страница 14: ...rm the other side identifies this switch as Muster Additional double sided inserts may be supplied for Chinese or Japanese applications 5 5 1 To change the inserts 1 Isolate the mains supply to the pa...

Страница 15: ...nut by turning the nut a quarter of a turn Press the frame against the enclosure door using fingers only and check for any slack 22 Repeat step 21 until the frame is firmly seated Note Over tightenin...

Страница 16: ...hinge These are used to secure the door stay enclosure mounting bracket 6 Offer the door stay door mounting bracket up to the studs on the display frame as shown in Figure 9 and fit one M6 washer and...

Страница 17: ...basic wiring continuity is proven 6 3 An Overview of the Commissioning Procedure Commissioning is broken in to 3 sections 1 Pre commissioning wiring check 2 Powering the panel up with no field wiring...

Страница 18: ...between the IS barrier and the end of line resistor will support open circuit fault monitoring only short circuit fault will raise a detector fire It will not support detector MCP discrimination all...

Страница 19: ...tively Charts are provided in the System Log Book for planning recording the actual configuration This configuration is not lost when the panel is powered down 7 Operating the Engineer s functions 7 1...

Страница 20: ...Any current alarms disablements will be re indicated along with any active status indications Delay on etc o Close and lock the panel door o Return the ACCESS keyswitch to the 0 position to disable th...

Страница 21: ...Zones o OFF Configuration mode disabled o ON Enables selected zones to be configured to non latching fire mode via the Engineer s Select feature Not EN54 compliant function SW 1 5 Config I S Zones o...

Страница 22: ...immediately if there is a fire in a machinery space zone but will be delayed for 2 minutes for a fire on any other zone Sounder circuits 3 4 on the control board and any output board sounder circuits...

Страница 23: ...lt Output Fault monitored powered O P J6 J7 J8 Fitted C1627 motherboard to the right of the Fault Routing Output relay Volt Free C O relay O P Removed Fire Protection Output Fault monitored powered O...

Страница 24: ...d type of output expansion boards are set on DIL switches on the C1630 For the standard T1216W C panel the C1630 will be configured at works prior to dispatch If further output expansion modules are t...

Страница 25: ...Engine Top Zone 2 O P 2 Main Engine Top Zone 3 O P 3 Generator Sets 1 2 3 Zone 4 O P 4 Generator Sets 1 2 3 Zone 5 O P 5 Generator Engine 4 Zone 6 O P 6 Generator Engine 4 Zone 7 O P 7 Purifier Space...

Страница 26: ...ate a fire condition on a zone to operate the output Check that the fire signal operates the interface relay adjacent to the fire protection equipment 4 Open circuit the field wiring and confirm that...

Страница 27: ...he primary supply Note The battery requires a period in excess of 24hrs to achieve a fully charged condition 7 9 12 T1216W C WMRCP Interface This work must be carried out in conjunction with the Engin...

Страница 28: ...enclosure Check that all Earth leads are correctly firmly connected Check that End Of Line resistors in unused circuits are positioned in a safe manner and are unlikely to create short circuit faults...

Страница 29: ...led Yellow Flashes for a fault on the Fire Output Steady when Fire Output is disabled Fault Output Fault Disabled Yellow Flashes for a fault on the Fault Output Steady when Fault Output is disabled 1...

Страница 30: ...When controls are unlocked Reset Resets any standing fire and or fault conditions When controls are unlocked and panel has fire and or fault conditions Silence Buzzer Press to stop the buzzer soundin...

Страница 31: ...SW1 1 to SW1 10 J18 Earth Fault Monitoring Link Connector for C1632 Zone Expansion Board Alarm Circuits Marked with Active Polarity Aux DC Supply 24V 0V Remote Inputs Silence Alarms Evacuate Reset Aux...

Страница 32: ...osition Muster mode Link removed Evacuate Muster modes disabled Figure 11 Rear Right Hand Side of Display PCB SW1Config switch Top to bottom AD0 AD1 ZN0 ZN1 ZONAL VDR OFF Comms Fault LED J2 Comms In o...

Страница 33: ...ity and type of O P modules connected From top to bottom F P0 Fire Protection F P1 Fire Protection S C0 Sounder Controller S C1 Sounder controller LED0 LED driver LED1 LED driver VDR Voyage Data Recor...

Страница 34: ...DIMENSIONS SHOWN WITH BOTTOM ENTRY CABLE GLAND PLATE IF TOP ENTRY REQUIRED REVERSE DIMENSIONS ENCLOSURE ENCLOSED SPACES SUBJECT TO TEMPERATURE HUMIDITY VIBRATION TECHNICAL DATA DIMENSIONS 400mm WIDE x...

Страница 35: ...PPLY INCOMING PRIMARY AC MAINS SUPPLY OUTGOING AC MAINS SUPPLY TO PANEL INCOMING 24Vdc SUPPLY FROM PANEL 24V 0V AUX D C 24V 0V 4 SIL EVAC RST Panel Motherboard Auxiliary 24Vdc Terminals Mains Terminal...

Страница 36: ...erminals C1634 Relay O P module address 2 zonal outputs 9 14 to Watermist panel C1634 Relay O P module address 1 zonal outputs 1 8 to Watermist panel Gland Plate Earth Wiring Screen Earth Terminal Blo...

Страница 37: ...ect return to Aux 24V Zones 2 8 10k end of line resistor Zones 9 16 10k end of line resistor Field wiring terminals on panel PCB Detector base Manual Call Point Sounder 3k9 end of line resistor Aux 24...

Страница 38: ...80R 1W activation resistor Z15 Z16 Z15 Z16 Wire Links Zones 15 16 from T1216W C panel 9 10 7 8 5 6 TB2 RL FLT I F Fault Signal from from T1216W C panel Watermist Control Panel Modification Note 1 Mods...

Страница 39: ...with a suppression diode as shown in Figure 20 4 Remote Inputs Silence Alarms Evacuate Reset Class Change Connections Connect to 0V AUX DC via the Normally Open contact inactive condition 5 Remote Ou...

Отзывы:

Похожие инструкции для TYCO T1216W-C