EQUIPMENT:
T1216W-C
PUBLICATION:
MARINEW-P-I
ISSUE No. & DATE:
1
11/12
© 2012 Thorn Security Ltd
PAGE 21 of 39
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
flash.
o
The System Fault and Select LEDs on the
display will flash.
o
The fault relay will operate.
o
The panel buzzer will sound.
o
The Cursor indication will clear.
o
Configuration will be inhibited.
To clear the invalid condition check the zone
and output config switches [1/4, 1/5, 1/6, 1/7,
1/8] on the motherboard and ensure that only
one is selected to ON.
Invalid condition: Selecting any config mode
switch [1/4, 1/5, 1/6, 1/7, 1/8] to the On position
whilst the panel is in the fire condition.
o
The Config LED on the motherboard will
flash.
o
The System Fault and Select LEDs on the
display will flash.
o
The panel buzzer will sound.
o
The Cursor indication will clear.
o
Configuration will be inhibited.
To clear the invalid condition, select the config
switch to OFF. Reset the fire alarm condition
before attempting the configuration process
again.
7.6
List of configuration DIL switches
and their functions:
SW 1/1 - Inhibit F/P on NLZ
:
o
OFF
: Fire Protection relay operates for a fire
condition on any zone.
o
ON
: Fire Protection relay does not operate
for a fire condition on any zone configured to
non-latched mode.
[Not EN54 compliant function].
S/W 1/2 - Delay Alarm Sil & Rst:
o
OFF
: Silence and reset available at all times.
o
ON
: Prevents alarms being silenced or reset
for a period of 3 minutes after a fire alarm
condition occurs.
[Not EN54 compliant function].
SW 1/3
– Delay ON Auto:
o
OFF: Configuration mode disabled.
o
ON: Enables Coincidence on paired zones
for Water-Mist Panel use.
SW 1/4 - Config Non-Latch Zones:
o
OFF
: Configuration mode disabled.
o
ON
: Enables selected zones to be configured
to non-
latching fire mode via the Engineer’s
Select feature.
[Not EN54 compliant function].
SW 1/5 - Config I/S Zones:
o
OFF
: Configuration mode disabled.
o
ON
: Enables selected zones to be configured
to Intrinsically Safe alarm thresholds via the
Engineer’s Select feature. [For use with
MTL5061/MTL5561 I.S. galvanic barriers].
SW 1/6 - Config M/S Zones:
o
OFF
: Configuration mode disabled.
o
ON
: Enables zones to be configured as
Machinery Space zones via the Engineer’s
Select feature.
SW 1/7
– Not Used
SW 1/8 - Configure Delay O/Ps:
o
OFF
: Configuration mode disabled.
o
ON
: Enables the selection of outputs, via the
Engineer’s Select feature, to which the panel
delay will apply.
NOTE: This feature does not comply with the
requirements of EN54-2.
SW 1/9
– Not Used
SW 1/10 - Alarms on Evac Only:
o
OFF
: Sounders operate on any fire condition
including manual fire alarm/muster.
o
ON
: Selects sounders to operate only when
the panel is in the manual fire alarm/muster
condition.
[Non-EN54 compliant function].
SW 2/1 - Silence Before Reset:
Select type of reset mode.
o
OFF
: Reset available when panel is in the
[un-silenced] fire or fault condition.
o
ON
: Fire Condition Reset available only
when panel is in Alarm Silenced condition.
Fault reset available when panel is in the
fault condition. (Not permitted under EN54-
2).
SW 2/2 - Pulse Alarms:
Select type of sounder Operation.
o
OFF: Sounders will be continuous.
o
ON: Sounders will pulse.
NOTE: The Muster Alarm signal will override
any configuration settings.
SW 2/3 - Restart Delay:
Select type of Delay response in
Crew Mode
only
.
o
OFF: If Sounders are silenced before the end
of the 2-minute delay, a new fire condition
will immediately operate all delayed outputs
without delay.
o
ON: If Sounders are silenced before the end
of the 2-minute delay, a new fire condition
will restart the delay timer.
SW 2/4 to 2/5
– Not Used