EQUIPMENT:
T1216W-C
PUBLICATION:
MARINEW-P-I
ISSUE No. & DATE:
1
11/12
© 2012 Thorn Security Ltd
PAGE 25 of 39
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
Table 7
– Setting C1634 to Fire Protection Mode
SW1
VDR
Function
Standard T1216W
configuration
Off
Fire protection
output module
On
Not compatible
with T1216W-C
7.9
Commissioning Procedure
After completion of the pre-commissioning wiring
check, panel power-up and configuration steps,
commission the circuits in line with the following
guide.
7.9.1 Alarm Circuits
1.
Remove the resistor from the first alarm circuit
terminal and connect the first alarm circuit
wiring to the terminals, observing correct
polarity. Check that any alarm fault indications
clear after a few seconds.
2.
Use the Alarm Test facility [see T1200-C User
Manual] or press Manual fire alarm to operate
the sounders. Check that all sounders
connected to the alarm circuit operate.
3.
Clear the Alarms Test
condition or if “Manual
fire alarm
” was used, press silence alarms to
stop the sounders operating.
4.
Repeat steps 1 to 3 for the second and any
subsequent alarm circuits.
Table 8
– Zone and Zonal Output Allocation
T1216W-C
Detection
Zones
T1216W Zonal Output
Watermist Fire Protection Zone
C1634 address 1
[Left hand board]
C1634 address 2
[Right hand board]
Zone 1
O/P 1
Main Engine Top
Zone 2
O/P 2
Main Engine Top
Zone 3
O/P 3
Generator Sets 1,2,3
Zone 4
O/P 4
Generator Sets 1,2,3
Zone 5
O/P 5
Generator Engine 4
Zone 6
O/P 6
Generator Engine 4
Zone 7
O/P 7
Purifier Space
Zone 8
O/P 8
Purifier Space
Zone 9
O/P 1
Boiler Firing Units
Zone 10
O/P 2
Boiler Firing Units
Zone 11
O/P 3
Incinerator Firing units
Zone 12
O/P 4
Incinerator Firing units
Zone 13
O/P 5
Zone 7
Zone 14
O/P 6
Zone 7
7.9.2 Zones
Work logically and systematically through each
zone.
1. Zone fault conditions:
o
Remove the resistor from the zone 1 terminals
and connect the cables of the zone 1 circuit to
the panel terminals, observing the correct
polarity. Check that any zone 1 fault
indications clear after a few seconds.
o
Check the fault monitoring of the cable is
correct by applying an open circuit then a short
circuit at the end-of-line device (in the field).
Check that the fault condition is indicated on
zone 1 on the fire panel.
o
Remove the circuit faults, restoring the circuit
to the healthy condition and confirm that the
fault indication clears.
2. Zone fire conditions:
o
On each zone in turn, start with the device
nearest the panel and operate each manual
call point and detection device on the zone.
o
After operation of each device confirm:
The fire indication is provided on the panel
on the correct zone.
The fire alarm devices operate correctly in
line with the panel configuration.
The Fire Output [fire output signal] and Fire
protection outputs operate correctly in line
with the panel configuration.
o
Press the Silence Alarms and the Reset