background image

P a g e

 | 

 

18-5-10 

TCH-150 & 460 

LOCATION: 
 

The cabinet can operate at temperatures up to 80ºC with high humidity (see control envelope page 
8). Therefore it should placed in a well ventilated area away from sensitive equipment that may be 
affected by the local heat and humidity. 
Since ambient air is usually drawn through the cabinet, the operating range of the cabinet will be 
greatly affected by the ambient temperature and humidity. It is best located in a stable air 
conditioned environment. 
The cabinet is provided with castor wheels so that it can be easily moved around.  
Allow sufficient space around the cabinet to provide adequate ventilation. We recommend a space 
of 30cm on both sides and 10cm at the rear. In particular, make sure that the ventilation slots 
around the top of the cabinet are not blocked off or restricted in any way. 
Ensure that there is sufficient room in front of the cabinet to allow the door to open. 
 
 

SERVICES: 
ELECTRICAL: 

Confirm that the power supply is suitable for this equipment. 
Refer to the equipment rating plate for details: 
TCH-150: 

10 amps 

240 volts 

50Hz. 

TCH-460: 

15 amps 

240 volts 

50Hz 

Note: Only the TCH-150 model plugs into a standard 10 amp power point (otherwise known as a 
general purpose outlet or gpo). The TCH-460 requires a 15 amp power point. You will notice that 
the plug has a large earth pin and will not plug into a standard 10 amp power point. 
 

  

WARNING: 

Ensure that the electrical outlet is earthed, is the correct voltage, and 

capable of carrying the stated current. 

 

 

Model TCH-150 is suitable for bench top or floor use, whereas the TCH-460 is 
suitable for 

floor standing only. 

These cabinets are not suitable for stacking.  

 
WATER: 

A water supply is required for the humidity trough inside the cabinet. The connection for the water 
supply is found on the right hand side of the cabinet. 
Since the water level is automatically regulated, the water supply can come from either town water 
or from a gravity fed water reservoir. 
If the water supply is town water, we recommend that it should be filtered to prevent the build up of 
mineral salts frequently found in town water. The water in the humidity trough is constantly being 
heated, and therefore evaporation will leave mineral deposits behind. 
An alternative method, 

and one that we recommend

, is to use a water supply from a gravity fed 

tank. Thermoline supply an optional 25 litre water tank complete with hoses and connection fittings. 
This tank should be elevated by at least 1 metre and filled with water, the 25 litres would last at 
least 2 to 3 days even under the worst operating conditions. 
The gravity fed water supply has a number of advantages over a town water supply: 

  Firstly, the water in the tank can be “treated water”: such as distilled water or deionised 

water. The deionised water does have the potential under certain conditions to corrode 
stainless steel (refer to “caring for stainless steel” on page 18). Using distilled water will not 

Содержание TCH-150

Страница 1: ...t Pty Ltd T A Thermoline Scientific ABN 80 000 859 129 10 12 Ross Place Wetherill Park N S W 2164 Australia P O Box 6862 Wetherill Park Delivery Centre N S W 1851 Australia Phone 02 9604 3911 Internat...

Страница 2: ...pment be aware of the ALERT BOXES that appear throughout these operating instructions INDEX IMPORTANT INFORMATION Page 1 INDEX Page 1 2 PRODUCT WARRANTY Page 3 INTRODUCTION Page 4 THE MANUAL Page 4 UN...

Страница 3: ...HANGING THE SET VALUE Pages 13 ADJUSTING THE VENTS Pages 14 15 SENSOR CORRECTION FOR CALIBRATION PURPOSES Page 16 MEASURING EQUIPMENT Page 16 ADJUSTING THE CALIBRATION OFFSET Page 17 MAINTENANCE CLEAN...

Страница 4: ...stralia This warranty does not apply to refrigeration compressor s that are not protected by Thermoline Scientific factory installed VFP Voltage Fluctuation Protection unit 4 Limitation of Liability E...

Страница 5: ...ese items could be included as part of the packing list if ordered Water supply bottle 25 litre bottle complete with hose connection fittings 1 x 4 pin plug for retransmission connection Circular char...

Страница 6: ...d 10 amp power point WARNING Ensure that the electrical outlet is earthed is the correct voltage and capable of carrying the stated current Model TCH 150 is suitable for bench top or floor use whereas...

Страница 7: ...HE CABINET DURING SERVICE ASSEMBLY INSTALLATION ASSEMBLY SHELVES Place the shelves at the required level The shelf runners are fixed at 100mm centres PERSPEX HOLDER This holder is provided so that the...

Страница 8: ...er to gain access to the drain valve see photo 3 below The drain valve is shown in the closed position Note Prior to leaving the factory the water pressure regulator has been left fully open as it sho...

Страница 9: ...of products within the range shown below in the control envelope NOTE Temperature and humidity inside the cabinet can only be controlled at temperatures above the ambient WARNING Do not use flammable...

Страница 10: ...justable vents on top of the cabinet an air inlet and an air exhaust The operator can adjust these vents to increase or decrease the amount of ambient air that is mixed with the air inside the cabinet...

Страница 11: ...P a g e 10 18 5 10 TCH 150 460 Figure 1 Section side view of cabinet showing air flow EXPLANATION OF CONTROLS Figure 2 Control Panel Layout...

Страница 12: ...and quick recovery times Maximum recommended temperature is 80 C Humidity control This is a Eurotherm 3216 microprocessor based instrument with digital indication of set humidity and operating humidi...

Страница 13: ...off the fan and heating elements when the door is open 4 Position the mains switch to the ON position reset and immediately both controllers will go through a short initiation period the two displays...

Страница 14: ...e alarm will switch off all forms of heating if the actual temperature exceeds the set temperature by 2 0 C This will be indicated by a red flashing indicator and a scrolling message of Over Temperatu...

Страница 15: ...gher humidity both vents will be closed for lower humidity the vents will be more open The ambient temperature and humidity will have a large bearing on the temperature and humidity attainable inside...

Страница 16: ...P a g e 15 18 5 10 TCH 150 460...

Страница 17: ...the operator access level so that it can be used to correct the displayed operating value If adjustments need to be made use the calibration procedure below MEASURING EQUIPMENT Ensure that the equipme...

Страница 18: ...e should be carefully considered If in doubt return the value to zero and recalculate the offset value Press the scroll key again to return to the original screen The offset value will have changed to...

Страница 19: ...rocess There are several chemicals which will attack the surface of stainless steel plus the lack of oxygen at the surface will cause rusting corrosion and pitting Note Deionised water is particularly...

Страница 20: ...lly there is still enough pressure reduction through the valve even when fully open to reduce bounce When mains water is connected to the cabinet As described previously when town water is connected a...

Страница 21: ...65 Fan motor Betts 50D503 86A 5 70 Centrifugal blower wheel 5 66 Cooling fan blade 4 30 MRA Bit 02 pressure regulator 4 32 Water solenoid valve L171B13 ZZ23A 1 8 TECHNICAL ASSISTANCE If you require ad...

Страница 22: ...the cabinet for connection to an outside monitoring system which is able to accept the 4 20mA signals representing 0 0 to 100 0 C and 0 to 100 RH Maximum load to be applied to the analogue output is 5...

Отзывы:

Похожие инструкции для TCH-150