Controller operating manual
15.11.2020 – Version 1.1
TCS.2 series –
thermofin
®
control system 2
nd
generation
Page: 36/162
Operating manual - translation into English © thermofin GmbH
Low load regulation control
See also chapter 4.6.5 “Low load settings” and chapter 5.7.5 “
Signal type:
Binary
0 = OFF, 1 = ON
Options:
* Factory setting
Off *
Function deactivated.
Internal
The switching thresholds for the individual
levels are automatically calculated by the
program based on the number of steps and the
limit value. These can be set under: Device
settings
Additional functions
“Low load”
(chap. 0) or in the Main menu
Additional
functions
“Load load” (chap. 5.7.5)
Via terminal
A maximum of 2-level control is possible. The
first (base load level) remains switched on, the
second is activated with the following DI.
+ 24 V DC at terminal X7.6 (DI-6) “External low
load level 1”
Device settings
Inputs / Outputs
“Digital
IN basic unit”
(chap. 4.3.1)
See also chapter 1.4 (Circuit diagram
TCS.2)
Via bus
The type of communication bus is set in the
Device settings
BMS bus system
[see also
chapter “4.5 „
The following parameters apply to direct
communication via MODBUS:
Writing:
Register 2
SL control level 1, bit 0 (Bool), (register value
1)
Via bus
The type of communication bus is set in the
Device settings
BMS bus system
[see also
chapter “4.5 „
”].
The following parameters apply to direct
communication via MODBUS:
Writing:
Register 1, bit 15 (Bool), (register value 32767)
Reading:
Register 143, bit 8 (Bool), (register value 256)
* Factory setting