Controller operating manual
15.11.2020 – Version 1.1
TCS.2 series –
thermofin
®
control system 2
nd
generation
Page: 104/162
Operating manual - translation into English © thermofin GmbH
Picture 78
Editable values
If the control has been selected, the “Spray pump” field in the “Additional functions” menu appears
blue and can be activated (Picture 76). The editing level of the “Spray pump” opens.
Startup delay in seconds
If the current speed setpoint (
⑦
) exceeds the “Pump ON, fan speed %” value (
③
), the time
set here starts. When it has expired, the spray pump switches ON.
Editable from … to:
0 … 600 s
Factory setting:
0 s
Run-on time in seconds
If the current speed setpoint (
⑦
) falls below the “Pump OFF, fan speed %” value (
③
), the time
set here starts. When it has expired, the spray pump switches OFF.
Editable from … to:
0 … 1800 s
Factory setting:
120 s
Pump ON, fan speed in %
Display speed
output circuit 1
①
②
③
①
②
③
④
⑤
⑥