VOLTMAX ELECTRIC BOILER Installation and Operation Manual
(
Revised March 2019)
, Page
41.
Program
name
The controller’s program name and version.
---
---
HEATING MODE W1 SETTINGS
(Variables beginning with AV and BV are read variables, while variables beginning with "W" are editable)
Display
BACnet variable
Instance
Tag
Description
Parameters
Default
Head
demand W1
WP_HeatingW1
43
20971563
Allows to select W1 heating demand source.
BACnet or Local
Local
Bacnet
Local
Operating
Mode
WP_HeatingMod
eW1
11
8388619
Selects the power limitation mode between Stop,
Modulation T. Ext, DCC 0-10VDC and Fixed.
0 = Stop
1 = Outdoor Reset
2 = DCC 0-10VDC
3 = Fixed
Fixed
FIXED MODE
Configure the fixed set-point temperature
Display
BACnet Variable
Instance
Tag
Description
Selection
Default
W1 Set
point
WP_FixedSTPT
W1
22
8388630
Selects the fixed set-point temperature when there
is demand on W1.
10 to 93
0
C
50 to 200
0
F
140
0
F