VOLTMAX ELECTRIC BOILER Installation and Operation Manual
(
Revised March 2019)
, Page
52.
BOOST MENU SETTINGS
(Variables beginning with AV and BV are read variables, while variables beginning with "W" are editable)
Display
BACnet Variable
Instance
Tag
Description
Settings
Default
Mode
BOOST
WP_ActivateMod
eBoost
37
20971557
This option enables the BOOST functionality.
0 = Off
1 = On
Off
WARM WEATHER SHUTDOWN MENU SETTINGS
(Variables beginning with AV and BV are read variables, while variables beginning with "W" are editable)
Display
BACnet Variable
Instance
Tag
Description
Settings
Default
Warm
Weather
Shutdown
WP_ActivateWar
mWeatherSD
26
20971546
Shuts down the boiler when the outside
temperature reaches a specific temperature. This
temperature can be set in the
Warm Weather
Shutdown Temperature box.
OFF / ON
0 = Off ; 1 = On
OFF
T. Ext
Shutdown
WWSD
WP_WarmWeath
erSDTemp
51
8388659
Sets the outside temperature that activates the
Warm Weather Shutdown
, if it shuts down the
boiler.
0 to 55 °C
0 to 99 °F
68 °F
Current Ext.
T.
AV_OutdoorT
2
8388610
Shows the outside temperature in real time.
-46 to 107 °C
-50 to 250 °F
---