VOLTMAX ELECTRIC BOILER Installation and Operation Manual
(
Revised March 2019)
, Page
51.
CONFIG. ALARM MENU SETTINGS
(Variables beginning with AV and BV are read variables, while variables beginning with "W" are editable)
Display
BACnet Variable
Instance
Tag
Description
Settings
Default
Occupation
mode
WP_Schedule_O
n
46
20971566
Allows to select Bi-energy activation contact
source. BACnet or Local
Local
BACnet
Local
Status:
HL/LWCO
alarm
BV_StatusExtAlar
m
28
20971548
Displays the external alarm status. The external
alarm contact is activated only if a high limit or low
water level alarm occurs.
0 = Off
1 = On
---
Silence
Alarm
WP_SilenceAlar
m
27
20971547
Temporarily suspends the alarm.
0 = Off
1 = On
Off
Reset
Lockdown
WP_ResetLockD
own
29
20971549
Cancels the Lockdown mode without resetting the
unit.
Resetting the unit is required when it is in
LOCK-
OUT mode
, following high external temperature or
low water level alarms over a short period.
0 = Off
1 = On
Off
Internal
buzzer
WP_ActivateInter
nalBuzzer
30
20971550
Activates the controller’s internal buzzer.
0 = Off
1 = On
On
OCCUPATION MENU SETTINGS
(Variables beginning with AV and BV are read variables, while variables beginning with "W" are editable)
Display
BACnet Variable
Instance
Tag
Description
Settings
Default
Occupation
Mode
WP_ActivateOcc
upationMode
33
20971553
Activates the Occupation function.
0 = Off
1 = On
---
Source OCC
WP_SourceOccu
pation
34
20971554
Selects the source used to determine the building’s
occupation schedule.
0 = Schedule
1 = Contact OCC
Lowering T.
WP_LoweringTIn
noccupation
52
8388660
Lowers the set-point temperature.
---
Off
Occupation
Status
BV_StatusOccup
ation
35
20971555
Displays the Occupation mode status.
Off: Day mode; the set-point temperature is not
lowered
On: Night mode; the set-point temperature is
lowered according to the configuration
0 = Off
1 = On
On
Force Day
Mode
WP_ForceOccup
ationDay
36
20971556
Forces the Day mode. The set-point temperature
will not be lowered.
0 = Off ; 1 = On
Off