Installation manual

Gas condensing boiler

Paramount four

30 – 115 kW

Summary of Contents for Paramount four

Page 1: ...United Kingdom en Installation manual Gas condensing boiler Paramount four 30 115 kW ...

Page 2: ...using the product and keep it in a safe place for later reference In order to ensure continued safe and efficient operation we recommend that the product is serviced regularly Our service and customer service organisation can assist with this We hope you enjoy years of problem free operation with the product ...

Page 3: ...ons and connections 20 3 5 Wiring diagram 22 4 Description of the product 25 4 1 Main components 25 4 1 1 Room device RGT 26 4 2 Control panel description 27 4 2 1 Operating elements 27 4 2 2 Displays 27 4 3 Standard delivery 27 4 4 Accessories and options 27 4 4 1 Installation of extension module 27 5 Before installation 28 5 1 Regulations governing installation 28 5 2 Installation requirements 2...

Page 4: ...om natural gas to LPG and vice versa 46 7 4 5 Gas valve 47 7 4 6 Manual adjustment of burner output controller stop function 48 7 4 7 Guidance values for gas flow rate injector pressure and CO2 content 48 7 4 8 Guidance values for the gas flow rate 48 7 4 9 Guidance values for the gas flow rate 49 7 4 10 Guidance values for injector pressure 49 7 4 11 Guidance values for injector pressure 49 8 Ope...

Page 5: ...ct 129 10 1 4 Approved detergents 129 10 1 5 Unhooking the control panel 129 10 1 6 At the end of the maintenance work 129 10 2 Maintenance messages 130 10 2 1 Maintenance code table 130 10 2 2 Operating phases of the Control Centre LMS 130 10 3 Standard inspection and maintenance operations 130 10 3 1 Clean siphon 130 10 3 2 Check electrodes 131 10 4 Specific maintenance instructions 131 10 4 1 R...

Page 6: ...by a qualified installer Danger of electric shock Danger to life due to improper work All electrical work in connection with the installation may only be carried out by a trained electrician Danger Risk of poisoning Never use water from the heating system as drinking water It is contaminated by deposits Caution Danger of freezing If there is a danger of freezing do not shut down the heating system...

Page 7: ... will become void if these instructions are not observed Caution Replacement of damaged parts may only be per formed by a qualified installer Caution Connections sealed with thread sealant must never be opened or modified by a non specialist The seals serve as proof that essential connections for safe trouble free operation have not been tampered with The guarantee becomes void if the seals are da...

Page 8: ...below ground level 1 4 Liabilities 1 4 1 Manufacturer s liability Our products are manufactured in compliance with the re quirements of the various Directives applicable They are therefore delivered with the marking and any documents necessary In the interests of the quality of our products we strive constantly to improve them We therefore reserve the right to modify the specifications given in th...

Page 9: ... compliance with prevailing legisla tion and standards Carry out initial commissioning and any checks necessary Explain the installation to the user If maintenance is necessary warn the user of the obliga tion to check the appliance and keep it in good working or der Give all the instruction manuals to the user 1 4 4 User s liability To guarantee optimum operation of the system you must abide by t...

Page 10: ...Regulations standards CE Notes for installation location Application example Standard application Commissioning operation and programming Maintenance Installer User manual Commissioning Operation User settings programming Fault table Cleaning maintenance Energy saving tips Customer Asset ledger Commissioning report Check list for commissioning Maintenance Installer Abridged instructions Operation ...

Page 11: ...hock Risk of electric shock Warning Risk of dangerous situations that may result in minor personal in jury Caution Risk of material damage Note Please note important information See Reference to other manuals or pages in this manual 2 About this manual 7658013 02 15092016 Paramount four 30 115 kW 11 ...

Page 12: ...l connections Fuel Ordinance State Ordinances Regulations of the local Electricity Board Obligation to register possibly Group Exemption Regulation ATV Code of practice M251 of the waste water technology association Regulations of the public authorities for the run off of condensate 3 2 Technical data 3 2 1 Technical data Boiler space heaters Tab 2 Technical parameters for boiler space heaters Mod...

Page 13: ... boiler No No No No No Cogeneration space heater No No No No No Combination heater No No No No No Rated heat output Prated kW 49 56 75 93 112 Useful heat output at rated heat out put and high temperature mode 2 P4 kW 48 7 56 4 74 9 92 5 111 7 Useful heat output at 30 of rated heat output and low temperature mode 1 P1 kW 16 3 18 9 25 1 31 0 37 4 Seasonal space heating energy effi ciency ƞs 93 93 Us...

Page 14: ...2 9 7 39 6 10 8 52 1 15 1 60 4 22 6 80 2 21 4 98 6 26 7 119 3 Standard operating efficiency 75 60 C 106 pH value condensate 4 5 4 5 4 5 4 5 4 5 4 5 4 5 Volume condensate 40 30 C l h 0 83 3 00 1 19 2 84 1 60 4 68 1 78 4 71 2 53 6 46 2 75 8 42 3 85 9 61 NOX standard emission factor mg k Wh 17 20 20 20 20 25 30 CO standard emission factor mg k Wh 5 10 10 10 10 20 20 Data for design of the chimney to ...

Page 15: ...2 20 Natural gas LL HUB 8 13 kWh m m h 0 69 3 7 1 11 4 7 1 23 6 20 1 72 7 10 2 58 9 50 2 46 11 70 3 08 14 10 Connection pressure for propane mbar min 25 max 45 Propane HU 12 87 kWh kg kg h 0 44 2 33 0 70 2 95 0 93 3 89 1 09 4 51 1 63 5 98 2 33 7 38 2 72 8 94 Propane HU 24 64 kWh m m h 0 23 1 22 0 37 1 54 0 49 2 03 0 57 2 35 0 85 3 13 1 22 3 86 1 42 4 67 Electrical power consumption Electrical conn...

Page 16: ...sor KVF drinking water sensor TWF return sensor KRF sensor B4 Temperature C Resistance Ω 0 32555 5 25339 10 19873 15 15699 20 12488 25 10000 30 8059 35 6535 40 5330 45 4372 50 3605 55 2989 60 2490 65 2084 70 1753 75 1481 80 1256 85 1070 90 915 95 786 100 677 3 Technical specifications 16 Paramount four 30 115 kW 7658013 02 15092016 ...

Page 17: ...ax 1 Rfh 100 Dmin 1 2 Dmax 2 10 Pst RA 0000195 Key Dmax 1 Paramount four 30 max Dmax 2 Paramount four 40 max Dmin 1 2 Paramount four 30 min Paramount four 40 min Pst Pumping stage Rfh Total dynamic head Wms Water mass flow Note The select min and max values are controlled via the program numbers for minimum pump speed and maximum pump speed 3 Technical specifications 7658013 02 15092016 Paramount ...

Page 18: ...R Heating return 3 2 HR Heating return heating circuit 2 4 Gas Gas connection 5 SiV Safety valve 6 KA Condensate connection 7 SV Storage tank flow accessory 8 SR Storage tank return accessory Tab 7 Dimensions and connections Model Paramount four 30 40 HV Heating flow G 1 3 Technical specifications 18 Paramount four 30 115 kW 7658013 02 15092016 ...

Page 19: ...ng return heating circuit 2 G 1 Gas Gas connection G 3 4 SiV Safety valve G 3 4 KA Condensate connection Ø 25 mm Gravity lock blocked valve opened Operating position Paramount four Z A Z A 3 Technical specifications 7658013 02 15092016 Paramount four 30 115 kW 19 ...

Page 20: ...ystem page 36 3 4 Dimensions and connections Fig 3 Dimensions and Connections Paramount four 50 115 160 110 RA 0000310 B C 851 883 975 1 2 3 4 1 HV Heating flow 2 HR Heating return 3 Technical specifications 20 Paramount four 30 115 kW 7658013 02 15092016 ...

Page 21: ...G 1 1 2 G 1 1 2 G 1 1 2 G 1 1 2 HR Heating return G 1 1 2 G 1 1 2 G 1 1 2 G 1 1 2 Gas Gas connection G 1 G 1 G 1 G 1 SiV Safety valve G 3 4 G 3 4 G 3 4 G 3 4 KA Condensate connection Ø 25 mm Ø 25 mm Ø 25 mm Ø 25 mm Dimension A mm 447 542 580 580 Dimension B mm 168 168 163 163 Dimension C mm 132 132 152 152 3 Technical specifications 7658013 02 15092016 Paramount four 30 115 kW 21 ...

Page 22: ...3 5 Wiring diagram Fig 4 Wiring diagram Paramount four 30 40 3 Technical specifications 22 Paramount four 30 115 kW 7658013 02 15092016 ...

Page 23: ...Fig 5 Wiring diagram Paramount four 50 60 3 Technical specifications 7658013 02 15092016 Paramount four 30 115 kW 23 ...

Page 24: ...Fig 6 Wiring diagram Paramount four 80 115 For more information see Strain reliefs page 42 3 Technical specifications 24 Paramount four 30 115 kW 7658013 02 15092016 ...

Page 25: ...RA 0000312 15 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 8 3 4 2 9 7 5 6 10 11 12 13 14 16 15 Paramount 50 60 Paramount 80 Paramount 95 115 1 4 2 3 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 Paramount 30 40 15 14 1 2 3 4 5 6 7 8 9 10 11 12 13 23 17 17 17 4 Description of the product 7658013 02 15092016 Paramount four 30 115 kW 25 ...

Page 26: ... valve 1 Accessories 19 Gravity lock 20 Heating circuit pump 21 Connection 2 heating circuit1 22 Control LMS 23 Gas pressure monitor 1 Accessories 4 1 1 Room device RGT Remote setting of all adjustable control functions of the basic appliance is possible via the operating unit when using the room device RGT accesso ry 1 Operating mode key heating mode 2 Operating mode key domestic water mode 3 Scr...

Page 27: ...etting level active Heating system switched off automatic summer winter changeover or automatic heating limit active 4 3 Standard delivery Gas condensing boiler for fitting to the wall packed in a cardboard box Info package with manual Outside temperature sensor Mounting rail Accessories 4 4 Accessories and options A list of the accessories selection available for the Paramount four can be found b...

Page 28: ...pli ance The boiler must not be started up if there is heavy dust de velopment e g during construction work There could be damage to the boiler Where the Paramount four is operated based on room ventilation there must be a sufficiently large opening for combustion air available in the in stallation room The operator must be informed that this opening must never be closed or blocked and that the co...

Page 29: ...ting water has to be checked within the scope of the recommended maintenance of the boiler and the corresponding amount of additive has to be added if necessary 5 2 4 Further information on the heating water The water must not contain any foreign matter such as sweat beads rust particles scale or sludge During commissioning flush the system until only clean water runs out When flushing the system ...

Page 30: ...gram water hardness Paramount four 50 115 RA 0000313 Anlagenvolumen 0 200 400 600 800 1000 1200 1400 1600 1800 2000 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 Vmax l dH 1 5 2 5 mmol l If the volume is below the curve no need for water treatment 2 1 Tab 10 Key to diagram water hardness Number 1 2 Boiler model Paramount four 50 60 Paramount four 80 115 Description The boiler type the water hardne...

Page 31: ...proved Complete desalination cartridge SureFill from Sentinel www senti nel solutions net Partial softening It must be ensured with an automatic blending device that the min hard ness is not less than 6 dH See The specifications of the manufacturer must be followed Caution If non approved products are used the guarantee becomes void Antifreeze agent Note The use of antifreeze agents with Potterton...

Page 32: ...ness tips 1 If partial softening to 6 dH is insufficient according to the project spe cific water hardness diagram use either an additive or use only fully desalinated water with pH stabiliser If a boiler is replaced in an existing system we recommend installing a dirt trap or filter in the system return upstream of the boiler Flush the system thoroughly 2 Depending on the materials used determine...

Page 33: ...he technology especially the regulations of the federal German states such as fire and construction ordinances as well as heating room guidelines must be observed There should be sufficient space in front of the equipment to carry out inspection and maintenance work Caution Risk of damage to the device Aggressive foreign substances in the combustion supply air can destroy or damage the heat genera...

Page 34: ... fittings have to be tightened so that no water can enter the inside of the housing 1 Protection area 2 2 Protection area 3 When the Paramount four is installed in bath or shower rooms in resi dential buildings the protection areas and minimum clearances must be heeded The Paramount four complies with IP rating IPx4D protection area 2 or 1 and may be installed in protection area 2 refer also to th...

Page 35: ...e does not increase when the safety valve responds It must not be routed to the outside the opening must be clear and observable Any heating water that may possibly escape should be safely drained off Caution The blow off line of the safety valve must be designed in such a way that the pressure does not increase when the safety valve re sponds It must not be routed to the outside the opening must ...

Page 36: ...h the local supply conditions An approved thermally activated disconnector valve must be installed up stream of the Paramount four If old gas pipes still exist in the region the installation of a gas filter is rec ommended Residues in pipes and pipe joints should be removed 6 2 2 Venting the gas line The gas line must be vented before initial commissioning For this open the measuring nozzle for th...

Page 37: ...5 2 C33 1 Concentric Vertical 80 1 25 13 0 110 180 22 0 110 180 13 0 110 180 10 3 0 110 180 10 3 0 C33 1 Concentric Vertical 110 160 3 20 0 120 180 3 20 0 120 180 3 C33 2 Concentric Vertical 80 1 25 15 3 2 110 180 24 3 2 110 180 15 3 2 110 180 18 3 2 110 180 20 3 2 C33 3 Concentric Vertical 80 1 25 7 3 2 110 180 13 2 2 110 180 9 3 2 110 180 110 180 B23 Conventional Flue 3 80 20 3 3 110 25 3 3 110 ...

Page 38: ... use as a combustion air supply duct suitable measures such as shake out of the fireplace should be taken It must be ensured that there is no contamination of the combustion air with foreign matter If an appropriate clean up of the existing flue gas tract is not possible the heat generator can be operated on a concentric flue gas pipe independent of ventilation The concentric flue gas pipe must ru...

Page 39: ...l of the shaft open ing a bore hole Ø 10 mm must be provided on the level fo the opening edge Then the pin of the support rail has to be hammered into the bore hole 3 The flue pipe is lowered from the top into the shaft For this connect a rope to the support leg and insert the pipes section by section from the top To prevent the components sliding apart during assem bly the rope must be kept on te...

Page 40: ...w etc 300 mm D 2 Below gutters soil pipes or drain pipes 25 75 mm E 2 Below eaves 25 200 mm F 2 Below balconies or car port roof 25 200 mm G 2 From a vertical drain pipe or soil pipe 25 150 mm H 2 From an internal or external corner 25 300 mm I Above ground roof or balcony level 300 mm J From a surface or boundary line facing a terminal 600 mm K From a terminal facing a terminal Horizontal flue Fr...

Page 41: ...ines at the outer wall must have at least one clean ing opening in the lower part of the exhaust gas facility For exhaust gas facilities with building heights of 15 00 m in the vertical section a pipe line length of 2 00 m in the horizontal section and a maximum pipeline diameter of 150 mm with a maximum deflection except for deflection di rectly at the boiler and in the shaft one cleaning and ins...

Page 42: ...er route them in parallel to mains cables interference Otherwise shielded cables must be installed Permissible cable lengths for all sensors Cu cable up to 20m 0 8 mm2 Cu cable up to 80m 1 mm2 Cu cable up to 120m 1 5 mm2 Cable types e g LIYY or LiYCY 2 x 0 8 6 4 3 Strain reliefs All the cables should be fixed in the strain relief clamp of the control panel and connected according to the connection...

Page 43: ...d the cables 6 4 7 Circulating pumps The permissible current load per pump output is IN max 1A 6 4 8 Appliance fuses Appliance fuse in the control unit ISR Mains fuses T 6 3A H 250V 6 4 9 Connecting sensors components Danger Risk of electric shock Danger to life through incorrect work The wiring diagram must be followed Optional accessories must be fitted and connected according to the instruction...

Page 44: ... gas system checked 9 Gas pipeline checked and vented 10 Static pressure measured at the gas valve inlet mbar 11 Free wheeling of pumps checked 12 Filling the heating plant 13 Water additives used 14 Gas flow pressure measured at full load at the gas valve inlet mbar 15 Gas injector pressure measured at full load at the gas valve outlet mbar 16 CO2 content at low load 17 CO content at low load ppm...

Page 45: ...oad by the manu facturer Gas type G20 natural gas G20 with Wobbe index WoN 15 0 kWh m3 The specific set gas type can be seen on the optional label glued to the burner The factory setting data must be checked against the on site sup ply conditions before installation of the Paramount four 7 4 2 Supply pressure The supply pressure must be between the values given in the technical data table see refe...

Page 46: ... Wocurrent 0 5 above Paramount four 50 CO2 content 8 8 WoN Wocurrent 0 5 The air quantity set in the factory must not be changed For more information see Technical data page 14 Technical data page 0 7 4 4 Changing over from natural gas to LPG and vice versa Danger Danger Danger to life by gas The gas type of the Paramount four may only be changed by an approved heating specialist The Potterton Com...

Page 47: ...r full load 3 Setting for low load remove protective plug in ad vance 5 4 Measuring nozzle for connecting pressure 5 Protective plug 6 Fan pressure x Flow direction Setting of jet pressures Paramount four 30 60 Torx T15 Paramount four 80 Allen key 2 0 mm Paramount four 95 115 Allen key 2 5 mm Note The keys are located in the accessory kit 7 Commissioning 7658013 02 15092016 Paramount four 30 115 k...

Page 48: ...to be met during the controller stop function 7 4 7 Guidance values for gas flow rate injector pressure and CO2 content The values given in are for guidance It is important that the gas quantity is set via the injector pressure in such a way that the CO2 value is within the specified values If the Paramount four is used in areas with fluctuating natural gas compo sition the CO2content must be adju...

Page 49: ...40 Injector diameter for Natural gas E G20 mm 4 90 7 80 LPG propane mm 3 90 5 80 Guide values for injector pressure 1 G20 15 0 2 mbar 8 3 9 3 6 0 7 0 Propane mbar 8 3 9 3 6 0 7 0 CO2 content see reference below 1 At pressure at end of boiler 0 mbar 1013 hPa 15 C 2 Values in brackets Wobbe Index WoNin kWh m3 For more information see Technical data page 14 Technical data page 0 7 4 11 Guidance value...

Page 50: ...ramount four 115 CO2 content see reference below 1 at pressure at end of boiler 0 mbar 1013 hPa 15 C 2 Values in brackets Wobbe index WoN in kWh m3 For more information see Technical data page 14 Technical data page 0 7 Commissioning 50 Paramount four 30 115 kW 7658013 02 15092016 ...

Page 51: ...5 h using the control knob 7 Press OK 8 Carry out minute setting e g 30 minutes with the control knob 9 Press OK 10 Leave the programming level by pressing the operating mode key for heating mode Note The previous menu item is retrieved by pressing the ESC key without applying previously modified values If no settings are car ried out for approximately 8 minutes the basic display is called up with...

Page 52: ...regulating control and safety equipment and measures the combustion values If this work is not carried out correctly there is a risk of considerable damage to persons environment and prop erty Warning Risk of damage The gas condensing boiler may only be installed in rooms with clean combustion air Foreign matter such as pollen must never filter through the inlet apertures to reach the inside of th...

Page 53: ...gram please see the Operation chapter For more information see Changing parameters page 51 8 7 Setting the heating mode The operating mode key for heating mode enables a changeover between the various heating operating modes The selected setting is marked with a bar underneath the operating mode symbol Automatic mode Heating mode according to time program Temperature setpoints or according to time...

Page 54: ...rtable room setpoint How to adjust the comfortable room setpoint is described here 1 Set the comfort setpoint using the control knob The value is taken over automatically 8 10 Setting reduced room setpoint How to set the reduced room setpoint is described here 1 Press OK 2 Select the Central heating menu item 3 Press OK 4 Select the Reduced temp setpoint parameter 5 Press OK 6 Set the reduced setp...

Page 55: ...e design point 19 kPa 1 9 mWS Max speed read off 50 Set parameter 883 50 2 Parameter 882 Pump speed min Heating systems with radiators The minimum pump speed for heating systems with radiators is the result of entering the system resistance again at volume flow zero l h in the diagram see Fig Tab 19 Example Fig System resistance at the design point 19 kPa 1 9 mWS Min speed read off 30 Set paramete...

Page 56: ...er Manual control prog no 7140 5 Press OK 6 Select the parameter On 7 Press OK 8 Leave the programming level by pressing the operating mode key for heating mode 8 13 Chimney sweep function The chimney sweep function is activated or deactivated using the chimney sweep key 1 Press the chimney sweep key The activated special function is displayed by the symbol in the display Note If there is demand f...

Page 57: ...rast of display 25 Eu Operation lock Off On 26 E Off Programming lock Off On 27 E Off Units C bar F PSI 29 Eu C bar Save basic settings 1 No Yes 30 E No Activate basic settings 2 No Yes 31 E No Used as page 0 Room unit 1 Room unit 2 Room unit 3 Operator unit 1 Operator unit 2 Operator unit 3 Service unit 40 C Room unit 1 Assignment device 1 3 Temps mode CH1 Central heating 1 and 2 Central Heating ...

Page 58: ...ssing Operator unit 3 Missing In operation No recept n Change batt 137 C Missing Service unit Missing In operation No recept n Change batt 138 C Missing Delete all devices No Yes 140 C No 1 Parameters only visible if wireless room device exists Time program Heating cir cuit 1 Prog no Heating cir cuit 2 1 Prog no Heating cir cuit 3 Prog no Level Standard value Select Mon Sun Mon Sun Mon Fri Sat Sun...

Page 59: ... Eu day month Operating level Off Reduced 648 658 668 Eu Off 1 Parameters only visible if heating circuit is installed Heating circuit 1 Prog no 2 1 Prog no 3 1 Prog no Level Standard value Comfort setpoint 710 1010 1310 Eu 20 0 C Reduced temp setpoint 712 1012 1312 Eu 18 C Frost protection setpoint 714 1014 1314 Eu 10 0 C Heating curve slope 720 1020 1320 Eu 1 24 Heating curve displacement 721 10...

Page 60: ...r curing day current 856 1156 1456 E Excess heat draw Off Heating mode Always 861 1161 1461 E Heating mode With buffer No Yes 870 1170 1470 E Yes With prim contr system pump No Yes 872 1172 1472 E Yes Pump speed reduction Operating level Characteristic Temp differential nominal 880 1180 1480 E Characteristic Pump speed min 882 1182 1482 C Paramount four 30 35 Paramount four 40 35 Paramount four 50...

Page 61: ...over None Off On 1680 E Off Consumer circuit swimming pool circuit Consumer circuit 1 Prog no Consumer circuit 2 Prog no Swimming pool circuit Prog no Level Standard value Flow temp setp cons request 1859 1909 1959 C 70 C Hot water charging priority No Yes 1874 1924 1974 E Yes Excess heat draw Off On 1875 1925 1975 E On With buffer No Yes 1878 1928 1978 E Yes With prim contr system pump No Yes 188...

Page 62: ...ation lock Heating mode only Heating and HW mode 2305 E Heating mode only Temp differential max 2316 C Temp differential nominal 2317 C 15 C Pump modulation None Demand Boiler setpoint Temp differential nominal Burner output 2320 E Demand Pump speed min 2322 E 10 Pump speed max 2323 E 100 Output nominal 2330 E Paramount four 30 30 kW Paramount four 40 38 kW Paramount four 50 50 kW Paramount four 6...

Page 63: ...ter mode only Heating and HW mode 2450 E Heating mode only Controller delay fan output 1 2452 E Paramount four 30 10 0 kW Paramount four 40 14 0 kW Paramount four 50 20 0 kW Paramount four 60 22 5 kW Pa ramount four 80 34 5 kW Paramount four 95 36 0 kW Para mount four 115 40 0 kW Controller delay duration 2453 E 40 s Switching diff on CHs 2454 E 4 C Switching diff off min CHs 2455 E 5 C Switching ...

Page 64: ...Charging temp min buffer 3815 E C Temp diff on swi pool 3816 E C Temp diff off swi pool 3817 E C Charging temp min swi pool 3818 E C Charging prio storage tank None Hot water storage tank Buffer storage tank 3822 E Hot water storage tank Charging time relative prio 3825 E min Waiting time relative prio 3826 E 5 min Waiting time parallel op 3827 E min Delay secondary pump 3828 E 60 s Collector star...

Page 65: ...gration No Yes 4783 E Yes Temp diff on return div 4790 E 8 C Temp diff off return div 4791 E 4 C Compar temp return div With B4 With B41 With B42 4795 E With B4 Optg action return diversion Temp decrease Temp increase 4796 E Temp increase Full charging Off Heating mode Always 4810 E Off Full charging temp min 4811 E 8 C Full charging sensor With B4 With B42 B41 4813 E With B42 B41 Domestic water s...

Page 66: ... 5130 E Always Interm circ boost recharging 5139 E 5 C Intermediate circuit boost 5140 E 2 C Excess interm circ temp max 5141 E 2 C Flow setp compensation delay 5142 E 30 s Flow setp compensation Xp 5143 E 60 C Flow setp compensation Tn 5144 E 30 s Flow setp compensation Tv 5145 E 30 s Full charging with B36 No Yes 5146 E No Min start temp diff Q33 5148 E 3 C Excess interm circ temp del 5151 E 30 ...

Page 67: ... 5891 C None Relay output QX3 See Parameters see Relay output QX1 prog no 5890 5892 C Hot water ctrl elem Q3 Sensor input BX1 None Hot water sensor B31 Collector sensor B6 HW circulation sensor B39 Buffer sensor B4 Buffer sensor B41 Common flow sensor B10 Solid fuel boiler sensor B22 HW charging sensor B36 Buffer sensor B42 Common return sensor B73 Cascade return sensor B70 Swimming pool sensor B1...

Page 68: ...er CH1 Optg mode changeover CH2 Optg mode changeover CH3 Heat generation lock Error alarm message Consumer request VK1 Consumer request VK2 Release swimpool source htg Excess heat discharge Release swi pool solar Operating level HW Operating level CH1 Operating level CH2 Operating level CH3 Room thermostat CH1 Room thermostat CH2 Room thermostat CH3 Hot water thermostat Pulse count Checkb sign flu...

Page 69: ...CHs in system 6625 E All CHs in system Note OT limit ext source No Yes 6632 E No Clock mode Autonomously Slave without remote setting Slave with remote setting Master 6640 C Slave with remote setting Outside temp source 6650 E Fault Prog no Level Standard value Message 6700 Eu SW diagnostic code 6705 Eu Burn ctrl phase lockout pos 6706 Eu Reset alarm relay No Yes 6710 C No Flow temp 1 alarm 6740 E...

Page 70: ... Off On 7140 Eu Off Controller stop function Off On 7143 E Off Controller stop setpoint 7145 E Compulsory heat draw off DHW Off On 7165 E Off Telephone customer service 7170 C PStick storage pos 7250 E 0 PStick Reg data set 7251 E PStick command No operation Reading from stick Writing on stick 7252 E No operation PStick progress 7253 E 0 PStick status No stick Stick ready Writing on stick Reading ...

Page 71: ...rog no 7307 7308 C None Function input H2 module 1 None Optg mode change CHs HW Optg mode changeover HW Optg mode changeover CHs Optg mode changeover CH1 Optg mode changeover CH2 Optg mode changeover CH3 Heat generation lock Error alarm message Consumer request VK1 Consumer request VK2 Release swimpool source htg Excess heat discharge Release swi pool solar Operating level HW Operating level CH1 O...

Page 72: ... Cons circuit pump VK1 Q15 Boiler pump Q1 Alarm output K10 heating pump CH3 Q20 Cons circuit pump VK2 Q18 System pump Q14 Heat gen shutoff valve Y4 Solid fuel boiler pump Q10 Time setting 5 K13 Buffer return valve Y15 Solar pump ext exch K9 Solar ctrl elem buffer K8 Solar ctrl elem swi pool K18 Swimming pool pump Q19 Cascade pump Q25 St tank transfer pump Q11 Hot water mixing pump Q35 HW interm ci...

Page 73: ... prog no 7348 7423 E None Signal output UX21 module 2 10 V PWM 7425 E PWM Funct output UX22 module 2 See Parameters see Funct output UX21 module 1 prog no 7348 7430 E None Signal output UX22 module 2 10 V PWM 7432 E PWM Input output test Prog no Level Standard value Relay test 7700 C No test Output test P1 7713 C PWM signal P1 7714 C Outside temp B9 7730 C Hot water temp B3 B38 7750 C Boiler temp ...

Page 74: ...ntact state H2 module 2 Open Closed 7849 C Frequency H4 7862 C Contact state H5 Open Closed 7865 C Contact state H6 Open Closed 7872 C Input EX21 module 1 7950 C Input EX21 module 2 7951 C Status Prog no Level Standard value State central heating CH1 8000 C State central heating CH2 8001 C State central heating CH3 8002 C State hot water 8003 C State boiler 8005 C State solar 8007 C State solid fu...

Page 75: ... temperature 8310 C Boiler setpoint 8311 C Boiler switching point 8312 C Control sensor Boiler sensor B2 Return sensor B7 HW charging sensor B36 HW outlet sensor B38 HW circulation sensor B39 Cascade sensor B10 B70 8313 E Boiler return temp 8314 C Fan speed 8323 C Set point fan 8324 C Current fan control 8325 C Burner modulation 8326 C Ionization current 8329 C Hours run 1st stage 8330 Eu Start co...

Page 76: ...ctor pump 8532 Eu Solid fuel boiler temp 8560 C Hours run solid fuel boiler 8570 C Diagnostics consumers Prog no Level Standard value Outside temp 8700 Eu Outside temp min 8701 Eu Outside temp max 8702 Eu Outside temp attenuated 8703 E Outside temp composite 8704 E Central heating pump 1 Off On 8730 C Heat circ mix valve 1 open Off On 8731 C Heat circ mix valve 1 close Off On 8732 C Speed CH pump ...

Page 77: ... C Hot water temp setpoint 8831 C Hot water temp 2 8832 C Hot water circulation temp 8835 E HW charging temp 8836 E Flow temp setp VK1 8875 C Flow temp setp VK2 8885 C Flow temp setp VK3 8895 C Swimming pool temp 8900 C Swimming pool setpoint 8901 C Primary controller temp 8930 E Primary controller setpoint 8931 E Common flow temp 8950 E Common flow temp setpoint 8951 E Common return temp 8952 E C...

Page 78: ...15 56 6 kW Required output ignition1 9512 E Paramount four 30 14 5 kW Paramount four 40 19 5 kW Paramount four 50 32 0 kW Paramount four 60 35 0 kW Pa ramount four 80 50 0 kW Paramount four 95 50 8 kW Para mount four 115 56 6 kW Required output LF1 9524 E Paramount four 30 5 6 kW Paramount four 40 9 0 kW Paramount four 50 10 0 kW Paramount four 60 14 0 kW Pa ramount four 80 21 0 kW Paramount four ...

Page 79: ... can be determined by the gas meter for example Info option 1 Prog no Level Standard value Fault message Maintenance Setpoint manual operation Setpoint control stop Boiler temperature Outside temp Domestic water temperature Collector temp Solar Gain 24 Hour Total Solar Gain Solid fuel boiler temp Buffer storage tank temperature Swimming pool temp State central heating CH1 State central heating CH2...

Page 80: ...tons for heating and drinking water mode Rotary selector room temperature comfort setpoint Presence button only room unit Programming lock 27 If this lock is activated parameters can be displayed but not changed Temporary unlocking Press OK and ESC simultaneously for at least 3 s The lock will be re activated after leaving the setting level Permanent unlocking First temporary unlocking then prog n...

Page 81: ... prog no 40 is selected it must be defined under prog no 44 or 46 whether the heating circuits HK2 and HK3 P are to be operated together with heating circuit 1 or independently of heating circuit 1 Room temp device 1 47 The assignment of room unit 1 to the heating circuits can be selected here CH circuit 1 only The room temperature is sent exclusively to heating circuit 1 For all assigned HCs The ...

Page 82: ...is changed all 3 start stop phases will be copied to the day group automatically To select groups of days Mon Sun Mon Fri or Sat Sun turn the control knob anti clockwise to select individual days Mon Tue Wed Thu Fri Sat Sun turn the control knob clockwise Heating phases 501 606 Up to 3 heating phases can be set per heating circuit These are active on the days selected under Select prog no 500 520 ...

Page 83: ... in the heating phases Without room sensor or with the room influence switched off prog no 750 1050 1350 this value is used for calculation of the flow temperature to theoretically reach the set room temperature Reduced temp setpoint 712 1012 1312 Setting of the desired room temperature during the reduced heating phase Without room sensor or with the room influence switched off prog no 750 1050 13...

Page 84: ... intersection of both lines provides the value for the heating curve slope Heating curve displacement 721 1021 1321 Heating curve correction by parallel offset if the room temperature is gen erally too high or too low Heating curve adaption 726 1026 1326 Automatic adaptation of the heating curve to the actual conditions as a re sult of which no correction of the heating curve slope is required Not...

Page 85: ...her requirements it can cause higher resulting temperatures in the pump heating circuit Flow temp setpoint room stat 742 1042 1342 For room thermostat mode the flow setpoint set here applies With the setting C the value calculated via the heating curve is used as the flow setpoint Swi on ratio room stat 744 1044 1344 The boiler tries to adapt the flow temperature so that the switch on ratio set un...

Page 86: ... Room temperature actual value TRS A Room temperature setpoint raised The boost heating becomes active when the room temperature setpoint is switched over from protection or reduced mode to comfort mode During the boost heating the room temperature setpoint is increased by the value set here This causes the actual room temperature to rise to the new tem perature setpoint quickly The boost heating ...

Page 87: ...0 9 2 1 4 3 6 4 8 6 21 5 15 C 0 0 7 1 8 3 6 5 5 7 3 18 2 20 C 0 0 6 1 6 3 2 4 7 6 3 15 8 For more information see Time constant building 6110 page 111 Optimum start control max 790 1090 1390 and Optimum stop control max 791 1091 1391 Xon Start time set forward Xoff Stop time set forward ZSP Time switching program TRw Room temperature setpoint TRx Room temperature actual value The optimisation of t...

Page 88: ...ting of the pump heating circuit by switching the pump on and off if the flow temperature is higher than the flow tem perature required according to the heating curve e g in case of higher re quests from other consumers Mixing valve boost 830 1130 1430 The heat request of the mixed heating circuit to the heat source is raised above the value set here This boost is intended to correct temperature f...

Page 89: ...boiler Yes The heating circuit can be supplied from the buffer storage tank With prim contr system pump 872 1172 1472 5092 This parameter establishes whether a zone system pump goes into opera tion with a heat demand of the heating circuit This system pump is based on the segment in which this controller is located LPB bus system and which is controlled with a primary control No The heating circui...

Page 90: ...When an external timer is used above the inputs Hx selection of the oper ating level to which the heating circuits are to be switched is possible Off Reduced On Optg mode changeover 900 1200 1500 With external change of operating mode via Hx it can be selected whether during automatic operation it is changed from comfort set point to the frost prevention setpoint or reduced setpoint 9 2 7 Domestic...

Page 91: ...ion see Delay heat request 746 1046 1346 page 85 Legionella function 1640 Function to kill legionella germs by heating up to the set legionella function setpoint see programme number 1645 Off Legionella function is switched off Periodically Legionella function is repeated periodically depending on the set value prog no 1641 Fixed weekday Legionella function will be activated on a certain week day ...

Page 92: ...tion and actual value during the legionella function The setpoint set must be observed on the sensor during the dwell time set prog no 1646 The maximum setting of the circulation value is limited by the nominal set point Optg mode changeover 1680 Using external switching above the entrance H1 it can be selected into which operating mode is switched into Off The function is switched off 9 2 8 Consu...

Page 93: ...has dropped by 1 C below the maximum heating limit tem perature With solar integration 2080 Setting of whether the swimming pool heating can be done by solar ener gy or not 9 2 10 Primary control feed pump Flow temp setpoint min 2110 and Flow temp setpoint max 2111 With these boundaries a range for the flow setpoint can be defined Syst pump on heat gen lock 2121 This parameter can set whether the ...

Page 94: ...utdown differential is increased by 50 However this setting cannot guarantee that the burner remains operational for the selec ted period Burner off time min 2243 The boiler minimum pause time only takes effect between heating require ments coming following in sequence The boiler minimum pause time blocks the boiler for a set time SD burner off time 2245 When a switching difference is exceeded Bur...

Page 95: ... speed of the boiler pump so that the nominal rise between the boiler return and boiler flow is ob served If the actual rise is larger than the nominal rise the pump speed is in creased otherwise the pump speed is reduced Burner output If the burner is operated with low output then the boiler pump should also run at low speed During high boiler output the boiler pump should run at high speed Pump ...

Page 96: ...ecessary switch off during transient effects the switch off dif ference adapts dynamically depending on the temperature profile see fig Delay heat req special op 2470 The heat request during special operation chimney sweep function con troller stop manual operation is sent to the burner delayed by the time set here In this way slowly opening mixers can already start up before the burner goes into ...

Page 97: ...s Early on late off Additional boilers are switched on as early as possible output range min and switched back off again as late as possible out put range min I e as many boilers as possible in operation or long run ning times for additional boilers Release integral source seq 3530 A value generated from temperature and time The lag boiler is switched on when the set limit is exceeded Reset integr...

Page 98: ...itched over again 9 2 13 Solar Temp diff on 3810 and Temp diff off 3811 1 0 On off collector pump T Temperature T1 Temp diff on T0 Temp diff off TK Collector temperature TL Charging temperature min buffer storage tank swimming pool TS Storage tank temperature t Time The switching on and switching off point of the collector pump is set with these functions Basis is the temperature difference betwee...

Page 99: ...Charging temp max prog no 4750 Setpoint solar heat ing prog no 2055 C Storage tank temp max prog no 5051 Storage tank temp max prog no 4751 Swimming pool temp max prog no 2070 1 With swimming pool heating set as priority prog no 2065 the swimming pool will be heated before the storage tanks For more information see Charging priority solar 2065 page 93 Charging time relative prio 3825 If the prefer...

Page 100: ...rier 3860 Pump protecting function to prevent overheating of the collector pump in case of evaporating danger of the heat carrying medium due to high col lector temperature Pump speed min 3870 andPump speed max 3871 Input of the minimum and maximum solar circuit pump speeds in percent Antifreeze 3880 Information of the antifreeze used Antifreeze concentration 3881 Input of antifreeze concentration...

Page 101: ... None The automatic heat generator lock is deactivated With B4 The automatic heat generator lock is triggered by the buffer cylinder B4 With B4 and B42 B41 The automatic heat generator lock is triggered by the buffer cylinders B4 and B41 B42 Auto heat gen lock SD 4721 The heat generator is locked if the the temperature in the buffer storage tank is higher than the boiler setpoint Auto heat gen loc...

Page 102: ...il return sen sor B73 must also be configured Optg action return diversion 4796 The function can either be used as return temperature increase or as re turn temperature decrease Temp decrease If the return temperature of the consumers is higher than the temperature on the selected sensor prog no 4795 the lower part of the storage tank can be preheated with the return flow The re turn temperature d...

Page 103: ...lly charged at every DHW demand Full charging legio The cylinder is fully charged if the legionella function is enabled otherwise it is only recharged Full charg 1st time day During the first charging of the day the cylinder is fully charged then recharged Full charg 1st time legio The cylinder is fully charged during the first charging of the day and if the legionella function is enabled otherwis...

Page 104: ... the surrounding of the collector El imm heater optg mode 5060 Substitute The DHW is only heated by an immersion heater if the boiler signals a malfunction or a boiler lock exists Summer The DHW is heated by an immersion heater if all connecting heating circuits have switched to summer mode As soon at least one heating circuit is switched to heating mode the DHW preparation is tak en over by the b...

Page 105: ...rcent Speed Xp 5103 The P band Xp defines the amplification of the controller A smaller Xp val ue leads to a higher actuation of the charging pump with equal control dif ference Speed Tn 5104 The reset time Tn determines the reaction speed of the controller when compensating for remaining controller differences A shorter reset time Tn leads to faster compensating Speed Tv 5105 The preholding time ...

Page 106: ...ature has reached the boiler setpoint plus the value set here The setting 5 C results in the intermedi ate circuit pump being switched on as soon as the boiler temperature is 5 C below the boiler setpoint Excess interm circ temp del 5151 Control of the burner output on the charging temperature is activated if the time set here has elapsed since switching on the intermediate circuit pump 9 2 17 Con...

Page 107: ...nal consumer circuits All requests The diverting valve is connected hydraulically for all re quests and switches between DHW mode and the remaining requests The boiler pump runs for all requests Request CH1 HW only The diverting valve is connected hydraulically only for heating circuit 1 and DHW and switches between DHW mode and heat circuit 1 mode All other requests are not connected hydrauli cal...

Page 108: ... the settings Buffer return valve Y15 This valve must be configured for the return temperature increase reduction or partial charging of the buffer storage tank Solar pump ext exch K9 The solar circuit pump for the external heat ex changer K9 must be set here Solar ctrl elem buffer K8 If several exchangers are connected the buf fer storage tank must be set at the respective relay output and the ty...

Page 109: ...mming pool sensor B13 Sensor for measurement of swimming pool temperature Solar flow sensor B63 This sensor is required for the solar usage meas urement Solar return sensor B64 This sensor is required for the solar usage measurement Function input H1 5950 Function input H4 5970 and Function input H5 5977 None No function Optg mode change CHs HW Changeover of the operating modes of the heating circ...

Page 110: ...ge value 1 function value 1 and voltage value 2 function value 2 only applies to H1 Preselected output 10V The generator receives a voltage signal DC 0 10 V as output request The linear curve is defined via two fix points voltage value 1 function value 1 and voltage value 2 function value 2 only applies to H1 For more information see Optg mode changeover 900 1200 1500 page 90 Flow temp setp cons r...

Page 111: ...Time constant building 6110 The value set here influences the reaction speed of the flow setpoint in case of fluctuating outside temperatures as a function of the building de sign Example values refer also to Quick setback 40 for buildings with thick walls or outer insulation 20 for buildings of normal building design 10 for buildings of light building design For more information see Quick setback...

Page 112: ...erting valve for buffer storage tank K8 Solar charging pump for swimming pool K18 Solar diverting valve for swimming pool K18 External solar ex changer Solar pump K9 DHW DHW stor age tank B Buffer storage tank 0 No solar 1 1 3 DHW B 5 X 6 X 8 X DHW B 9 X DHW B 10 X DHW 11 X DHW 12 X P 13 X P 14 X 15 X 17 X DHW B 18 X DHW B 19 X X 20 X X 22 X DHW B 23 X X DHW B 24 X X DHW 25 X X DHW 26 X X P 27 X X...

Page 113: ...ump 2 Heating circuit pump 02 Heating circuit pump 02 Heating circuit pump 3 Heating circuit pump mixer 03 Heating circuit pump mixer 03 Heating circuit pump mixer Software version 6220 Display of the actual software version 9 2 18 LPB system Device address 6600 andSegment address 6601 The two part LPB address of the controller consists of the 2 digit segment number and the 2 digit device number B...

Page 114: ...All CHs in segment DHW heating applies to all heating circuits in this section All CHs in system DHW heating applies to all heating circuits in the sys tem Note For all settings the controllers which are in holiday status are also taken into account for the DHW preparation Note OT limit ext source 6632 Additional generators connected via the LBP bus can be locked or re leased according to their ow...

Page 115: ...etting Flow temp 1 alarm 6740 Flow temp 2 alarm 6741 Flow temp 3 alarm 6742 Boiler temp alarm 6743 and Hot water charging alarm 6745 Setting the time after which a fault message will be triggered in case of persisting deviation from temperature nominal and actual values Error history Error codes 6800 6995 The last 20 error messages with error codes and time of occurrence are saved to the error mem...

Page 116: ...hat heat pumping to the domestic hot water circuit takes priority when the chimney sweep function is active Off Compulsory pumping of the heat to the heating circuits On When the chimney sweep function is active heat is pumped with priority into the domestic hot water circuit Telephone customer service 7170 Here the desired telephone number of customer service can be entered PStick storage pos 725...

Page 117: ...ying the data from the stick to the LMS control The operation was aborted The control LMS is locked Status change to read lock Incompatible data set Data set does not match LMS control Compati bility conditions are not met The data set can not be imported Wrong stick type Stick type does not match selected action E g read ing from write stick or writing to read stick is not possible Stick format e...

Page 118: ...g mode is set under prog no 5060 Collector pump Q5 Connection of a circulating pump in case of solar collector use Consumer circuit pump VK1 2 Connection of a pump at the input Q15 18 for an additional consumer which is requested via an Hx input Boiler pump Q1 the connected pump is used for recirculation of the boil er water Alarm output K10 Any new fault will be signalled by means of this alarm r...

Page 119: ...there is a disturbance which prevents the burner control from operating the status output is switched off Status information K36 The output is set when the burner is in opera tion Fan shutdown K38 This output serves to switch the fan off The output is activated when the fan is needed otherwise it is not activated The fan should be switched off as often as possible in order to minimise the total en...

Page 120: ...excess heat Release swi pool solar This function enables the solar swimming pool heater to be released externally e g via a manual switch or the solar charging priority to be specified as compared to the storage Operating level DHW HCs The operating level can be set via the con tact instead of via the internal time switching program external time switching program Ambient thermostat HCs With the i...

Page 121: ...ng circuits HC1 HC3 Collector pump Q5 Actuation of a circulating pump when a solar collec tor is used Solar pump ext exchanger K9 The solar circuit pump for the external heat exchanger K9 must be set here Solar pump buffer K8 If several exchangers are connected the buffer storage tank must be set at the respective relay output and the type of solar regulating unit must be defined under prog no 584...

Page 122: ...protection active Frost prot room active Frost protection flow active System frost protect active Summer operation Summer operation Off 24 hour Eco active Setback reduced Setback off Room temp limitation Off Tab 28 Status table domestic water The following messages are possible under Drinking water End user Eu Commissioning Engineer menu Status Limitter has tripped Limitter has tripped Manual cont...

Page 123: ...harged max charging temp Charged legionella temp Charged nominal temp Charged reduced temp Off Off Ready Ready Tab 29 Status table boiler The following messages are possible under Boiler End user Eu Commissioning Engineer menu Status SLT has tripped SLT has tripped Fault Fault Limitter has tripped Limitter has tripped Manual control active Manual control active Chimney sweep funct active Chim swee...

Page 124: ...ntrol active Fault Fault Frost prot collector active Frost prot collector active Recooling active Recooling active Max st tank temp reached Max st tank temp reached Evaporation prot active Evaporation prot active Overtemp protect active Overtemp protect active Max charging temp reached Max charging temp reached Charg HW buffer swi pool Charg HW buffer swi pool Charging HW buffer Charging HW buffer...

Page 125: ...Overrun active Overrun active In operation In operation Assisted firing active Assisted firing active Released Released Frost protection active System frost protect active Boiler frost prot active Off Off Tab 32 Status table burners The following messages are possible under Burner End user Eu Commissioning Engineer menu Status Lockout position Lockout position Start prevention Start prevention In ...

Page 126: ...ault Heating mode restricted Heating mode source Heated max swi pool temp Heated max swi pool temp Heated Heated setpoint solar Heated setpoint source Heating mode Heating mode solar off Heating mode source off Cold Cold 9 2 24 Diagnostics cascade heat generation consumers Diagnostics cascade heat generation consumers 8100 9058 Displays of different setpoint and actual values relay switching statu...

Page 127: ...nformation see Controller delay fan output 2452 page 96 Required output HF 9529 Nominal output fan speed under boiler in HF Postpurge time 9540 After venting time Caution This parameter must only be changed by a heating specialist Fan output speed slope 9626 and Fan output speed Y section 9627 The speed of the fan can be adjusted with this This is important for com plex installations or change to ...

Page 128: ... Cleaning of heating surfaces and burner should be carried out by the ap proved installer Before beginning work the gas tap and the shut off valves of the heating water should be closed 10 1 2 Inspection and service as required Note We recommend having the Paramount four inspected annually If the need for maintenance work is found during inspection this should be carried out according to need Main...

Page 129: ...or the detergents listed are included with the product or are available from the respective manufacturers Caution During application of the detergent only the heat exchanger on the flue gas side may be treated No detergent residue may remain on the boiler components the cable plugs or casing since this can otherwise lead to corrosion and appliance malfunction Residues sprayed by mistake must be cl...

Page 130: ... ignition TSA2 Safety time variable Flame monitoring without ignition TI Interval time Flame stabilisation MOD Modulating mode Operating burner THL2 Subsequent ventilation with last operating fan speed Fan continues to run THL2A Subsequent ventilation with pre purging fan speed Fan continues to run TNB Burner shut off delay Permitted burner run on time TNN Overrun time Permitted fan run on time ST...

Page 131: ...nsion Danger of electric shock Risk of electric shock Danger to life due to high voltage Caution Do not touch plug contacts during the ignition process For measurement of the ionization current pull plug from the gas burner control and connect an ampere meter between plug and electrode Ignition electrodes 2 To ensure that the Paramount four unit ignites reliably and quietly the in stallation posit...

Page 132: ... Undo the attachment screw for the air intake silencer at the top of the Paramount four 5 Remove the air intake silencer 6 Loosen the screw connections of the gas connection pipe at the mix ing tube and the gas valve 7 Remove the gas connection pipe and the gas nozzle 8 Loosen the 5 fastening screws at the mixing tube heat exchanger 9 Remove the bracket 10 Pull the burner together with mixing tube...

Page 133: ...f flow and return on the heat ex changer flat seal 5 Remove the air vent 6 Paramount four 30 40 Remove the plastic retainer from the top of the heat exchanger For this remove 2 screws from the casing cover 7 Take the holding clips off 8 Lift the heat exchanger off the flue gas collector and lift it out 9 Pull the cable off the water pressure monitor 10 Undo the screwed connector at the pump replac...

Page 134: ...ensor fault Check connection inform heating specialist1 54 Flow temperature DHW sensor fault 57 Drinking water circulation temperature sensor fault 60 Room temperature 1 sensor fault 65 Room temperature 2 sensor fault 68 Room temperature 3 sensor fault 70 Storage tank temp 1 top sensor fault 71 Storage tank temp 2 bottom sensor fault 72 Storage tank temp 3 middle sensor fault 73 Collector temperat...

Page 135: ...t 1 3 146 Configuration fault common message 151 Internal fault Check parameters see adjustment table installer and or call up values unlock LMS replace LMS installer 1 3 152 Parameterization fault 160 Fan fault Fan possibly defective speed threshold set wrongly 3 162 Air pressure monitor does not close 171 Alarm contact H1 or H4 activated 172 Alarm contact H2 EM1 EM2 or EM3 or H5 activated 178 Te...

Page 136: ... damper 427 Configuration flue damper 432 Functional earth X17 not connected 1 Switch off start prevention re start after elimination of fault 2 Check parameter in accordance with table Check the installer adjustment table and program to the basic settings or query internal LMS SW diagnosis code and correct the corresponding parameter faults according to fault specification 3 switch off and lockin...

Page 137: ...t connected No gas Gas pressure too low In spite of flame formation the burner goes into fault mode after expiration of the safety time Ionization electrode defective or soiled Ionization electrode does not penetrate the flame Ionization electrode is not connected Gas pressure not stable 11 Troubleshooting 7658013 02 15092016 Paramount four 30 115 kW 137 ...

Page 138: ...ble See Please follow the legal requirements applicable to disposal in your country 12 1 2 Appliance disposal The appliance can be returned to Potterton Commercial for disposal via a specialist company The manufacturer undertakes to recycle the appliance correctly Note The appliance is recycled by a disposal company If possible the materials especially the plastics are identified This enables cor ...

Page 139: ...13 Appendix 13 1 Declaration of conformity 13 1 1 Declaration of conformity 13 Appendix 7658013 02 15092016 Paramount four 30 115 kW 139 ...

Page 140: ...rew connections 35 Frost protection setpoint 27 53 G Gas connection 18 19 21 36 Gas filter 36 Gas tap 53 Gravity lock 128 H Hardness stabiliser 29 Heating emergency switch 53 Heating mode 53 heating water quality 28 I INFO 27 Information key 26 27 Inspection apertures 33 Installation room 33 Introducing into a shaft 39 IP rating 34 43 K Keys 26 27 ESC key 0 0 Information key 0 0 OK key 0 0 Presenc...

Page 141: ... curve 83 Shortening of the pipes 39 Shut off valve 36 Softening system 29 Software version 14 Standards 12 Summer winter heating limit 84 T Tip on energy saving circulating pump 92 Topping up water 128 Index 7658013 02 15092016 Paramount four 30 115 kW 141 ...

Page 142: ...Index 142 Paramount four 30 115 kW 7658013 02 15092016 ...

Page 143: ...hnological information contained in these technical instructions as well as any drawings and technical de scriptions supplied remain our property and shall not be multiplied without our prior consent in writing Subject to alterations ...

Page 144: ...Oaklands Business Centre Oaklands Park Wokingham RG41 2FD Phone 0345 070 1055 www potertoncommercial co uk Potterton Commercial Part of Baxi Heating UK Ltd Innovation House 7658013 02 15092016 ...