INSTALLATION
INSTALLATION
1
2 3 4
5
0
6
F
Ps
Pa
Is
Ia
CN3
CN4
CN6
3
2
1
4 5 6
Psc
Psr
Ua
C
S1
Us
C
C
Cable duct (not supplied)
Sensor connections
- Route probe cables through the cable guides (F), the
fairleads (Ps), the passages on the insulation (Is), the
solar station outlets (Us/Ua) and connect them to termi-
nal board M4 of solar regulator (terminals S1-S2-S3-S4)
making reference to the instructions provided in the
specific regulator manual.
Upon connection, or should it be necessary to increase probe
cable length, refer to these remarks:
- Absolutely avoid laying probe cable together with
mains power cables and/or AC cables
- Absolutely avoid routing cables close to strong mag-
netic fields
- Avoid any cable jointing as much as possible; solder
and duly insulate any indispensable jointing
- Use twisted and shielded wires
- Use cables having a cross-section of over 0.5 mm
2
Solar controller power connections
- Route the supply cable through the cable guides (F),
the fairleads (Pa), the passages on the insulation (Ia),
the solar station outlets (Ua) and connect it to terminal
board M1 of solar regulator (terminals L-N-GND) mak-
ing reference to the instructions provided in the specific
regulator manual.
Once electrical connections are completed, fasten cables us-
ing the guides supplied, close regulator cover and solar sta-
tion protection housing.