3200 Series
User Manual
Part No HA028651 Issue 11.0 July-12 57
CONTROL LIST
‘
CTR L
’
Parameter
Name
Parameter Description
(Scrolling Display)
Value
Default
Access
Level
O P. H I
OUTPUT HIGH
Adjust to limit the maximum heating
power applied to the process
+100.0%
100.0% L3
O P. LO
OUTPUT LOW
Adjust to limit the maximum cooling
power applied to the process or to
apply a minimum heating power
+100.0%
0.0 (heat
only)
-100
(cool)
L3
M TR . T
MOTOR TRAVEL TIME
Set this value to the time that it takes
for the motor to travel from its fully
closed to its fully open position.
0.0
to
999.9
seconds
Note: In motorised valve control only the PB
and TI parameters are active. The TD
parameter has no effect on the control.
0.0 L3
D . B A N D
CHANNEL 2 DEAD BAND
Period when no output is demanded
from either channel 1 or channel 2
Adjust, for example, to increase the
period when no heating or cooling
power is applied
Off
or 0.1 to 100.0% of the cooling
proportional band
OFF
L3
H Y S T. H
HEATING HYSTERESIS
1 to 9999 display units
1
L3
On/off
only
H Y S T. C
COOLING HYSTERESIS
1
S A FE
SAFE OUTPUT POWER
To set the output level in a sensor
break (open circuit) condition
-100.0 to 100.0% limited by OP.HI and OP.LO
0.0%
L3
F. M O D
FORCED MANUAL OUTPUT MODE
Selects how the loop behaves on
transfer from Auto to Manual.
Transfer from Manual to Auto is
always bumpless.
none
Transfer between Auto/Manual/Auto
is bumpless
none
L3
SteP
Transfer from Auto to Manual, the
output goes to a pre-set value (F.OP)
Last
Transfer from Auto to Manual, the
output goes to the previously set
manual value
C oo l. t
NON-LINEAR COOLING TYPE
This selects an algorithm most suited
to the type of cooling. Typically used
in extruders.
Lin
Linear As
order
code
Conf
OIL
Oil cooling
H20
Water cooling
Fan
Forced air cooling
F. O P
FORCED OUTPUT
To pre-set a value for the Manual
output when F.MOD = STEP
-100.0 to 100.0% limited by OP.HI and OP.LO
0.0
L3
A -M
LOOP MODE – AUTO MANUAL OFF
see also section 4.4.4.
Auto
To select automatic operation
L3
Man
To select manual operation
OFF
Control outputs inhibited
lb r
LOOP BREAK STATUS
No
Shows the current status of loop
break.
Read
only
YES
TU . H I
TUNE HIGH LIMIT. Set this to limit
the maximum heating output during
autotune
Range between OP.HI and OP.LO
L3
TU . LO
TUNE LOW LIMIT. Set this to limit
the maximum cooling output during
autotune
Parameters are further described in the following sections.
Содержание XST-2-0-12-1V1-E28
Страница 16: ...12 FURNACE TROUBLE SHOOTING ...
Страница 27: ...ɸ ...
Страница 28: ...ɸ ...
Страница 29: ......
Страница 30: ......
Страница 31: ...3216 3208 3204 User Manual 3200 Range Process Controller HA028651 11 Aug 2012 ...
Страница 170: ...User Manual 3200 Series 138 Part No HA028651 Issue 11 0 July 12 21 Certificate of Conformity ...
Страница 171: ......
Страница 173: ...Model 2416 Process Controller User Manual Part No HA025041_12 Date August 2014 ...
Страница 174: ...This page is intentionally blank ...
Страница 259: ...This page is intentionally blank ...