126 Part No HA028651 Issue 11.0 July-12
17.10
To Set up Recipes
A recipe can store up to 38 parameters, as listed in section 14.3.1. Up to five recipes are available in 3200 series
controllers, as described in section 14.
17.10.1
Example 1: Using the Browser view
Set Two Different Alarm Thresholds and Store in Recipes 1 and 2
1.
Set an alarm threshold - see example 17.6.2.
2.
Select ‘RECIPE’ in the browser
3.
In RecipeSave, select the recipe number e.g. 1
4.
Set the alarm threshold to another value and save in Recipe 2
5.
In RecipeNumber choose the recipe to run. This can also be done through the controller user interface
Any of the 38 parameters can be set up in any of the five recipes using the above procedure.
It may be more convenient to open more than one parameter list as shown in the above view. To do this, double click on
each list header in turn. The lists can be arranged using Window in the main menu and choose Tile Vertically, Tile
Horizontally or Cascade.