Load Current Monitoring and Diagnostics Installation and Operation Handbook
8.10 The Scaling Factor
The value of the current displayed on the controller is scaled using the scaling factor. This is found in the
inSt
ConF
list. It is set, by default, to 100 and assumes a single turn through the current transformer. If two turns are
made through the current transformer it will be necessary to adjust the scaling factor to 50 to obtain the same
reading.
Under normal conditions you should not need to change the scaling factor.
If, however, you wish to change the sensitivity of the current reading, for example, to read very low currents you
may need to change the number of turns through the PDCTX and/or adjust the scaling factor to compensate. See
also note 1 below.
8.10.1 To Adjust the Scaling Factor
Do This
This Is The Display You Should See
Additional Notes
Press
button until
inSt Conf
is
displayed
Press
until
LC.Hi
is displayed
Press
or
to change the
scaling factor
Should you wish to read currents lower than 4A using a PDCTX it is necessary to increase the number of turns
through the PDCTX and adjust the scaling factor to compensate.
For example: To read 1.0A wind 4 turns through the PDCTX and adjust the scaling factor to 25 as shown in the
table below.
Scalar = 100/N Where N = Turns through PDCTX
N
Scalar
N
Scalar
1
100
5
20
2
50
10
10
4
25
Finally Exit configuration level.
See Chapter 5
i
Note:
MinimumResolvable Current
.
TE10 4A RMS. It is not possible to read currents lower than 4A when using a TE10.
PDCTX 4A RMS for a single turn through the PDCTX
i
Note:
Maximum Resolvable Current
TE10 Determined by the maximum range of the SSR
PDCTX 100A (or 100 ampere turns)
LC.Hi
100
inSt
Conf
8-8 HA025041 issue 12 Aug 14
Содержание XST-2-0-12-1V1-E28
Страница 16: ...12 FURNACE TROUBLE SHOOTING ...
Страница 27: ...ɸ ...
Страница 28: ...ɸ ...
Страница 29: ......
Страница 30: ......
Страница 31: ...3216 3208 3204 User Manual 3200 Range Process Controller HA028651 11 Aug 2012 ...
Страница 170: ...User Manual 3200 Series 138 Part No HA028651 Issue 11 0 July 12 21 Certificate of Conformity ...
Страница 171: ......
Страница 173: ...Model 2416 Process Controller User Manual Part No HA025041_12 Date August 2014 ...
Страница 174: ...This page is intentionally blank ...
Страница 259: ...This page is intentionally blank ...