3200 Series
User Manual
Part No HA028651 Issue 11.0 July-12 121
17.7.3
Example 3: Inverted Status Word
The Inverted Status Word is available in firmware versions 2.11+. It is used to generate a message when a bit in a status
word is not true. For example, it may be applied to an alarm or event to indicate that the process is operating normally.
The example below continues from the previous example and adds the message PROCESS OK on the controller when the
Alarm 1 condition is not true.
1.
Press
and select the ‘Message Table’ tag.
2.
Add the ‘InverseStatus’
parameter as follows:-
a.
Click where the parameter
is required.
b.
Select ‘Insert’
c.
Select
‘STATUSInverseStatus’ from
the pop up.
3.
In the Operator box select
‘Mask’.
4.
In the Value box select 1 (Alarm
1 only).
5.
In the message box enter ‘PROCESS OK’.
6.
Press
‘Update Device Flash Memory’ button.
The controller will now indicate the scrolling message PROCESS OK when Alarm 1 is not true and TOO HOT when Alarm 1
is exceeded.