Controller Operation 

Figure 1 – Control Panel 

 

 
The controller uses a set of digital LED displays to 
show various temperatures as well as status and 
alarm conditions.  
 

Start 

 

To start the unit press the Start button. If the water 
level in the reservoir is below the level required to 
satisfy the low level sensor, the controller will initiate 
an initial fill sequence. During this sequence, the fill 
valve opens and will remain open until the proper 
water level is achieved. The automatic fill cycle has a 
four-minute timer that will close the fill solenoid 
valve and stop the pump. This safety has been 
included in case there is a leak present that does not 
allow the reservoir to fill up. After the initial fill cycle 
is complete, the unit will automatically fill the tank if 
the level gets too low. If the fill valve remains open 
for more than 20 seconds, the unit will close the fill 
solenoid valve and shut off the pump. The display

 

will show a 

1

 as the first digit followed by the tank 

temperature.

  

 

Stop 

 

To stop the unit press the Stop button. When the 
unit is stops, the status display and the last digital 
display on the right will display a dot. 
 
 
 
 

 

CAUTION: Stopping the unit without cooling the 
water in the reservoir can lead to potential user 
injury during servicing of the unit. In order to allow 
the water in the reservoir to be cooled automatically 
during shut down, depress the Temperature Adjust 
button and the Password ‘C’ button to initiate an 
automatic cool down cycle. The controller will open 
the cooling valve and keep it open until the 
temperature of the water in the reservoir is below 
105°F (40°C). The automatic cool down cycle can be 
stopped at any time by depressing the Off button. 

 

Temperature Adjust 

 

The Temperature Adjust button is used to view and 
change the set point temperatures. 
 

Display Set Point Temperature 

To display the Set Point temperature press and 
release the Temperature Adjust button. This will 
show the Set Point temperature in the display. If no 
other buttons are pressed for 5 seconds, the display 
will return to the actual temperature. 
 

Setting Set Point Temperature 

To change the Set Point temperature press the 
Temperature Adjust button and release to display 
the current Set Point temperature and then 
immediately used the Increase or Decrease buttons 
to change the Set Point temperature until the 
desired temperature is displayed. Once the desired 
Set Point temperature displays, release all buttons. 
After 5 seconds, the display will return to the actual 
temperature and the new set point is active. 
 

Increase 

 

Pressing the Increase button increases the value of 
the set point, deviation alarm, and timer settings 
when those adjustment features are active. 
 

Decrease 

 

Pressing the Decrease button decreases the value of 
the set point, deviation alarm, and timer settings 
when those adjustment features are active. 

Date & Time  

 

Press the Timer button to display and adjust pump 
running hours and automatic start/stop timers as 
indicated below. 
 

Содержание Vactherm RV

Страница 1: ......

Страница 2: ......

Страница 3: ...Running Hour Counter 5 Displaying Clock Time 5 Setting Clock Time 5 Displaying Day of the Week 5 Setting Day of the Week 5 Timer On Off 5 Display Status of Timer 5 Turning Timer On Off 5 Setting Star...

Страница 4: ...t Temperature 10 Setting Set Point Temperature 10 Step 6 Adjusting the Vacuum 11 Preventive Maintenance 11 Once a Week 11 Once a Month 11 Once a Year 11 General Troubleshooting 12 Charts and Drawings...

Страница 5: ...eneral Mandatory Action Wear Eye Protection Wear Protective Gloves Wear Ear Protection Disconnect Before Carrying Out Maintenance or Repair Connect an Earth Terminal to Ground Only qualified personnel...

Страница 6: ...trols or any other major component torn loose from its mounting point Record any signs of concealed damage and file a shipping damage claim immediately with the shipping company Most carriers require...

Страница 7: ...percentage of imbalance is then 452 442 x 100 452 2 2 This exceeds the maximum allowable of 2 There is a terminal block for main power connection to the main power source The main power source should...

Страница 8: ...mperature Adjust button and the Password C button to initiate an automatic cool down cycle The controller will open the cooling valve and keep it open until the temperature of the water in the reservo...

Страница 9: ...our clock and will begin keeping dates from that point forward until reset To adjust the day press the Date Time button twice release and immediately use the Increase and Decrease buttons to set the c...

Страница 10: ...tons Once the desired day is displayed use the On button to toggle the status of the timer for that day Examples of days of week displays Monday timer off 1 Monday time on 1 Tuesday timer off 2 Tuesda...

Страница 11: ...rrent tank temperature in the display Password Entry Pressing the Password Entry buttons will allow for secured access to the control program and will prevent unauthorized personnel from making change...

Страница 12: ...t Circuit Temperature display flashing Alarm horn on and X1 output powered Temperature Sensor Disconnected Temperature display flashing Alarm horn on and X1 output powered Draining the Mold The temper...

Страница 13: ...and cumulative pressure rating of the maximum pump pressure and the unit fill fluid pressure NOTE A cooling source inlet filter ships loose in the crate with the unit Install this in the inlet of the...

Страница 14: ...F 7 2 C 5 40 F 4 4 C 10 35 F 1 7 C 15 30 F 1 1 C 20 25 F 3 9 C 25 20 F 6 7 C 30 CAUTION When your application requires the use of glycol use industrial grade glycol specifically designed for heat tran...

Страница 15: ...m the set point there may be a problem with the unit If this is the case refer to the General Troubleshooting section of this manual or contact our Customer Service Department 2 Check the pump dischar...

Страница 16: ...ent defective Replace heating element Safety fuse defective Replace safety fuse The unit does not cool Solenoid valve at Cooling Water In defective Replace solenoid valve Cooling heat exchanger clogge...

Страница 17: ...13 Charts and Drawings Figure 1 Pump Performance 60 Hz...

Страница 18: ...14 Figure 2 Cooling Capacity...

Страница 19: ...15 Figure 3 High Voltage Wiring Diagram...

Страница 20: ...16 Figure 4 Low Voltage Wiring Diagram...

Страница 21: ...17 Figure 5 Control Board Details...

Страница 22: ...18 Figure 6 Heating Element Details...

Страница 23: ...perature sensor 9 Microprocessor control 10 Heat exchanger 11 Heating element 12 Overflow pipe 13 Solenoid valve for water filling 14 Solenoid valve for cooling 15 Connection for external sensor 16 Ch...

Страница 24: ...20 Notes...

Страница 25: ...21 Notes...

Страница 26: ...22 Notes...

Страница 27: ......

Страница 28: ...Sales Customer Service Parts Department 847 966 2260 info thermalcare com 847 966 2260 847 966 9358 fax 847 966 2636 847 966 8560 847 966 9358 fax www thermalcare com info thermalcare com service the...

Отзывы: