8
Example of password deleted, no password entered
C
.
4.
Press the On button to start the unit. The set
point temperature can occur without the need
for a password.
Pump Status Indicator
There are two indicating lights in the Pump icon.
When the pump is on the upper LED will be green.
When the pump overloads the lower LED will be
yellow.
Heating Status Indicator
There are two indicating lights in the Heating icon.
When Heater 1 is on the upper LED will be green.
When Heater 2 is on the lower LED will be green.
Cooling Status Indicator
When the cooling valve is open, the LED in the
Cooling icon will be green.
Low Level Alarm Indicator
The LED in the Low Level icon will be yellow when
the oil level in the reservoir is too low.
Deviation Alarm Indicator
The LED in the Deviation Alarm icon will be green
when the Deviation Alarm is active. The LED will not
be on if the Deviation Alarm has been turned off.
Automatic Timer Status Indicator
The LED in the Timer icon will be green when the
Automatic Start/Stop Timer is active. The LED will
not be on if the Automatic Start/Stop Timer is not
active.
Controller Control Fault Logic
Alarm
Condition
Indication
Tank Low Level Low Level Alarm indicator light on
Temperature display flashing
Alarm horn on and X1 output powered
Temperature
Deviation
Temperature Deviation Alarm indicating light on
Temperature display flashing
Alarm horn on and X1 output powered
Temperature
Sensor Short
Circuit
Temperature display flashing
Alarm horn on and X1 output powered
Temperature
Sensor
Disconnected
Temperature display flashing
Alarm horn on and X1 output powered
Draining the Mold
The temperature control unit is equipped with a
specific program that can automatically cool to
105°F before draining the mold. To initiate a mold
drain sequence depress the Temperature Adjust
button and then immediately depress the On button.
The display will show ‘E’ followed by the actual
temperature in the tank. The cooling solenoid valve
opens and will remain energized unit the tank
temperature drops to 105°F. When the tank
temperature reached 105°F, the alarm horn will
sound to signal the mold is ready for draining.
Once the unit has cooled to 105°F, close the vacuum
adjusting valve and remove the hose on the valve.
The vacuum created will automatically pull the water
through the hoses and the mold back to the unit.
When the unit is finished draining, turn the unit off
by depressing the Off button and remove the hoses.
Start-up
Every unit is factory set to deliver oil in accordance
with the standard operating specifications for that
particular unit. Due to variables involved with
different applications and different installations,
minor adjustments may be required during the initial
start-up to ensure proper operation. Use a qualified
technician to perform the start-up procedure in
sequence. The following serves as a checklist for the
initial start-up and for subsequent start-ups if the
unit is out of service for a prolonged time.
WARNING: This equipment contains hazardous
voltages that can cause severe injury or death.
Содержание Vactherm RV
Страница 1: ......
Страница 2: ......
Страница 17: ...13 Charts and Drawings Figure 1 Pump Performance 60 Hz...
Страница 18: ...14 Figure 2 Cooling Capacity...
Страница 19: ...15 Figure 3 High Voltage Wiring Diagram...
Страница 20: ...16 Figure 4 Low Voltage Wiring Diagram...
Страница 21: ...17 Figure 5 Control Board Details...
Страница 22: ...18 Figure 6 Heating Element Details...
Страница 24: ...20 Notes...
Страница 25: ...21 Notes...
Страница 26: ...22 Notes...
Страница 27: ......