Installation and Operation
Installation Procedures
2-15
Themis Computer
2.1.7
Power Supply
Each load-sharing (N+1 redundant) power supply can be hot-swapped while the sys-
tem is still on and operational.
2.1.7.1 Removing a Power Supply
Perform the following steps to remove a power supply:
1.
Loosen the two screws holding the power supply locking bracket to the chas-
sis (see
A
,
Figure 2-12
). Place the bracket in a safe place for further use.
2.
Put the right index finger on the power supply extraction handle and the right
thumb on the left side of the power supply locking lever (see
B
,
Figure 2-12
).
Figure 2-12.
The RES-12XR3-S for X8DAL-3/i Power Supply Locking Mechanism
Extraction
Handle
Power Supply
Locking Lever
Power LED
AC Input
Phillips Screw Hole
for knurled captive screw
A
... then push locking lever to the right and remove power supply
B
Power supply locking bracket
Knurled captive Phillips screw
Knurled captive Phillips screw
Push lever to the right to release power supply
Phillips Screw Hole
for knurled captive screw
on power supply
locking bracket
Remove power supply locking bracket...
Power Supply
Locking Lever
Содержание RES-12XR3-S
Страница 5: ...iii Themis Computer VersionRevisionHistory Version 1 0 November 2010...
Страница 16: ...RES 12XR3 S for X8DAL 3 i Installation Manual Version 1 0 xiv Themis Computer...
Страница 20: ...RES 12XR3 S for X8DAL 3 i Installation Manual Version 1 0 xviii Themis Computer...
Страница 64: ...RES 12XR3 S for X8DAL 3 i Installation Manual Version 1 0 2 20 Themis Computer...
Страница 99: ...BIOS Setup Utility BIOS Error Beep Codes 3 35 Themis Computer...
Страница 100: ...3 36 Themis Computer RES 12XR3 S for X8DAL 3 i Installation Manual Version 1 0...
Страница 108: ...Themis Computer RES 12XR3 S for X8DAL 3 i Installation Manual Version 1 0 B 4...
Страница 132: ...E 4 Themis Computer RES 12XR3 S for X8DAL 3 i Installation Manual Version 1 0...