7.Commisioning and Operation
• Restore the power from the mains supply breaker or
isolating switch and test for the correct operation.
• Adjust the time dial (fully anti-clockwise), and the Lux
dial should be set to the sun symbol for daylight/night
operation for the purpose of the walk test.
• Allow the PIR to settle down if the attched load is switched
on, this is called warm up mode and can take several minutes
to switch off as long as there is nothing detected in the pickup
area.
• Once the unit is in the OFF position walk across the
detection area, when the PIR is triggered and the load will
turn ON for the minimum set amount of time.
• Once you are happy with the pickup area of the PIR you
can set the Lux dial in the anticlockwise direction to trigger
when dusk is approaching. (This may be best performed in
real time in the evening subject to the users preferance).
• You can also adjust the time dial which will vary the
timeout peroids of the PIR once the pickup area is vacated
of any movement.
Walk Test Procedure
8.Switching from Presence to
to Absence mode
• The PIR will come pre-set to presence mode as standard, if
you require an absence detector continue following this
section. Note that a IR10AB remote will be required to
change modes. Otherwise you can skip to section 9.