background image

5

For the DALI configuration, there are 3 options available:

†

y

"Group assignment (unaddress.)": only DALI EBs without a 

group address are processed.

†

y

"Group assignment (all)": all connected DALI EBs are con-

figured. 

NOTE

: All existing group assignments with group 

number 1 or 2 are deleted.

†

y

"Change group assignment": the next existing EB is 

searched for and selected.

 

After selecting the required group assignment, the 
detector is in the programming mode.

 

A DALI light starts to pulse (random order).

†

†

Use   to assign the required C1 or C2 channel to the DALI 

EB. 

†

†

For further steps, see "Configuring the lighting groups with 

SendoPro".

Configuring the lighting groups using buttons

†

†

Set the <Configuration button/RC> parameter to "Enabled". 

All connected buttons can be used for the configuration.

†

†

Press any button 5 times briefly (< 0.4 s) and press and 

hold once (> 15 s).

 

The LED is switched off.

 

A DALI light starts to pulse (random order).

 

The lighting group is assigned by pressing the approp-
riate button:

†

y

1 x short button press = channel C1

†

y

2 x short button press = channel C2 

 

▻ As confirmation, the light dims to 20% (3 s after the 

last button press). 

 

The next DALI light starts to pulse. One after the other, 
the lighting groups are assigned to all the lights. 

 

If all DALI EBs are assigned to a lighting group, the 

detector terminates the configuration process and 

restarts (startup phase of 30 s). 

 

The detector switches to the normal operating mode 

and the configuration is completed.

 

L

If required, the configuration process can be ended by 

pressing and holding any button for longer than 15 s. The 
detector restarts. 

 

In this case, the system is not ready for operation.

 

L

Instead of using the button, the configuration can also 

be carried out with the ON/OFF buttons on the theSenda 
B/S.

Checking the configuration

The assignment of the lighting groups can be checked by 

switching the individual lighting groups on or off using but-

tons, the SendoPro remote control or the theSenda B/app (for 

SendoPro/theSenda B (app), select the "Control commands" 

menu).

 

L

Changing the lighting group for DALI EBs: use the Sendo-

Pro or the theSenda B/app to change the DALI configura

-

tion via the "Change group assignment" command. 

 

L

With the button: the whole DALI configuration must be 

re-executed.

 

L

A video on configuring the lighting groups can be found at 

https://www.youtube.com/user/TheThebenAG

Switch-on response (configured system)

If voltage is applied, the presence detector goes through two 

phases which are indicated by the LED:

1. Start-up phase (30 s)

 

The red LED flashes in one-second intervals; the lighting 

is switched on with the switch on dimming value.

 

The detector does not react to button commands or to 
the theSenda B/S.

 

If absent, the lighting is switched off after 30 s.

2. Operation

 

The red LED is off. The constant light control or switching 
mode are started.

 

The detector is ready for operation.

7.  Functions

Z1

Z2

 Mixed light measurement 

 Presence detection

 Artificial light

 Button for manual lighting control

 Incident daylight

Lighting channel C1 (broadcast) 

Lighting channel C1, C2 (addressable)

The lighting is controlled by presence and brightness. In case 

of little daylight and presence, the artificial light is switched 

on via the DALI interface and regulated to a constant bright-

ness level.

In case of sufficient daylight or absence, the lighting is swit

-

ched off via the DALI interface. 

Constant light control

 

It compensates for daylight fluctuations by controlling

 

the lighting.

 

The total brightness is kept constant at the required 
brightness level. 

 

The lighting is switched on with the switch on dimming 
value and regulated to the set brightness setpoint value. 

 

Depending on the "school" or "office" configuration type, 

the presence detector responds as follows after manual 
dimming using the buttons: 

"School" configuration type (in school and conference 

rooms):

†

y

Manual dimming stops the constant light control.

†

y

When someone is present, the lighting remains at the 

dimmed value (no brightness influence).

†

y

Switching off and on again leads to control mode.

Содержание thePassa P360-221 DALI UP WH

Страница 1: ...ting disconnect the power supply and ensure that the parts are no longer live Read the entire manual and follow the instructions Prior to commissioning and using the product read the operating instructions 3 Proper use The presence detector is used in passageways stairca ses garages basements and warehouses for controlling the lighting and HVAC The presence detector is intended for indoor installa...

Страница 2: ...tangle of about 2 x 4 m on the floor Depending on the operating mode and the selected detection zone the light measurements are assigned as follows 1 channel broadcast Selection of detec tion zone Lighting channel Light measuring zone Only zone 1 Channel C1 light Zone 1 Only zone 2 Channel C1 light Zone 2 Zone 1 zone 2 Channel C1 light Ø from zone 1 zone 2 2 channel addressable Lighting channel Li...

Страница 3: ...by connecting the P terminals Presence is detected collectively by all the detectors The master measures the brightness processes the button information and controls the lighting The other detectors slaves merely provide presence information e g thePassa P360 Slave UP Master DALI DA DA S1 S2 P N L Slave P N L N L EVG Only for the addressable operating mode Master master parallel switching Several ...

Страница 4: ...t function button Select thePassa P360 221 DALI as the type in the SendoPro Select Menu right function button then Control com mands left function button Open DALI configuration with Open right function button For the DALI configuration there are 3 options available y y Group assignment unaddress only DALI EBs without a group address are processed y y Group assignment all all connected DALI EBs ar...

Страница 5: ...SendoPro remote control or the theSenda B app for SendoPro theSenda B app select the Control commands menu L LChanging the lighting group for DALI EBs use the Sendo Pro or the theSenda B app to change the DALI configura tion via the Change group assignment command L LWith the button the whole DALI configuration must be re executed L LA video on configuring the lighting groups can be found at https...

Страница 6: ...ghting can be switched or dimmed manually via a button A short button press switches the light on or off a long button press dims the light brighter or darker If the lighting is switched off manually it remains switched off as long as people are present The lighting switches on again after the time delay has elapsed Fully or semi automatic device Fully automatic device the lighting is switched on ...

Страница 7: ...tor If the sent value is below the set parameter the LED lights up briefly If the sent value is equal to or above the set parameter the LED lights flickers for 2 s Detection zone The detection area is divided into two independent detec tion zones see 4 Installation detection area For a maxi mum range zone 1 and zone 2 are activated If a limitation of the detection area is required zone 1 or zone 2...

Страница 8: ...t the Brightness measurement value C1 parameter Using the theSenda B remote control Set up the theSenda B according to the drawing and move a few steps away from the measurement location so the lux measurement will not be influenced Press OK A new window with the measured brightness measu rement value is shown If you would like to apply this value Press OK Important Press the send button After thi...

Страница 9: ...assa P360 221 DALI detector type which owns 2 addressable lighting groups L LAfter changing over to the addressable mode the detector is in the emergency mode For programming the lighting groups see chapter 6 Start up Teach in C1 During the teach in process the currently measured bright ness value is adopted as brightness setpoint value C1 Values outside the permitted range are automatically set t...

Страница 10: ...ton RC Selection Enabled Disabled x Parameter Description Can be checked by Sendo Pro the Senda B app Can be changed by Sen doPro theSenda B app Can be changed by the Senda P LED motion display OFF ON x L LThe selection of parameters is limited with the theSenda P Checking the set values With the SendoPro and the theSenda B app parameters can be checked by gradually sending the values to the detec...

Страница 11: ...d or ente red values outside the permitted range are automatically set to the appropriate limit value The calculated room correction factor is adopted The room correction factor can be checked via the Room correction factor C1 C2 parameter for monitoring pur poses The default value is 0 3 theSenda B and the theSenda Plug app Connect the theSenda B with the corresponding theSenda Plug app Select th...

Страница 12: ...da B app DALI configuration Configuration of the lighting group operating mode DALI components Group assignment unaddress Configuration of the unaddressed lighting groups x Group assignment all Configuration of all lighting groups x Change group assignment Change configuration of the lighting groups x End group assignment End configuration of the lighting groups x Change over to broadcast opera ti...

Страница 13: ... can be selected and sent to the detector with the SendoPro and the theSenda B app With the theSenda P the sensitivity can be reduced by one increment by pressing the button or raised by pressing the button Value range Incre ment Sensitivity 1 Very insensitive 2 Insensitive 3 Standard 4 Sensitive 5 Very sensitive L LBy selecting the presence test mode the set sensitivity increment is not changed L...

Страница 14: ... SendoPro theSenda B app Switch off the lighting after the set time 5 min 9 h The lighting is never switched off Never off Staircase light function Value range with SendoPro theSenda B app The lighting can be switched on and off manually OFF The lighting can be switched on but not switched off manually It only switches off after the set time delay ON Dimming speed for manual dimming Value range wi...

Страница 15: ...0 x 5 m IH 3 5 m 100 m2 moving radially 30 x 5 m IH 3 5 m 150 m2 moving tangentially Setting range of brightness setpoint value 10 3000 lux Lighting time delay 10 s 60 min Presence switch on delay 0 s 10 min Presence time delay 10 s 120 min Lighting standby time 0 s 60 min permanently on Standby dimming value 1 25 Lighting control output DALI interface 100 mA max 50 DALI devices base insulation Co...

Страница 16: ...nts and solvents Disposal Dispose of device in environmentally sound manner 10 Dimensions diagrams 86 46 25 40 11 Contact Theben AG Hohenbergstr 32 72401 Haigerloch GERMANY Phone 49 7474 692 0 Fax 49 7474 692 150 Hotline Phone 49 7474 692 369 hotline theben de Addresses telephone numbers etc www theben de ...

Страница 17: ...17 ...

Отзывы: