LED display motion

Motion detection can be displayed using the LED.

Value range (with SendoPro/theSenda B/app)

No display of motion detection.

OFF

The LED is switched on when motion is detected, otherwise it 

remains off.

ON

Presence test

The presence test mode checks the presence detection and 

wiring. The presence test mode can be activated with the 

SendoPro, the theSenda B/app or with the theSenda P (  

button). When the test mode is set, the detector switches 

directly to test mode:

 

Every movement is indicated by the LED.

 

The lighting is switched on where there is movement.

 

If there is no movement, the lighting is switched off after 
10 s.

 

The brightness measurement is deactivated, the detector 
does not respond to brightness.

 

Constant light control is deactivated (switching mode).

 

The standby function is deactivated.

 

The detector responds as in the "fully automatic device" 

configuration type – even if "semi-automatic device" is 

set.

 

Teach-in cannot be activated in test mode.

 

The test mode ends after 10 min. The detector restarts 
(see "Switch-on response").

Light test

The light test mode checks the brightness threshold and  

the constant light control. The light test mode can be activa-

ted with  

the SendoPro or the theSenda B/app. When the  

test mode is set, the detector switches directly to test mode:

 

The LED shows the light test mode (5 seconds ON, 0.3 
seconds OFF).

 

The presence detector responds as in the normal 
operating mode; it only responds faster to brightness/
darkness.

 

To simulate the response, either actuate the blinds or 
illuminate the area under the presence detector.

 

The test mode ends after 10 min. The detector restarts 
(see "Switch-on response").

 

L

Note: Do not use a torch to trigger the presence detector 
to switch! The adaptive light switching thresholds are 

falsified!

Resetting the DALI EBs/DALI relays

The connected DALI EBs/DALI relays are reset to the factory 

settings.

9.  Technical data

Operating voltage

110 – 230 V AC, +10%/-15%

Frequency

50–60 Hz

Upstream protection device:

16 A

Power consumption (without DALI EB)

< 0.4 W

Type of installation

Ceiling installation; flush/

surface mounted or ceiling 

installation

Recommended installation height

2.0–6.0 m

Minimum height

> 1.7 m

Detection area 

horizontal 360°

Maximum range

20 x 5 m (IH 3.5 m)/100 m

2

 

moving radially

30 x 5 m (IH 3.5 m)/150 m

2

 

moving tangentially

Setting range of brightness setpoint 

value

10–3000 lux

Lighting time delay

10 s – 60 min

Presence switch-on delay

0 s – 10 min

Presence time delay

10 s – 120 min

Lighting standby time

0 s – 60 min/permanently on

Standby dimming value

1–25%

Lighting control output

DALI interface 100 mA, max. 50 

DALI devices, base insulation

Connection type

Screw terminals

Max. cable cross-section

max. 2 x 2.5 mm²

Flush-mounted box size

Size 1, Ø 55 mm (NIS, PMI)

Protection rating

IP 20 (IP 54 when installed)

Ambient temperature

–15 °C – 50 °C

CE Declaration of Conformity

This device conforms to the 

safety regulations of the EMC 

Directive 2014/30/EU and of 

Directive 2014/35/EU. 

Troubleshooting 

Fault

Cause

Light does not switch 

on or off if presence 

is detected and in 

darkness

Brightness setpoint value is set too low; detector 

is set to semi-automatic device; light was switched 

off manually using buttons or the theSenda B/S; 

person is not in the detection area; obstacle(s) 

disrupt detection; time delay is too short

Light stays on with 

detection of presence 

despite sufficient 

brightness 

Brightness setpoint value is set too high; the light 

was switched on manually a short while ago using 

buttons or the theSenda B/S (wait 30 min during 

switching mode); detector is in test mode

Light does not switch 

off, or light switches on 

spontaneously when 

no one is present 

Wait for time delay (self-learning);

thermal sources of interference in detection area; 

fan heaters, light bulb/halogen spotlight, moving 

objects (e.g. curtains in front of open windows) 

Button does not work

Device still in the start-up phase; illuminated 

button was used without neutral conductor; 

button not connected to master. 

Light cannot be 

switched off with the 

button

Button is not connected to the detector. Check the 

button wiring. 

Lighting does not 

respond

Short circuit or interruption on DALI bus. Overvol-

tage on DALI bus: disconnect the detector from the 

mains for 1 minute (thermal fuse).

Error flashing 

 

(4 x per second)

Error in self-test; 

device not functional!

LED is switched on and 

flashes 2 x OFF briefly 

every 3 s

The detector has not detected any DALI EBs. Check 

DALI connections. At least 1 DALI EB must be con-

nected to the detector. Short circuit on DALI bus.

Master/slave, master/

master parallel swit-

ching is not working

The detector and button are not connected to the 

same external conductor. 

Содержание thePassa P360-221 DALI UP WH

Страница 1: ...ting disconnect the power supply and ensure that the parts are no longer live Read the entire manual and follow the instructions Prior to commissioning and using the product read the operating instructions 3 Proper use The presence detector is used in passageways stairca ses garages basements and warehouses for controlling the lighting and HVAC The presence detector is intended for indoor installa...

Страница 2: ...tangle of about 2 x 4 m on the floor Depending on the operating mode and the selected detection zone the light measurements are assigned as follows 1 channel broadcast Selection of detec tion zone Lighting channel Light measuring zone Only zone 1 Channel C1 light Zone 1 Only zone 2 Channel C1 light Zone 2 Zone 1 zone 2 Channel C1 light Ø from zone 1 zone 2 2 channel addressable Lighting channel Li...

Страница 3: ...by connecting the P terminals Presence is detected collectively by all the detectors The master measures the brightness processes the button information and controls the lighting The other detectors slaves merely provide presence information e g thePassa P360 Slave UP Master DALI DA DA S1 S2 P N L Slave P N L N L EVG Only for the addressable operating mode Master master parallel switching Several ...

Страница 4: ...t function button Select thePassa P360 221 DALI as the type in the SendoPro Select Menu right function button then Control com mands left function button Open DALI configuration with Open right function button For the DALI configuration there are 3 options available y y Group assignment unaddress only DALI EBs without a group address are processed y y Group assignment all all connected DALI EBs ar...

Страница 5: ...SendoPro remote control or the theSenda B app for SendoPro theSenda B app select the Control commands menu L LChanging the lighting group for DALI EBs use the Sendo Pro or the theSenda B app to change the DALI configura tion via the Change group assignment command L LWith the button the whole DALI configuration must be re executed L LA video on configuring the lighting groups can be found at https...

Страница 6: ...ghting can be switched or dimmed manually via a button A short button press switches the light on or off a long button press dims the light brighter or darker If the lighting is switched off manually it remains switched off as long as people are present The lighting switches on again after the time delay has elapsed Fully or semi automatic device Fully automatic device the lighting is switched on ...

Страница 7: ...tor If the sent value is below the set parameter the LED lights up briefly If the sent value is equal to or above the set parameter the LED lights flickers for 2 s Detection zone The detection area is divided into two independent detec tion zones see 4 Installation detection area For a maxi mum range zone 1 and zone 2 are activated If a limitation of the detection area is required zone 1 or zone 2...

Страница 8: ...t the Brightness measurement value C1 parameter Using the theSenda B remote control Set up the theSenda B according to the drawing and move a few steps away from the measurement location so the lux measurement will not be influenced Press OK A new window with the measured brightness measu rement value is shown If you would like to apply this value Press OK Important Press the send button After thi...

Страница 9: ...assa P360 221 DALI detector type which owns 2 addressable lighting groups L LAfter changing over to the addressable mode the detector is in the emergency mode For programming the lighting groups see chapter 6 Start up Teach in C1 During the teach in process the currently measured bright ness value is adopted as brightness setpoint value C1 Values outside the permitted range are automatically set t...

Страница 10: ...ton RC Selection Enabled Disabled x Parameter Description Can be checked by Sendo Pro the Senda B app Can be changed by Sen doPro theSenda B app Can be changed by the Senda P LED motion display OFF ON x L LThe selection of parameters is limited with the theSenda P Checking the set values With the SendoPro and the theSenda B app parameters can be checked by gradually sending the values to the detec...

Страница 11: ...d or ente red values outside the permitted range are automatically set to the appropriate limit value The calculated room correction factor is adopted The room correction factor can be checked via the Room correction factor C1 C2 parameter for monitoring pur poses The default value is 0 3 theSenda B and the theSenda Plug app Connect the theSenda B with the corresponding theSenda Plug app Select th...

Страница 12: ...da B app DALI configuration Configuration of the lighting group operating mode DALI components Group assignment unaddress Configuration of the unaddressed lighting groups x Group assignment all Configuration of all lighting groups x Change group assignment Change configuration of the lighting groups x End group assignment End configuration of the lighting groups x Change over to broadcast opera ti...

Страница 13: ... can be selected and sent to the detector with the SendoPro and the theSenda B app With the theSenda P the sensitivity can be reduced by one increment by pressing the button or raised by pressing the button Value range Incre ment Sensitivity 1 Very insensitive 2 Insensitive 3 Standard 4 Sensitive 5 Very sensitive L LBy selecting the presence test mode the set sensitivity increment is not changed L...

Страница 14: ... SendoPro theSenda B app Switch off the lighting after the set time 5 min 9 h The lighting is never switched off Never off Staircase light function Value range with SendoPro theSenda B app The lighting can be switched on and off manually OFF The lighting can be switched on but not switched off manually It only switches off after the set time delay ON Dimming speed for manual dimming Value range wi...

Страница 15: ...0 x 5 m IH 3 5 m 100 m2 moving radially 30 x 5 m IH 3 5 m 150 m2 moving tangentially Setting range of brightness setpoint value 10 3000 lux Lighting time delay 10 s 60 min Presence switch on delay 0 s 10 min Presence time delay 10 s 120 min Lighting standby time 0 s 60 min permanently on Standby dimming value 1 25 Lighting control output DALI interface 100 mA max 50 DALI devices base insulation Co...

Страница 16: ...nts and solvents Disposal Dispose of device in environmentally sound manner 10 Dimensions diagrams 86 46 25 40 11 Contact Theben AG Hohenbergstr 32 72401 Haigerloch GERMANY Phone 49 7474 692 0 Fax 49 7474 692 150 Hotline Phone 49 7474 692 369 hotline theben de Addresses telephone numbers etc www theben de ...

Страница 17: ...17 ...

Отзывы: