14
Presence switch-on delay
The contact of the external DALI relay closes when some-
one is present regardless of the brightness and after the set
switch-on delay has elapsed. Buttons and the configuration
type (fully automatic device/semi-automatic device) do not
affect the relay contact.
Value range (with SendoPro/theSenda B/app)
No switch-on delay
0 s
Switch-on delay
30 s – 30 min
Presence time delay
The relay contact of the external DALI relay only opens once
the set time delay has elapsed in periods of absence.
Value range
Adjustable values from Sendo-
Pro/theSenda B/app
10 s – 120 min
Adjustable values from theSenda
P
10 s, 30 s, 60 s, 2 min, 10 min, 20 min,
120 min
Control speed
In the "Control" function, the speed of the constant light con-
trol can be set using the <Control speed> parameter.
Value range (with SendoPro/theSenda B/app)
The response is set ideally. The control function is slow and
barely perceptible.
Standard
The control function is a little faster.
Average
The control function is fast.
Fast
Minimum/maximum dimming value
The lower and upper limits of the lighting channel output
values can be set using the <Minimum dimming value> and
<Maximum dimming value> parameters.
Value range (with SendoPro/theSenda B/app)
Minimum dimming value
1% – 25%
Maximum dimming value
50% – 100%
Switch off brightness
In the Constant light control function, the lighting can be
switched off if the brightness is sufficient. If the lighting is
switched down to the lower limit of the control, the lighting is
switched off after the time set in the <Switch off brightness>
parameter. If the "Never off" option is selected, the lighting is
never switched off (only as long as there are people present).
Value range (with SendoPro/theSenda B/app)
Switch off the lighting after the set time.
5 min – 9 h
The lighting is never switched off.
Never off
Staircase light function
Value range (with SendoPro/theSenda B/app)
The lighting can be switched on and off manually.
OFF
The lighting can be switched on, but not switched off manually. It
only switches off after the set time delay.
ON
Dimming speed for manual dimming
Value range (with SendoPro/theSenda B/app)
Dimming speed when dimming with buttons or the remote
control
- theSenda S
- theSenda B/App
Standard
Fast
Response after man. dimming
With the constant light control function, the response after
manual dimming can be selected using the <Response after
man. dimming> parameter.
Value range (with SendoPro/theSenda B/app)
After manual dimming, the constant light control remains
temporarily active with the current brightness value as the new
brightness setpoint value. After the lighting time delay, the set
setpoint value is restored.
Office
Constant light control is temporarily interrupted by manual dim-
ming. The setpoint remains unchanged.
School
Standby time/standby dimming value
When the standby time is activated, the lighting is not swit-
ched off after the lighting time delay has elapsed, but remains
set to the standby dimming value as an orientation light.
Value range (with SendoPro/theSenda B/app)
Standby time
30 s – 60 min
Standby function (orientation light) is inactive
0 s
Standby function (orientation light) is switched on
permanently
ON
Standby dimming value
1–25%
Configuration button/RC
The teach-in function and the configuration of lighting groups
via the button or the theSenda B/S can be enabled or disab-
led with the <configuration button/RC> parameter.
Value range (with SendoPro/theSenda B/app)
Teach-in and configuration can be executed via the buttons/
remote controls.
Enabled
Teach-in and configuration via the buttons/remote controls
id disabled.
Disabled