Surface-mounted installation

with back box 110A (9070912, 7070913)

5.  Connection

 

!

Use the same external conductor for all detectors and 
buttons.

 

L

Several buttons can be connected to one control input. 

 

L

Illuminated buttons can only be used with a neutral con-
ductor connection. 

 

L

Up to 50 DALI operating devices can be connected to 
each master device. Distribute the DALI operating devices 
evenly over the 3 external conductors.

 

L

In the addressable operating mode, lighting channels C1 
and C2 can be assigned to the required button inputs S1 
and S2 via the remote control.

Individual switching

 

As master, the presence detector detects presence and 
brightness and controls lighting.

Master

DALI

DA+ DA–

S1 S2

EVG

P

*

N

L

N

L

EVG

*Only for the "addressable" operating mode

Master/slave parallel switching

 

If the detection area of a single presence detector is 

insuffi cient (spacious rooms), a maximum of 10 detec-

tors can be connected in parallel by connecting the P 
terminals. 

 

Presence is detected collectively by all the detectors. 

 

The master measures the brightness, processes the 
button information and controls the lighting. 

 

The other detectors (slaves) merely provide presence 
information (e.g. thePassa P360 Slave UP).

Master

DALI

DA+ DA–

S1 S2

P

N

L

Slave

P

N

L

N

L

EVG

*

*Only for the "addressable" operating mode

Master/master parallel switching

 

Several masters can be used. Every master controls 
its lighting groups according to its own brightness 
measurement. 

 

Time delays and brightness setpoint values are set indi-
vidually on each master. 

 

Presence is detected collectively by all the detectors. 

 

Switch up to 10 detectors in parallel.

Master

DALI

DALI

DA+ DA–

S1 S2

P

N

L

N

L

EVG

Master

DA+ DA–

S1 S2

P

N

L

EVG

*

*

*Only for the "addressable" operating mode

Integrating an external DALI relay

 

No more than 1 external DALI relay can be connected on 
one single DALI line (IEC 62386-208).

 

The detector automatically detects the DALI relay.

 

Switch-on delay and time delay can be set using the 
remote control.

Master

DALI RM

r

DALI

DA+ DA–

S1 S2

EVG

P

N

L

N

L

EVG

*

*Only for the "addressable" operating mode

Содержание thePassa P360-221 DALI UP WH

Страница 1: ...ting disconnect the power supply and ensure that the parts are no longer live Read the entire manual and follow the instructions Prior to commissioning and using the product read the operating instructions 3 Proper use The presence detector is used in passageways stairca ses garages basements and warehouses for controlling the lighting and HVAC The presence detector is intended for indoor installa...

Страница 2: ...tangle of about 2 x 4 m on the floor Depending on the operating mode and the selected detection zone the light measurements are assigned as follows 1 channel broadcast Selection of detec tion zone Lighting channel Light measuring zone Only zone 1 Channel C1 light Zone 1 Only zone 2 Channel C1 light Zone 2 Zone 1 zone 2 Channel C1 light Ø from zone 1 zone 2 2 channel addressable Lighting channel Li...

Страница 3: ...by connecting the P terminals Presence is detected collectively by all the detectors The master measures the brightness processes the button information and controls the lighting The other detectors slaves merely provide presence information e g thePassa P360 Slave UP Master DALI DA DA S1 S2 P N L Slave P N L N L EVG Only for the addressable operating mode Master master parallel switching Several ...

Страница 4: ...t function button Select thePassa P360 221 DALI as the type in the SendoPro Select Menu right function button then Control com mands left function button Open DALI configuration with Open right function button For the DALI configuration there are 3 options available y y Group assignment unaddress only DALI EBs without a group address are processed y y Group assignment all all connected DALI EBs ar...

Страница 5: ...SendoPro remote control or the theSenda B app for SendoPro theSenda B app select the Control commands menu L LChanging the lighting group for DALI EBs use the Sendo Pro or the theSenda B app to change the DALI configura tion via the Change group assignment command L LWith the button the whole DALI configuration must be re executed L LA video on configuring the lighting groups can be found at https...

Страница 6: ...ghting can be switched or dimmed manually via a button A short button press switches the light on or off a long button press dims the light brighter or darker If the lighting is switched off manually it remains switched off as long as people are present The lighting switches on again after the time delay has elapsed Fully or semi automatic device Fully automatic device the lighting is switched on ...

Страница 7: ...tor If the sent value is below the set parameter the LED lights up briefly If the sent value is equal to or above the set parameter the LED lights flickers for 2 s Detection zone The detection area is divided into two independent detec tion zones see 4 Installation detection area For a maxi mum range zone 1 and zone 2 are activated If a limitation of the detection area is required zone 1 or zone 2...

Страница 8: ...t the Brightness measurement value C1 parameter Using the theSenda B remote control Set up the theSenda B according to the drawing and move a few steps away from the measurement location so the lux measurement will not be influenced Press OK A new window with the measured brightness measu rement value is shown If you would like to apply this value Press OK Important Press the send button After thi...

Страница 9: ...assa P360 221 DALI detector type which owns 2 addressable lighting groups L LAfter changing over to the addressable mode the detector is in the emergency mode For programming the lighting groups see chapter 6 Start up Teach in C1 During the teach in process the currently measured bright ness value is adopted as brightness setpoint value C1 Values outside the permitted range are automatically set t...

Страница 10: ...ton RC Selection Enabled Disabled x Parameter Description Can be checked by Sendo Pro the Senda B app Can be changed by Sen doPro theSenda B app Can be changed by the Senda P LED motion display OFF ON x L LThe selection of parameters is limited with the theSenda P Checking the set values With the SendoPro and the theSenda B app parameters can be checked by gradually sending the values to the detec...

Страница 11: ...d or ente red values outside the permitted range are automatically set to the appropriate limit value The calculated room correction factor is adopted The room correction factor can be checked via the Room correction factor C1 C2 parameter for monitoring pur poses The default value is 0 3 theSenda B and the theSenda Plug app Connect the theSenda B with the corresponding theSenda Plug app Select th...

Страница 12: ...da B app DALI configuration Configuration of the lighting group operating mode DALI components Group assignment unaddress Configuration of the unaddressed lighting groups x Group assignment all Configuration of all lighting groups x Change group assignment Change configuration of the lighting groups x End group assignment End configuration of the lighting groups x Change over to broadcast opera ti...

Страница 13: ... can be selected and sent to the detector with the SendoPro and the theSenda B app With the theSenda P the sensitivity can be reduced by one increment by pressing the button or raised by pressing the button Value range Incre ment Sensitivity 1 Very insensitive 2 Insensitive 3 Standard 4 Sensitive 5 Very sensitive L LBy selecting the presence test mode the set sensitivity increment is not changed L...

Страница 14: ... SendoPro theSenda B app Switch off the lighting after the set time 5 min 9 h The lighting is never switched off Never off Staircase light function Value range with SendoPro theSenda B app The lighting can be switched on and off manually OFF The lighting can be switched on but not switched off manually It only switches off after the set time delay ON Dimming speed for manual dimming Value range wi...

Страница 15: ...0 x 5 m IH 3 5 m 100 m2 moving radially 30 x 5 m IH 3 5 m 150 m2 moving tangentially Setting range of brightness setpoint value 10 3000 lux Lighting time delay 10 s 60 min Presence switch on delay 0 s 10 min Presence time delay 10 s 120 min Lighting standby time 0 s 60 min permanently on Standby dimming value 1 25 Lighting control output DALI interface 100 mA max 50 DALI devices base insulation Co...

Страница 16: ...nts and solvents Disposal Dispose of device in environmentally sound manner 10 Dimensions diagrams 86 46 25 40 11 Contact Theben AG Hohenbergstr 32 72401 Haigerloch GERMANY Phone 49 7474 692 0 Fax 49 7474 692 150 Hotline Phone 49 7474 692 369 hotline theben de Addresses telephone numbers etc www theben de ...

Страница 17: ...17 ...

Отзывы: