thePassa P360-221 DALI UP WH

2010340

thePassa P360-221 DALI UP GR 

2010341

307421

19.10.2018

Presence detector

EN

1.  General information

 

Passive infrared presence detector for ceiling installation

 

2 operating modes for lighting channel, switchable:  
 – 1 DALI broadcast lighting channel 

(factory setting)

 or 

 – 2 DALI addressable lighting channels

 

2 separate detection zones

 

Rectangular detection area (max. 30 m x 5 m/150 m

2

)

 

Switch or constant light control mode  
with standby function

 

Mixed light measurement suitable for fluorescent lamps 

(FL/PL/ESL), halogen/incandescent lamps and LEDs

 

Adaptable 2-channel light measurement

 

Fully or semi-automatic operation, switchable

 

Reduction of time delay when present briefly (short-term 

presence)

 

1 presence channel for external DALI relay, e.g. for HVAC 
control

 

Accessories

: SendoPro 868-A management remote 

control (optional) (SendoPro for short); theSenda S user 
remote control (optional) (theSenda S for short); the-
Senda P service remote control (optional) (theSenda P 
for short); theSenda B app remote control (optional) and 
the corresponding "theSenda Plug" app (iOS/Android) 
(theSenda B/app for short)

2.  Safety

Assembly and installation should only be carried 

out by a qualified electrician, somebody who has 

completed appropriate professional training and 

has the knowledge and experience necessary to be 

able to recognise and avoid the potential dangers 

posed by electricity.

Before assembly/dismounting, disconnect the 

power supply and ensure that the parts are no 

longer live.

Read the entire manual and follow the instructions.
Prior to commissioning and using the product, read 

the operating instructions.

3.  Proper use

 

The presence detector is used in passageways, stairca-
ses, garages, basements and warehouses for controlling 
the lighting and HVAC.

 

The presence detector is intended for indoor installation.

4.  Installation

Detection area

 

L

The rectangular detection area enables the entire corridor 
to be covered.

 

L

The detection area is divided into two zones. These can 
be activated or deactivated individually by remote control 
(only with 1 DALI broadcast lighting channel).

 

L

Recommended installation height: 2.0 m – 6.0 m.  
The sensitivity of the presence detector decreases when 
the installation height is increased. From a installation 
height of 3.5 m, the detection areas of several detectors in 
the edge zones should overlap. 

 

L

The detection range is reduced as the temperature 
increases.

 

L

The detection area is divided into different areas based on 
the walking direction (frontal/across).

Detection areas: zone 1 and zone 2 (factory setting)

A

r

t

r

t

Zone 1

Zone 2

Installation height 

(A)

Walking persons 

frontal (r)

Walking persons 

across (t)

2.0 m

16 x 3.5 m (56 m

2

)

16 x 3.5 m (56 m

2

)

2.5 m

18 x 4 m (72 m

2

)

22 x 4 m (88 m

2

)

3.0 m

20 x 4.5 m (90 m

2

)

30 x 4.5 m (135 m

2

)

3.5 m

20 x 5 m (100 m

2

)

30 x 5 m (150 m

2

)

4.0 m

20 x 5 m (100 m

2

)

30 x 5 m (150 m

2

)

4.5 m

20 x 5 m (100 m

2

)

30 x 5 m (150 m

2

)

5.0 m

20 x 5 m (100 m

2

)

30 x 5 m (150 m

2

)

5.5 m

20 x 5 m (100 m

2

)

30 x 5 m (150 m

2

)

6.0 m

20 x 5 m (100 m

2

)

30 x 5 m (150 m

2

)

All figures are guidance values.

Содержание thePassa P360-221 DALI UP WH

Страница 1: ...ting disconnect the power supply and ensure that the parts are no longer live Read the entire manual and follow the instructions Prior to commissioning and using the product read the operating instructions 3 Proper use The presence detector is used in passageways stairca ses garages basements and warehouses for controlling the lighting and HVAC The presence detector is intended for indoor installa...

Страница 2: ...tangle of about 2 x 4 m on the floor Depending on the operating mode and the selected detection zone the light measurements are assigned as follows 1 channel broadcast Selection of detec tion zone Lighting channel Light measuring zone Only zone 1 Channel C1 light Zone 1 Only zone 2 Channel C1 light Zone 2 Zone 1 zone 2 Channel C1 light Ø from zone 1 zone 2 2 channel addressable Lighting channel Li...

Страница 3: ...by connecting the P terminals Presence is detected collectively by all the detectors The master measures the brightness processes the button information and controls the lighting The other detectors slaves merely provide presence information e g thePassa P360 Slave UP Master DALI DA DA S1 S2 P N L Slave P N L N L EVG Only for the addressable operating mode Master master parallel switching Several ...

Страница 4: ...t function button Select thePassa P360 221 DALI as the type in the SendoPro Select Menu right function button then Control com mands left function button Open DALI configuration with Open right function button For the DALI configuration there are 3 options available y y Group assignment unaddress only DALI EBs without a group address are processed y y Group assignment all all connected DALI EBs ar...

Страница 5: ...SendoPro remote control or the theSenda B app for SendoPro theSenda B app select the Control commands menu L LChanging the lighting group for DALI EBs use the Sendo Pro or the theSenda B app to change the DALI configura tion via the Change group assignment command L LWith the button the whole DALI configuration must be re executed L LA video on configuring the lighting groups can be found at https...

Страница 6: ...ghting can be switched or dimmed manually via a button A short button press switches the light on or off a long button press dims the light brighter or darker If the lighting is switched off manually it remains switched off as long as people are present The lighting switches on again after the time delay has elapsed Fully or semi automatic device Fully automatic device the lighting is switched on ...

Страница 7: ...tor If the sent value is below the set parameter the LED lights up briefly If the sent value is equal to or above the set parameter the LED lights flickers for 2 s Detection zone The detection area is divided into two independent detec tion zones see 4 Installation detection area For a maxi mum range zone 1 and zone 2 are activated If a limitation of the detection area is required zone 1 or zone 2...

Страница 8: ...t the Brightness measurement value C1 parameter Using the theSenda B remote control Set up the theSenda B according to the drawing and move a few steps away from the measurement location so the lux measurement will not be influenced Press OK A new window with the measured brightness measu rement value is shown If you would like to apply this value Press OK Important Press the send button After thi...

Страница 9: ...assa P360 221 DALI detector type which owns 2 addressable lighting groups L LAfter changing over to the addressable mode the detector is in the emergency mode For programming the lighting groups see chapter 6 Start up Teach in C1 During the teach in process the currently measured bright ness value is adopted as brightness setpoint value C1 Values outside the permitted range are automatically set t...

Страница 10: ...ton RC Selection Enabled Disabled x Parameter Description Can be checked by Sendo Pro the Senda B app Can be changed by Sen doPro theSenda B app Can be changed by the Senda P LED motion display OFF ON x L LThe selection of parameters is limited with the theSenda P Checking the set values With the SendoPro and the theSenda B app parameters can be checked by gradually sending the values to the detec...

Страница 11: ...d or ente red values outside the permitted range are automatically set to the appropriate limit value The calculated room correction factor is adopted The room correction factor can be checked via the Room correction factor C1 C2 parameter for monitoring pur poses The default value is 0 3 theSenda B and the theSenda Plug app Connect the theSenda B with the corresponding theSenda Plug app Select th...

Страница 12: ...da B app DALI configuration Configuration of the lighting group operating mode DALI components Group assignment unaddress Configuration of the unaddressed lighting groups x Group assignment all Configuration of all lighting groups x Change group assignment Change configuration of the lighting groups x End group assignment End configuration of the lighting groups x Change over to broadcast opera ti...

Страница 13: ... can be selected and sent to the detector with the SendoPro and the theSenda B app With the theSenda P the sensitivity can be reduced by one increment by pressing the button or raised by pressing the button Value range Incre ment Sensitivity 1 Very insensitive 2 Insensitive 3 Standard 4 Sensitive 5 Very sensitive L LBy selecting the presence test mode the set sensitivity increment is not changed L...

Страница 14: ... SendoPro theSenda B app Switch off the lighting after the set time 5 min 9 h The lighting is never switched off Never off Staircase light function Value range with SendoPro theSenda B app The lighting can be switched on and off manually OFF The lighting can be switched on but not switched off manually It only switches off after the set time delay ON Dimming speed for manual dimming Value range wi...

Страница 15: ...0 x 5 m IH 3 5 m 100 m2 moving radially 30 x 5 m IH 3 5 m 150 m2 moving tangentially Setting range of brightness setpoint value 10 3000 lux Lighting time delay 10 s 60 min Presence switch on delay 0 s 10 min Presence time delay 10 s 120 min Lighting standby time 0 s 60 min permanently on Standby dimming value 1 25 Lighting control output DALI interface 100 mA max 50 DALI devices base insulation Co...

Страница 16: ...nts and solvents Disposal Dispose of device in environmentally sound manner 10 Dimensions diagrams 86 46 25 40 11 Contact Theben AG Hohenbergstr 32 72401 Haigerloch GERMANY Phone 49 7474 692 0 Fax 49 7474 692 150 Hotline Phone 49 7474 692 369 hotline theben de Addresses telephone numbers etc www theben de ...

Страница 17: ...17 ...

Отзывы: