RAM 712 KNX
room thermostat for surface-mounted and flush-mounted installation
theben
Version: Dec-10 (subject to change) Page 15 of 65
•
Objects 11, 14 "Switching ON/OFF, priority, send value, temperature value, call/store
light scene, send, step / stop, height position , switching LED "
To use inputs E1 and E2 the external interface must be configured on the
settings,
parameter page
as
active
.
The function and type of object are dependent on
function of input
and
object type
parameters.
Table 8
Input function
Function
Description
Switch/key
Switching ON/OFF
Sends 1 bit switching commands in EIS 1
format
Priority
Sends priority telegram in 2 bit format
Send value
Sends a value between 0 and 255
Send temperature
value
Sends a temperature value in 2 byte format
Dimming
Switching ON/OFF
Switches dimmer on and off
Blinds
Step / stop
Sends 1 bit "UP" or "DOWN" telegrams.
Value
Valuator short/long
Sends 2 different 8 bit values depending on
length of time keystroks
Value for light
setting
Call/save light scene via 8 bit telegram
Valuator for blinds
Sends an 8 bit percentage value for positioning
blinds
Control LED
Receives 1 bit telegram for controlling LED
•
Objects 12, 15 "Brighter, darker, brighter/ darker, UP, DOWN, UP/DOWN, slat
position"
The function and the type of object also depend on
input function
parameter.
Table 9
Input function
Function
Description
Switch/key
Not available
Dimming
Brighter , darker
Brighter / darker
4 bit dimming commands for the dimming
actuator in EIS 4 format
Blinds
UP, DOWN,
UP/DOWN
1 bit motion commands for the blinds actuator
in EIS 7 format
Value for blinds
Slat position
Sends 1 byte telegram for positioning slats
Control LED
Not available