RAM 712 KNX
room thermostat for surface-mounted and flush-mounted installation
theben
Version: Dec-10 (subject to change) Page 21 of 65
Continuation:
Designation
Values
Application
Current setpoint value in
comfort mode
Feedback of current setpoint
value via the bus:
Sends actual value (heating
< > cooling)
The setpoint value actually
being controlled is always
sent
(=
Example
with base setpoint
2K:
During heating and cooling,
21 °C and base setpoint value
+ dead zone are sent
respectively (21 °C + 2K =
23°C)
Transmits average value
between heating and cooling
Same value in comfort
operation mode during both
heating and cooling operation,
i.e.:
Base setpoint value + half
dead zone
are transmitted to prevent
occupants being
inconvenienced.
Example
with base setpoint
value 21 °C and dead zone
2K:
Mean value= 21°+1K =22 °C
Although control takes place
at 21°C
or 23°C
Sends the current setpoint
value in cycles
How often should the
currently valid setpoint value
be sent?
Not cyclical, only in the event
of change
Only send in the event of a
change.
Every 2 min, , Every 3 min.
Every 5 min., Every 10 min.
Every 15 min., Every 20 min.
Every 30 min., Every 45 min.
Every 60 min.
Send cyclically