RAM 712 KNX
room thermostat for surface-mounted and flush-mounted installation
theben
Version: Dec-10 (subject to change) Page 64 of 65
7.3.2 Case 2: Heating with 2-point control and cooling with continuous
control
Cooling setpoint value
25 °C
DEAD ZONE 4 K
Heating setpoint value
20 °C
Heating hysteresis 1 K
The dead zone (4 K) is increased by the value of the hysteresis (1K) and offsets the cooling
setpoint value to 25 °C.
7.3.3 Case 3: Heating with continuous control and cooling with 2-point
control
Cooling setpoint value
25 °C
Cooling hysteresis 1 K
DEAD ZONE 4 K
Heating setpoint value
20 °C
The dead zone (4 K) is increased by the value of the hysteresis (1K) and offsets the cooling
setpoint value to 25 °C.
7.3.4 Case 4: Heating and cooling with 2-point control
Cooling setpoint value
26 °C
Cooling hysteresis 1 K
DEAD ZONE 4 K
Heating setpoint value
20 °C
Heating hysteresis 1 K
The dead zone (4 K) is increased by the value of both hysteresis (2K) and offsets the cooling
setpoint value to 26 °C.