RAM 712 KNX
room thermostat for surface-mounted and flush-mounted installation
theben
Version: Dec-10 (subject to change) Page 31 of 65
Continuation:
Designation
Values
Description
Response to rising
edge
For
switching
object type:
How should the channel respond when
an input voltage is applied?
None
Ignore
On
Send ON telegram
Off
Send OFF telegram
By
Reverse channel status
(cf. notching relay)
For
priority 2 bit
object type
None
No response.
Table 18: Telegrams
Function
Value
Priority inactive (00)
Priority inactive
(no control)
0 (00
bin
)
Priority ON (11)
Priority ON
(control: enable, on)
3 (11
bin
)
Priority OFF (10)
Priority OFF
(control: disable, off)
2 (10
bin
)
For
value
object type
Any value between 0 and 255 can be
sent.
These values can also be used
as
percentage values
or as HVAC
commands
None
No response
0 = 0 % (corresponds to
HVAC mode: Auto)
0. 0% or HVAC operating mode
“Auto”
1 (corresponds to HVAC
mode: Comfort)
1 or "comfort" operating mode
2 (corresponds to HVAC
mode: Standby)
2 or "standby" operating mode
3 (corresponds to HVAC
mode: Night-time
temperature reduction)
3 or "night-time temperature
reduction" operating mode
4 (corresponds to HVAC
mode: Frost protection)
4 or "frost protection" operating mode
5 .. 255
any desired value or percentage value
Percentage values are given in 5%
increments, e.g. 13 = 5%, 26 = 10%,
255 = 100 %.
Response to falling
edge
See
response to rising edge
How does the channel respond when
switched off, i.e. by a signal change
from 1 to 0?
See
response to rising edge
.