PlanoSpot 360 DALI-2 S DE manual
25
9.8
Button function
The PlanoSpot 360 DALI-2 S partially supports the button instances defined in IEC 62386 Part
301. The theSenda S or theSenda B user remote controls can be used to dim or switch the
lamps, to control the blinds, or to execute additional functions. The remote control commands
are sent to the PlanoSpot 360 DALI-2 S via the IR interface. The PlanoSpot 360 DALI-2 S sends
this information via the DALI bus to the higher-level controller. Using this information, the
controller can trigger the desired actions.
The "push button input events" and "event timer settings" are partially supported in line with
IEC 62386 Part 301.
The following "events" are supported:
•
Short press
•
Long press start / repeat / stop
1
•
Double press
•
Button free / stuck
1
The following "timer settings" are supported:
•
tDouble
•
tRepeat
1
•
tStuck
1
1)
is not supported by the Scene 1 and 2 buttons.
On button 1
On button 2
On button 3
Off button 3
Off button 2
Off button 1
Scene 2
Scene 1
theSenda B
theSenda S
The PlanoSpot 360 DALI-2 S provides "events" relating to the individual buttons on the DALI
bus in line with IEC 62386 Part 301 via the following instances:
-
Instance 6/8/10 provides events relating to any On button with the configured IR group
address
-
Instance 7/9/11 provides events relating to any Off button with the configured IR group
address
-
Instance 12 provides events relating to the Scene 1 button with the configured IR group
address
-
Instance 13 provides events relating to the Scene 2 button with the configured IR group
address