PlanoSpot 360 DALI-2 S DE manual
13
7
Operation
All settings are configured via the DALI bus or the remote control.
In its initial delivery condition, the PlanoSpot 360 DALI-2 S does not have a short
address.
7.1
Settings via remote control
The theSenda B/app
and theSenda P remote controls can be used to set the following
parameters and control commands.
7.1.1
Parameters
Parameter
Description
Can be
queried via
app
Can be
changed
via app
Can be
changed via
theSenda P
Room correction
factor
Int/2
Integral room correction
factor, instance 2
Range 0.05 ../
0.3
/… 2.00
-
Brightness
measurement
value
Int/2
Lux meter brightness value
For calibrating the integral
brightness measurement,
instance 2
-
-
Room correction
factor
Inn/3
Interior room correction
factor, instance 3
Range 0.05 ../
0.3
/… 2.00
-
Brightness
measurement
value
Inn/3
Lux meter brightness value
For calibrating the interior
brightness measurement,
instance 3
-
-
Room correction
factor
Mid/4
Middle room correction
factor, instance 4
Range 0.05 ../
0.3
/… 2.00
-
Brightness
measurement
value
Mid/4
Lux meter brightness value
For calibrating the middle
brightness measurement,
instance 4
-
-
Room correction
factor
Win/5
Window room correction
factor, instance 5
Range 0.05 ../
0.3
/… 2.00
-
Brightness
measurement
value
Win/5
Lux meter brightness value
For calibrating the window
brightness measurement,
instance 5
-
-
Detection
sensitivity (PIR)
Increment 1 / 2 /
3
/ 4 / 5
All instances
Detection zone
No function in mode 0x00.
-
-
Operating mode Selection of DALI operating
mode
0x00
/ 0x80 / 0x81
-
IR group
address A
IR group address button
instance 6–7
Range:
I
/II/III/ ../VIII/All
-
-