2020-04-27_307458
Manual
DALI-2 presence sensor
PlanoSpot 360 DALI-2 S DE
Страница 1: ...2020 04 27_307458 Manual DALI 2 presence sensor PlanoSpot 360 DALI 2 S DE ...
Страница 2: ...tion 9 5 Connection 11 6 Installation 12 6 1 Ceiling installation 12 7 Operation 13 7 1 Settings via remote control 13 7 2 Settings via the DALI bus 18 7 3 Status messages via the DALI bus 18 8 Light measurement 19 8 1 Light measurement 19 8 2 Determining a value via the DALI bus 20 9 Operating modes 21 9 1 Memory bank 2 occupancy sensor 21 9 2 Memory bank 3 6 light sensors 21 9 3 Memory bank 7 11...
Страница 3: ...other use is considered to be unacceptable The manufacturer does not accept liability for any resulting damages 1 3 Explanation of terms There is a difference between motion detectors and presence detectors Motion detectors can only detect large movements Presence detectors on the other hand can detect even the smallest of movements those made while seated for example DALI 2 sensors can detect bot...
Страница 4: ...pplication controller After start up the PlanoSpot 360 DALI 2 S supply information regarding room occupancy and motion detection as well as brightness values to the higher level controller via the relevant instances The lighting and other systems in a building are controlled on the basis of this information 2 1 Overview of available instances Instance no Instance name Instance type Standard Memory...
Страница 5: ...ion area horizontal 360 Detection area walking 2 7 0 x 7 0 m 49 m2 Detection area seated 3 4 5 x 4 5 m 20 m2 Light measurement approx 10 10 000 lux Protection rating IP 20 Ambient temperature 0 C to 50 C CE Declaration of Conformity This device corresponds to EN 60669 2 5 RCM conformity This device is compliant with the ACMA guidelines DALI conformity IEC 62386 101 103 303 304 1 Surface mounted in...
Страница 6: ...lted to adjust the detection area Test mode for checking function and detection area Configurable detection sensitivity Can be configured via DALI bus or remote control The theSenda S or theSenda B user remote controls can be used to dim or switch the lamps to control the blinds or to execute additional functions via the higher level control Flat design with interchangeable bezel frame in differen...
Страница 7: ...PlanoSpot 360 DALI 2 S DE manual 7 4 3 Dimensions 4 3 1 Ceiling installation with springs 4 3 2 Surface mounted installation with 75B back box ...
Страница 8: ...oSpot 360 DALI 2 S reacts very sensitively to the slightest movements The details refer to very slight movements at table height approx 0 8 m Walking persons From an installation height of 3 m the size of and distance between the active and passive zones increase More pronounced movements are required for clear detection Standard detection zone Installation height A Transverse t Seated s 2 0 m 20 ...
Страница 9: ...ection 7 1 Settings via remote control 4 6 Display visualisation The various statuses of the PlanoSpot 360 DALI 2 S are indicated via a red LED The LED is located under the lens The following statuses are indicated in descending priority IR command accepted 40 ms 2 s long Flickering 12 5 Hz when a valid remote control command is received IR command rejected 400 ms Rejection pulse when an invalid r...
Страница 10: ... address 160 ms repeating every 2 36 s No short addresses assigned to the sensor Presence test LED lights up if motion is detected otherwise switched off applies until presence test is completed Start up phase 1 280 ms 30 s long Start up flashing ...
Страница 11: ...e connected to the DALI line An external DALI supply is required for operation of the PlanoSpot 360 DALI 2 S devices This DALI supply must be able to ensure a reliable power supply for all connected DALI participants A minimum current of 10 mA per PlanoSpot 360 DALI 2 S must be provided ...
Страница 12: ...move the contact protection a and connect the DALI cable with plug in terminal b Implement cable strain relief with cable tie put on contact protection c Open springs and mount detector in ceiling d Pay attention to window interior alignment e Remove installation protection f Align the detection area as required by tilting the optics by 12 to the right I or left II g Snap on the bezel frame provid...
Страница 13: ... Room correction factor Inn 3 Interior room correction factor instance 3 Range 0 05 0 3 2 00 Brightness measurement value Inn 3 Lux meter brightness value For calibrating the interior brightness measurement instance 3 Room correction factor Mid 4 Middle room correction factor instance 4 Range 0 05 0 3 2 00 Brightness measurement value Mid 4 Lux meter brightness value For calibrating the middle bri...
Страница 14: ...tor is a measurement for the difference between brightness measure ments on the ceiling and the work area The brightness value on the ceiling is influenced by the installation location the incidence of light the position of the sun the weather conditions as well as the reflection properties of the room and the furniture With the room correction factor the measured brightness value is adjusted to t...
Страница 15: ...ntered values outside the permitted range are automatically set to the appropriate limit value The calculated room correction factor is adopted The room correction factor can be checked via the Room correction factor Int 2 Inn 3 Mid 4 Win 5 parameter for monitoring purposes The standard value is 0 3 and is suitable for most applications Changes are only sensible in strongly deviating situations De...
Страница 16: ...noSpot 360 DALI 2 S presence sensor the IR group address parameters are assigned to the following button instances IR group address A Button instance 6 and 7 IR group address B Button instance 8 and 9 IR group address C Button instance 10 and 11 IR group address D Button instance 12 IR group address E Button instance 13 Further information can be found in section 9 8 Button function LED display no...
Страница 17: ...30 seconds This phase is indicated by the LED start up phase flashing pattern see section 4 6 Display DALI reset All DALI variables are set to the reset values in accordance with IEC 62386 103 303 304 DALI default All DALI variables are set to the default values in accordance with IEC 62386 103 303 304 Please note This also means that the short address will be reset Factory settings This control c...
Страница 18: ...1 Yes Return the PlanoSpot 360 DALI 2 S for repair 1 Reserve 1 Yes 2 Checksum_Error_Parameter 1 Yes Reset to factory settings 3 Kein_HTS_Code 1 Yes Return the PlanoSpot 360 DALI 2 S for repair 4 EEPROM_Error 1 Yes Return the PlanoSpot 360 DALI 2 S for repair 5 Checksum_Error_DALI 1 Yes Reset to DALI default values 6 Reserve 1 Yes 7 instanceError 1 Yes Further queries are required see below In the ...
Страница 19: ...le of approx 40 below the PlanoSpot 360 DALI 2 S and to the side The central light measurement detects the brightness directly below the Middle brightness value detector A while the other two light measurements detect the brightness close to the window Window brightness value B or in the interior Interior brightness value C The installation location is the reference point for the lighting level Th...
Страница 20: ...he previous variables Example as pseudo code inputValue QUERY_INPUT_VALUE Variable inputValue 64 inputValue QUERY_INPUT_VALUE_LATCH Variable Variable inputValue 4 8 2 2 Evaluating events A light sensor instance event can be triggered cyclically or in the case of certain changes to the value The following steps are necessary in order to present the value that has been received in lux 1 Extract the ...
Страница 21: ...ge ROM 0x01 Indicator byte defined by manufacturer version of the memory bank 0x01 no change ROM 0x02 Memory bank lock byte 0xFF 0xFF NVM 0x03 Detection sensitivity 0x03 0x03 NVM 0x04 0xFF Not implemented Reserved Response NO no change ROM The value range for the Detection sensitivity instance variables is 1 to 5 see section 7 1 1 Parameters 9 2 Memory bank 3 6 light sensors The parameters of ligh...
Страница 22: ...group address button instance 8 9 instance variables is I 0x01 to VIII 0x08 and All 0xFF see also section 7 1 1 Parameters Address Description Default value factory RESET value Memory type 0x00 Address of last position in this MB 0x03 no change ROM 0x01 Indicator byte defined by manufacturer version of the memory bank 0x01 no change ROM 0x02 Memory bank lock byte 0xFF 0xFF NVM 0x03 IR group addres...
Страница 23: ...address button instance 10 11 0x04 0x04 NVM 0x04 0xFF Not implemented Reserved Respons e NO no change ROM Address Description Default value factory RESET value Memory type 0x00 Address of last position in this MB 0x03 no change ROM 0x01 Indicator byte defined by manufacturer version of the memory bank 0x01 no change ROM 0x02 Memory bank lock byte 0xFF 0xFF NVM 0x03 IR group address button instance...
Страница 24: ...pply is restored In accordance with IEC 62386 103 the PlanoSpot 360 DALI 2 S can send a telegram with the information Power Notification following start up if necessary This telegram will contain information about a bus failure or restart of the PlanoSpot 360 DALI 2 S The higher level controller can then decide whether or not to switch on the light following restoration of the bus supply 9 5 Addre...
Страница 25: ...llowing events are supported Short press Long press start repeat stop 1 Double press Button free stuck 1 The following timer settings are supported tDouble tRepeat 1 tStuck 1 1 is not supported by the Scene 1 and 2 buttons On button 1 On button 2 On button 3 Off button 3 Off button 2 Off button 1 Scene 2 Scene 1 theSenda B theSenda S The PlanoSpot 360 DALI 2 S provides events relating to the indiv...
Страница 26: ...if the IR group address set in the relevant memory bank matches the IR group address for the remote control Further information about setting the IR group addresses for the remote control can be found in the operating instructions for the theSenda B or theSenda S ...
Страница 27: ... WH Item no 9070796 Details www theben de en PlanoCover 76 BK Item no 9070592 Details www theben de en PlanoCover 76 SR Item no 9070592 Details www theben de en theSenda B Item no 9070985 Details www theben de en theSenda P Item no 9070910 Details www theben de en ...
Страница 28: ...PlanoSpot 360 DALI 2 S DE manual 28 theSenda S Item no 9070911 Details www theben de en ...
Страница 29: ...LI 2 S DE manual 29 11 Contact Theben AG Hohenbergstr 32 72401 Haigerloch GERMANY Phone 49 7474 692 0 Fax 49 7474 692 150 Hotline Phone 49 7474 692 369 hotline theben de Addresses telephone numbers etc www theben de en ...