IOM CRUZcontrol® Generation2 for NBC
P/N: 1118211
Revision Date: 05/31/2019
Page
22
of
66
Pulse Release
Definition
Upstream Logic Assembly releases for a length of time set by ZS ON (0-20s) and
then accumulates for length of time set by ZS OFF (0-20s).
Configuration When releasing from the discharge end of the conveyor line jumper terminal JP3,
NC - all other jumper terminals should be on pins 1-2.
User Action
Apply a high (24Vdc/120Vac) release signal to TB1, 1-2.
Logic Interrupt
Definition
Breaks release signal from downstream Logic Assembly. Upstream zones are
forced to accumulate despite downstream zone status.
Configuration When using TB1 to release set jumper terminal JP3, 2-3
When using TB4 to release set jumper terminal JP4, 2-3.
User Action
Apply a high signal to TB1 (24Vdc/120Vac) or TB4 (24Vdc). No action required
Zone Delay
Definition
After the downstream zone clears, the upstream zone releases only after the time
set by the Logic Delay potentiometer has expired.
Configuration Adjust Logic Delay potentiometer from 0 to 20 seconds.
User Action
No action required
Slug Interrupt Downstream
Definition
Logic Assemblies downstream of the Function Module will not slug release when
the Slug Release signal goes high.
Configuration JP1, 2-3 all other jumper terminals should be on pins 1-2.
User Action
No action required
Slug Interrupt Upstream
Definition
Logic Assemblies upstream of the Function Module will not slug release when the
Slug Release signal goes high.
Configuration JP2, 2-3 all other jumper terminals should be on pins 1-2.
User Action
No action required