Fire Alarm Examples
Example 1 – Two detection and releasing zones with single detection and actuation
mapping
•
Detection zone 1 goes into alarm due to a linear thermal heat detector fire alarm
o
Actuation occurs on zone 1.
o
The red Fire LED at Alarm Zone 1 is ON
o
The audible alarm sounds
o
Relays 1 & FACP Alarm relays transfer per mapping per fire detection
o
FACP Fault relay transfers as actuators are fired
•
The system cannot be reset from an Alarm condition until the damaged detection
wiring is replaced
•
Press System Reset button
•
If no fire is present,
o
The activated Fire relays 1 & FACP Alarm, will reset if the Fire condition is
cleared
o
If the actuation devices are fired (open) a Fault condition will exist until the
actuation devices are replaced
o
The activated FACP Fault relay – will return to normal when the actuators are
replaced
Figure 7 – Example 1 System Configuration