6.2 Flash Code Troubleshooting Table
Service System
Flash Code
Description
Troubleshooting
1X
Detection Zone 1
•
Check for continuity on detection zone 1.
•
Resistance between terminal strip row A position 1 - 2 should read
470K ohms +/- 23.5K ohms
•
If L.T. 445K ohms, check for moisture intrusion or chaffed wire
•
If G.T. 495K ohms, check for poor connections or damaged wiring
2X
Detection Zone 2
•
Check for continuity on detection zone 2.
•
Resistance between terminal strip row A position 3 - 4 should read
470K ohms +/- 23.5K ohms
•
If L.T. 445K ohms, check for moisture intrusion or chaffed wire
•
If G.T. 495K ohms, check for poor connections or damaged wiring
3X
Manual Release Zone
•
Check for continuity on manual release zone.
•
Resistance between terminal strip row A position 5 - 6 should read
470K ohms +/- 23.5K ohms
•
If L.T. 445K ohms, check for moisture intrusion or chaffed wire
•
If G.T. 495K ohms, check for poor connections or damaged wiring
4X
Actuation Zone 1
•
Ensure actuator(s) is/are connected
•
Check to ensure actuator is intact and not fired
•
Inspect wiring to look for breaks or chafing
•
Take care not to apply voltage to the actuation circuit if using a
multimeter or other device to check for continuity
5X
Actuation Zone 2
•
Ensure actuator(s) is/are connected
•
Check to ensure actuator is intact and not fired
•
Inspect wiring to look for breaks or chafing
•
Take care not to apply voltage to the actuation circuit if using a
multimeter or other device to check for continuity
6X
Auxiliary Switch
•
Check for continuity on auxiliary switch input
•
Resistance between terminal strip row A position 11 - 12 should
read 0 ohms
7X
Actuation Disable
•
Check the actuation disable toggle switch.
•
Unless intentionally switched, the toggle should be in the Normal
position
8X
Local Buzzer
•
Check the buzzer internal wiring to ensure it is connected
•
Verify the buzzer wiring has not been pinched
•
Check the front of the buzzer to verify no damage has taken place
•
Press the Push to Test button to verify buzzer is operating
9X
Ground Fault
•
The Advantage
DC
panel monitors for Ground fault on all field
wiring circuits.
•
To determine if and where a wiring ground fault exists, flip the
Actuation Disable switch then sequentially disconnect each circuit
pair and use a jumper wire between each pair until the Ground
Fault condition disappears. This indicates where the Ground
Fault problem exists.
10X
Abort Switch Fault
•
Check for continuity on the Abort Switch
•
Resistance between terminal strip row A position 13-14 should
read 470K ohms +/- 23.5K ohms
•
If L.T. 445K ohms, check for moisture intrusion or chaffed wire
If G.T. 495K ohms, check for poor connections or damaged wiring
11X
Cross Zone Fault
•
This fault indicates a single detection zone is in Alarm when cross
zoning is programmed.
12X
Temperature Fault
•
This fault indicates a high internal temperature of greater than
120
°
F has been recorded by the Advantage
DC
panel.