Product part no. 830049 Advantage
DC
Dual Zone Fire Control Panel
Manual part no 650.830049 rev. June 13, 2022
Fire Alarm
Flash Code
Description
Troubleshooting
1X
Alarm Zone 1
•
Check zone 1 detection wiring circuit for closure.
•
Check manual release switch circuit for closure.
1X
Alarm Zone 2
•
Check zone 2 detection wiring circuit for closure.
•
Check manual release switch circuit for closure
Other LED
Indicators
Description
Troubleshooting
Power Fault
Power Fault
•
Check to be sure both primary and secondary power
connectors are plugged into the control panel
•
Open the cover of the Advantage
DC
panel and check the
power pc board. If the green LED is ON, then 24 vdc is
available to the panel. If the green LED is OFF, then check
the power source for voltage.
•
Check the date code on the control panel label. If the backup
battery is older than two year from date of installation, replace
the backup battery and replace it with the fresh battery.
Record the battery change date