Walktest Mode 

Walktest Mode can be initiated from the Control Panel, Engineers 
Keypad, 

and

 RICOCHET™ Monitor

 or directly on the expander. 

When in Walktest mode LED’s are enabled and the response time 

for devices between activations is reduced to 10 seconds. Walktest 
will last for 1 hour. 

Control Panel 

Please refer to the Control Panel installation instructions to enter 
Walktest mode. The countdown timer does NOT appear on the 
panel’s keypad. 

Expander 

Option switch 4 toggles Walktest mode on and off. To enable 
Walktest mode from the expander switch Option switch 4 to the ON 
position. To leave Walktest mode turn option switch 4 OFF. The 
countdown timer will be visible on the engineer’s keypad or 

RICOCHET™ Monitor

Engineers Keypad 

See page 12. The countdown timer will appear. 

RICOCHET™ Monitor

 

Press the 

 button. The countdown timer will appear. 

System Status 

Shows various System Details 

1.

 

 

  = Receiver connected to Premier Network 

correctly 



 = Not Connected 

2.

 



 = Firmware version of the Expander 

3.

 



 = Receiver is being Jammed 

4.

 



 = Commission Mode 

5.

 



 = the Wireless Network. (

not the Premier Network

6.

 



 = 

RICOCHET™

 Panel Firmware 

7.

 



 = Not shown on 

Premier 48-W

 

 

 

 

Device Status Indications 

On the top line of the display the following may be seen depending on 
the device and status:- 



 = all devices Front Tamper 

    
  

 



 = all devices Rear Tamper 

    
  

 



 = Pir is Active 

    
  

 

  = Impaq Mag & Impaq Plus Reed Switch 

Open 

    
  

 

 = Impaq Mag Input 1 Active 

    
  

 

 = Impaq Mag Input 2 Active 

    

  

 

 = Impaq Plus Shock Sensor Active 

    
  

 

On the bottom line of the keypad when circumstances dictate the 
following messages may be seen:- 

 

 = Low Battery 

     
   

 

 

  = Receiver has just powered up 

and has not heard from the device 

     
   

 

 

 = Device Fault 

     

 

  

 

 

  = Shows when Device Attributes 

have been updated on the receiver but the 
device has not polled in or been updated by 
the Update Devices menu. This display also 
shows which devices are still out of date if 
the Update Devices broadcast message fails. 

     
   

 

 

= Device has not polled in and 

has been lost on the system. 

     
 

 

 

 

 

   

   

/

 

  

Erase All will delete all devices

and will delete the Wireless Network ID.
You should only delete the Network ID

if the system is conflicting with another

wireless network.



   



   

Bottom line indicates

JAM = Receiver is being jammed
CM = COMMISSION MODE 

/

/

/

Содержание Premier Elite 48-W

Страница 1: ...INS531 Premier 48 W Quick Start Guide...

Страница 2: ...nel 5 Control Panel Layout 6 Control Panel PCB Layout 7 4 Learning Devices 9 5 Expander Engineer Keypad Functions 10 Walktest Mode 12 6 Attributes Operation Modes 13 Polling 13 System Devices 13 Premi...

Страница 3: ...rect setup and operation of the Wireless Network it is important that the following procedures are used when learning and placing devices Learning Devices All devices should be learnt before they are...

Страница 4: ...that it powers If the total current exceeds the Rated Output for the grade you are installing to then an additional power supply is required Connecting AC Mains The AC Mains supply is connected to a...

Страница 5: ...black battery lead to the negative terminal The panel will only become live when the AC Mains is connected or the Battery Kick start button is pressed Connect the AC mains For a complete list of facto...

Страница 6: ...6 INS531 Control Panel Layout DANGE R HIGH VOLTAGE TF M 018 230V 0 0150A R E PLACE ME NT FUS E 0 125A 50 60Hz R ATE D VOLTAG E IS FAC TOR Y S E T AND C ANNOT B E ADJ US TE D Texecom Ltd CLAS S 2 Audi...

Страница 7: ...s are connected 7 Auxiliary 12V Power These terminals are for connecting devices that require 12V power protected by a 0 9A PTC fuse 8 PTC Protection Fuses The following fuses are provided PTC 0 9A Au...

Страница 8: ...ection Serial communications port for connecting to a PC via PC Com USB Com or Com IP for use with RICOCHET Monitor Software 24 Cover Tamper Disable Disables the lid tamper 25 Cover Tamper Provides ta...

Страница 9: ...panel keypad shows the average of the hopped signal strengths Follow the instructions opposite to learn devices to the system once complete follow the instructions in the relevant control panel manua...

Страница 10: ...ved by either pressing the key after each Premier SmartKey change or by pressing the key after scrolling through the devices and making multiple changes Once changed Premier SmartKey attributes will b...

Страница 11: ...ry again If not in commission mode you should wait 15 minutes and try again Walktest Mode Used to initiate stop Walktest Mode If the Walktest broadcast message fails the following will be seen In this...

Страница 12: ...version of the Expander 3 Receiver is being Jammed 4 Commission Mode 5 the Wireless Network not the Premier Network 6 RICOCHET Panel Firmware 7 Not shown on Premier 48 W Device Status Indications On t...

Страница 13: ...r any of the inputs are triggered the zone which the device is mapped too will go active Switch 3 on the expander controls how MAG 2 COM reports to the control panel By default the switch is on and an...

Страница 14: ...he receiver Closing the tamper circuit will activate the LED for a short period of time whilst communication with the receiver is established The LED will flash indicating the device is trying to comm...

Страница 15: ...ed zones on expanders are used correctly and any wireless devices or keypad zones are NOT using the zone numbers associated with the expander address The table below details which zones are fixed for...

Страница 16: ...attery Capacity 1 2Ah to 7Ah Remote Keypads Up to four Expanders 3 8XP Output Modules 2 Zones 0 expandable to 48 Panel Outputs 8 PGM X 2 100mA switched to 0V 500mA switched to 0V Speaker Output Minimu...

Страница 17: ...ucts are designed for reliable trouble free operation Quality is carefully monitored by extensive computerised testing As a result the Premier 48 W is covered by a two year warranty against defects in...

Страница 18: ...Premier 48 W Quick Start Guide 18 INS531 Notes...

Страница 19: ...Premier 48 W Quick Start Guide INS531 19 Notes...

Страница 20: ...Lancashire BB4 4PW England Technical Support UK Customers Tel 08456 300 600 Calls charged at local rate from a BT landline Calls from other networks may vary International Customers Tel 44 1278 68619...

Отзывы: